background image

13

53D9028

c

hiMney

 i

nstallation

1.  Lay out, cut and frame openings through all ceilings and the roof at the point where the chimney will pass 

through.  Unless the chimney is to be offset, the point where the center line of the chimney will pass through 

the ceiling and roof can be determined with a plumb line as shown by Figure 17.  The fireplace should 

be located in the planned installation position.  After the center line is established and a nail is driven to 

mark the point, the opening can be cut if you are satisfied with the chimney location relative to ceiling and 

roof joists and/or any other obstructions.  The roof  opening center line should be marked by driving a 

nail through the roof from underneath that will penetrate the roof and can be located from the rooftop.  If 

the chimney is to penetrate a pitched roof, the hole in the roof must be rectangular instead of square and 

should be sized according to Table1.

2.  Install the firestop spacer as required from beneath the ceiling unless the space above is attic space.  In an 

attic, the firestop spacer should be installed at the floor level of the attic.  You must have joists or headers 

on all four sides of the spacer and use a minimum of four 8-penney nails to secure the spacer.

3.  To install the “L” series chimney sections, insert the male end of the flue, the smallest diameter pipe, into 

the flue outlet of the fireplace and press down until the snap locks engage.  Continue the process, adding 

the chimney sections on top of each other until the chimney is at least six inches above the roof opening 

on all sided.  As the chimney sections are installed, check each joint to make sure it is properly locked to 

the previous section.  If additional strength of the outer pipe joints is desired, you may use two or three 

sheet metal screws placed through the area where the outer pipes overlap one another.  To install these 

screws, drill a 1/8-inch diameter hole through the chimney sections, taking care not to penetrate the inner 

flue pipe.  Warning:  Be very careful when drilling the holes into the outer pipe.  The drill must not penetrate 

the inner stainless steel pipe.

NOTE:  If you intend to have a total fireplace installation of more that 30 feet you must use chimney support 

model LCS at or below 30 feet to support the weight of additional chimney pipe.
To install the chimney support, place the crimped end of the flue and outlet air duct portions into the last sec-

tion of chimney pipe.  Push down until the outside or inlet air duct of the chimney support overlaps and snap 

locks the chimney support into the chimney section.
Nail the support straps tightly to a building frame member or ceiling joist as shown by Figure 18.  You must 

use at least two 8-penney nails per strap.

F

iguRe

 16

NOTE:

FLUE OUTLET SHOULD BE TWO FEET ABOVE ALL PORTIONS OF THE BUILDING

WITHIN TEN FEET AS SHOWN IN THE ILLUSTRATION. THE CHIMNEY MUST NOT

EXTEND MORE THAN 90 INCHES ABOVE THE ROOF WITHOUT ADDITIONAL SUPPORT. 

24" MIN.

36"

24" MIN.

36"

10'

10'

Содержание Majestic SB5400SS

Страница 1: ...SB5400SS Model Residential and Outdoor Fireplace Installation Operation and Maintenance Manual This fireplace is listed by OMNI Test Laboratories for use with L Series chimney system components...

Страница 2: ...ver that failure to install operate and maintain this or any other factory built fireplace properly can result in a house fire or other occurrences that could cause deaths injuries and property damage...

Страница 3: ...lly recommended for use in such areas Intended Product Usage The fireplace is designed to sit directly on a combustible floor The fireplace must be installed with clearances to combustible building ma...

Страница 4: ...g down to close the damper When the fireplace is not in use the damper should be closed to prevent cold air form entering the chimney as well as preventing warm air in the room from escaping up the ch...

Страница 5: ...SETS 15FT MIN HEIGHT 2 30 ELBOWS 21 FT MN HEIGHT 4 30 ELBOWS 86FT MAX HEIGHT CHIMNEY SUPPORT EVERY 25 FT FIRESTOP MODEL LF FS 2 REQUIRES 17x17 FRAMING 54 STORM COLLAR MODEL LC CHIMNEY CAP ROOF FLASHIN...

Страница 6: ...LCF FLAT FLASHING SHOWN OR EQUIVALENT L48 CHIMNEY SECTION 1 REQUIRED 8 FT MIN CLEARANCE AIR SPACE 1 1 2 16 MIN 27 7 8 23 1 2 28 MIN SCREENED OPENING MIN MIN 76 1 2 APPLIES WHEN GLASS DOORS ARE INSTALL...

Страница 7: ...1 8 L 3 6 39 5 16 76 11 16 L SERIES CHIMNEY SECTIONS 47 5 8 47 L48 35 5 8 35 17 5 8 17 11 5 8 11 L18 L36 L12 L18 L18 34 5 8 34 LINEAR GAIN L18 L36 52 LINEAR GAIN 52 5 8 L36 L36 70 5 8 70 LINEAR GAIN 1...

Страница 8: ...of the fireplace required spacing to combustible walls and some suggested fireplace locations When selecting a location choose one that is away from frequently opened doors central heat outlets or re...

Страница 9: ...material free space for the chimney to pass through If the chimney is to pass through living or storage spaces be sure there is adequate space to enclose the chimney to avoid personal contact with or...

Страница 10: ...ACE FLUE OUTLET HEIGHT STORM COLLAR FLASHING 612 OR 1212 LC CHIMNEY CAP FIRESTOP SPACER LF FS 2 2 AIR SPACE CLEARANCE TO COMBUSTIBLES 17 SQUARE OPENING IN JOIST 17 SQUARE OPENING IN JOIST 612 OR 1212...

Страница 11: ...essive strength to support the weight of the covering materials and persons standing on it and insulating qualities equal to or better than the 1 2 covering provided by the H2068 Figure 11 Figure 12 2...

Страница 12: ...developing the hearth extension materials must be firmly fastened in place Wall ties should be screwed to the face of the fireplace and imbedded in the mortar joints of brick stone or other non combus...

Страница 13: ...30 degree chimney incline through ceiling or floor 17 inch firestop spacer One required at each ceiling or floor level 6 12 12 12 pitch flashing for contemporary installation 0 6 12 pitch flashing for...

Страница 14: ...grounding the fireplace and chimney Chimney Installation In order to assure safe and satisfactory performance of the fireplace it is very important to properly install the chimney This is an importan...

Страница 15: ...ess down until the snap locks engage Continue the process adding the chimney sections on top of each other until the chimney is at least six inches above the roof opening on all sided As the chimney s...

Страница 16: ...x 20 17 x 20 5 8 17 x 21 3 8 17 x 22 1 4 17 x 23 ROOF PITCH 0 12 1 12 2 12 3 12 4 12 5 12 6 12 7 12 8 12 9 12 10 12 11 12 12 12 INSTALLATION OF FIRESTOP SPACER AT FLOOR LEVELS INSTALLATION OF FIRESTO...

Страница 17: ...minimum air space clearance to the chimney at the extremities of the offset It is recommended that enclosing material not follow the inclined portions of the chimney Offset Installation Sequence 1 Det...

Страница 18: ...ROOF AND INSTALL ROUND CHIMNEY CAP OR CHIMNEY HOUSING FIRESTOP SPACER DIAGONAL CHIMNEY ENCLOSURE RISE FIRESTOP SPACER 2 AIR SPACE CLEARANCE TO COMBUSTIBLES SUPPORT STRAPS DIAGONAL CHIMNEY ENCLOSURE O...

Страница 19: ...ce and slide the flashing over the chimney Adjust the chimney to assure that the proper minimum clearances are maintained 5 Nail the flashing securely in place with eight nails 6 Seal the crack betwee...

Страница 20: ...1 2 101 104 107 110 112 1 2 116 118 1 2 122 4 0 0 0 0 0 0 0 1 0 1 1 0 1 1 0 2 1 0 2 1 0 2 1 3 2 1 3 2 1 3 2 4 3 2 4 3 2 4 3 5 3 0 0 0 0 0 1 0 0 1 0 0 2 0 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2 3 1 2 0 1 3 0 2...

Страница 21: ...s should be at least 24 inches apart to help prevent smoke from a fireplace in use from being drawn down the chimney of a fireplace that is not in use Additional spacing between caps or staggering the...

Страница 22: ...RESTOP SPACER TO OUTSIDE WALL DUCT EXTENDED TO MISS JOIST SECOND FLOOR LONGER LENGTH OF THE TUBE TO OUTSIDE INSULATION RING INSERT SHORTEST SIDE OF THE TUBE THROUGH THE FIREPLACE OUTER WRAP TO PROPERL...

Страница 23: ...an exterior location which is not likely to be accidentally blocked in any manner The assembly should be located above the snow line to prevent blockage by snow accumulation 3 The combustion air inlet...

Страница 24: ...yond the face of the wall to which the AK 4 inlet air vent will be attached The duct may be cut with a standard pocket knife use FP 4 U duct for maximum efficiency and safety Do not use a combustible...

Страница 25: ...NSI IAS AGA Z21 11 2 unvented room heater is installed in this fireplace a H2853 CANOPY must also be installed Warning Do not operate an unvented gas log set in this fireplace with the chimney removed...

Страница 26: ...ming and attaching the base to the supporting floor will further reduce the possibility of such a crack developing Wall ties should be fastened to the face of the fireplace with sheet metal screws and...

Страница 27: ...BLE MANTEL USE ONLY NON COMBUSTIBLE MATERIALS BELOW TOP OF SPACERS COMBUSTIBLE FRAMING MEMBERS TO TOP OF SPACERS 12 MAX 18 MIN FROM FIREPLACE OPENING TO BOTTOM OF COMBUSTIBLE MANTEL MANUFACTURER RECOM...

Страница 28: ...ore expensive but a little combined with other wood goes a long way Start your fire with a mixture of softwood and hardwood then add some fruit or nut wood for nostalgic aroma Since most woods will no...

Страница 29: ...quipped with glass doors close them DO NOT LEAVE CHILDREN OR PHYSICALLY OR MENTALLY HANDICAPPED OR SENILE PERSONS ALONE WITH A BURNING FIREPLACE You ll need a minimum of three logs preferably four to...

Страница 30: ...on to determine if a creosote buildup has occurred If creosote has accumulated it should be removed to reduce the risk of a chimney fire The chimney cap can be removed for inspection maintenance and c...

Страница 31: ...he installation of the fireplace 4 Do insulate the exterior walls surrounding the fireplace to prevent excessive heat loss from the fireplace 5 Do trim the face of the fireplace only with noncombustib...

Страница 32: ...hing and between the flashing roof 14 Don t dry clothing or other articles near the fireplace 15 Don t store or place flammable liquids gases or pressurized containers near the fireplace 16 Don t negl...

Страница 33: ...of parts needed Technical Service Department MHSC 149 Cleveland Drive Paris KY 40361 www mhsc com 10 9 8 7 6 5 4 3 2 1 SB5400SS PART NO 047647 050918 073104 067514 052874 053127 037391 067517 N A 070...

Страница 34: ...e before you purchase it Blowers or fans which are warranted separately Heat loss due to the passage of heat or air through or around the fireplace Also under our five year coverage we do not pay the...

Страница 35: ...33 53D9028 Attention Appliance Installer Please return these Operating and Installation Instructions to the Appliance for Consumer Use...

Страница 36: ...34 53D9028 AUGUST 2008 53D9028 Rev 3 MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Отзывы: