DVBR Series Direct Vent Gas Fireplace

20000584

Always check for gas leaks with a mild 
soap and water solution applied with a 
brush no larger than 1” (25 mm). Never 
apply soap and water solution with a spray 
bottle. Do not use an open flame for leak 
testing.
The fireplace valve must not be subjected 
to any test pressures exceeding 1/2 psi. 
Isolate or disconnect this or any other gas 

appliance control from the gas line when 
pressure testing.

The gas control is equipped with a captured screw type 
pressure test point, therefore it is not necessary to pro-
vide a 1/8” test point up stream of the control.
When using copper or flex connector use only approved 
fittings. 

Always provide a union

 when using black 

iron pipe so the gas line can be easily disconnected for 
burner or fan servicing. (Fig. 6) See the gas specifica-
tions for pressure details and ratings.

Fig. 9

 EB-1 receptacle.

FP580

FP580

INSTA VENT FREE

EB1 JUNCTION BOX

11/18/97

OUTSIDE

ELECTRICAL BOX

�������������

INSIDE

FRONT

 OF UNIT

Remote Switch Installation

Do not wire the remote ON/OFF wall switch 
for this gas appliance into a 120v power 
supply.

1.  Thread wire through the electrical knockout located 

on either side of fireplace. Do not cut wire or insula-
tion on metal edges. Ensure that wire is protected. 
Run the other end to a conveniently located wall 
receptacle box.  

2.  Attach wire to switch and install switch into recepta-

cle box. Attach cover plate to switch.

3.  Connect wiring to gas valve. (Fig. 7)

W584-9
WIRING DIAGRAM
1/8/99   djt
11/9/99 added thermopile

Thermopile

Fig. 7

 Remote switch wiring diagram for R models.

W584-9

Switch

Gas Valve

EB-1 Electrical Box

The fireplace, when installed, must be elec-
trically connected and grounded in accor-
dance with local codes or, in the absence 
of local codes, with the current CSA C22.1 
Canadian Electrical Code.
For USA installations, follow the local 
codes and the national Electrical Code 
ANSI/NFPA No. 70.

It is strongly suggested that the wiring of 
the EB-1 Electrical Junction Box be carried 
out by a licensed electrician.
Ensure that the power to the supply line 
has been disconnected before commenc-
ing this procedure.

EB1 (Receptacle) Hook-Up
1.  Remove contents from plastic bag. Remove knock-

out in center of electrical box. Remove coverplate 
from fireplace and knockout. Insert connector 
through coverplate, plate and box. Screw nut on 
connector with screws provided (2) to secure the 
coverplate to the plate.

2.  Connect black positive wire to brass screw (polar-

ized side) of receptacle. The white wire is connected 
to chrome screw. The ground wire is connected to 
green ground screw of the receptacle. Fit receptacle 
into electrical box.

3.  Screw cover plate provided to electrical box.
4.  Secure receptacle to fireplace.

FP297A

INSTA VENT FREE

UVHB26 GAS SUPPLY 

7/1/98

FP297A

Fig.  6   

Typical gas supply installation.

1/2” Gas Supply

1/2” NPT X 1/2” Flare Shut-off Valve

3/8” Flex line 
(from valve)

Содержание DVBR36

Страница 1: ...rs instructions If you cannot reach your gas supplier call the re department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE PE...

Страница 2: ...f Applications Installation 20 Venting Components 22 Operating Instructions Glass Information 23 Glass Frame Removal 23 Glass Cleaning 23 Replacement of Ceramic Hearth Panels 23 Installation of Logs 2...

Страница 3: ...d not be used as a drying rack for cloth ing nor should Christmas stocking or decorations be hung in the area of it 9 Under no circumstances should any solid fuels wood coal paper or cardboard etc be...

Страница 4: ...ns and framing dimensions Ref DVBR36 DVBR42 A 40 1016 mm 46 1168 mm B 36 614 mm 36 914 mm C 36 914 mm 42 1067 mm D 23 591 mm 24 616 mm E 6 162 mm 6 162 mm F 6 162 mm 5 137 mm G 20 508 mm 20 508 mm H 6...

Страница 5: ...65 mm L 29 749 mm 29 749 mm M 30 768 mm 30 768 mm Framing Dimensions N 40 1029 mm 40 1029 mm O 41 1041 mm 47 1194 mm P 20 521 mm 20 521 mm Q 64 1645 mm 69 1765 mm R 45 1162 mm 49 1245 mm S 32 822 mm 3...

Страница 6: ...e of Combustion Chamber CFM170 Mantel Leg Mantel Leg from Side Ref Depth Ref of Combusion Opening F 14 356 mm K 14 356 mm G 12 305 mm L 12 305 mm H 10 254 mm M 10 254 mm I 8 203 mm N 8 203 mm J 4 102...

Страница 7: ...Pressures Natural LP Minimum Inlet Pressure 5 5 w c 11 0 w c Maximum Inlet Pressure 14 0 w c 14 0 w c Manifold Pressure 3 5 w c 10 0 w c Gas Speci cations Max Min Gas Input Input Model Fuel Control B...

Страница 8: ...ch and install switch into recepta cle box Attach cover plate to switch 3 Connect wiring to gas valve Fig 7 W584 9 WIRING DIAGRAM 1 8 99 djt 11 9 99 added thermopile Thermopile Fig 7 Remote switch wir...

Страница 9: ...e to replace gasket Fig 12 8 Set insulation in back of unit foil side down 9 Secure outer collar adapter to unit with the round collar on top secure with eight 8 screws NOTE Be sure not to damage any...

Страница 10: ...rmination area Location of Vent Termination It is imperative the vent termination be located observ ing the minimum clearances as shown on the following page General Venting DVBR42 1 Remove the seven...

Страница 11: ...assy I Clearance to service regulator vent outlet 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet...

Страница 12: ...ent pipe The same proce dure must be performed on the vent side Fig 15 Termination clearances Outside Corner Inside Corner Termination Clearances Termination clearances for buildings with combustible...

Страница 13: ...a vertical line to the bottom of the graph 3 Select the indicated dimension and position the replace in accordance with same EXAMPLE A If the vertical dimension from the oor of the unit is 11 feet 33...

Страница 14: ...necessary to seal this connection If a 45 elbow is being used attach the elbow to the appliance in the same manner then at tach the venting to the elbow It is critical that there is no downward slope...

Страница 15: ...bustion air intake and the ue gas exhaust certain limitations as to vent con gurations apply and must be strictly adhered to The Vent Graph showing the relationship between ver tical and horizontal si...

Страница 16: ...ystem is 270 Fig 30 Example Elbow 1 90 Elbow 2 45 Elbow 3 45 Elbow 4 90 Total angular variation 270 1 2 3 4 1 2 3 4 1 2 3 4 270 FP1180 Fig 30 Maximum elbow usage 3 x 90 Elbows 3 x 90 Elbows FP1176 Fig...

Страница 17: ...nt Opening Non combustible Wall 7 Dia 190mm Fireplace Hearth VO584 100 Fig 31 Locate vent opening on wall Step 3 Place replace into position Measure the vertical height X required from the base of the...

Страница 18: ...ck wall Follow Step 1 and 2 on Page 17 Step 3 Install the four 4 spacer springs on the 4 ex vent pipe When installing the spacer springs around the 4 pipe stretch the spring to approximately 15 381 mm...

Страница 19: ...atertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealant caulking supplied around the 4 and 7 snorkel collars 6 Slide the snorkel into the vent pipes and se...

Страница 20: ...er height 10 Apply high temperature sealant to 4 and 7 collars of vent termination and install If there is a room above ceiling level restop spacers must be installed on both the bottom and the top si...

Страница 21: ...0000584 Min 2 610 mm FP1185 Fig 45 Minimum termination to roof clearance TWL101a Twist Lock Pipe 2 8 99 djt 3 5 Sheet Metal Screws per Joint Sealant Storm Collar TWL101a Fig 46 Roof ashing 3 5 Sheet M...

Страница 22: ...odel 7TDVP 20 8 24 Starter Pipe Bulk Model 7FDVP 30 8 30 Flex Pipe Bulk 45o Elbow 7TDV45 for Rear Vent to Vertical Vent or Vertical Horizontal Offsets 90o Transition Elbow 7TDVRT90 for Rear Vent to Ve...

Страница 23: ...on the glass It is therefore recommended the glass be cleaned two or three times with a non ammonia household cleaner and warm water gas replace glass cleaner is recommended After initial use glass sh...

Страница 24: ...t Cross Log over the pin of the Right Rear Log and the pin of the Left Log Fig 3 8 DVBR42 only Place the Right Cross Log over the Right Rear Log and the Right Log as shown Fig 53 When positioned corre...

Страница 25: ...ce person Inspecting the Venting System This appliance venting system was designed and constructed to develop a positive ow adequate to remove ue gases to the outside atmosphere Any foreign objects in...

Страница 26: ...26 DVBR Series Direct Vent Gas Fireplace 20000584 Fig 57 Correct ame appearance for DVBR36 model LG389 Fig 58 Correct ame appearance for DVBR42 model LG387...

Страница 27: ...he pilot follow these instruc tions exactly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor...

Страница 28: ...Line Hooked Up Shutoff Valve Open PILOT STAYS LIT For Air In The Lines Thermopile Needs A Min 325mv Adjust Pilot Flame Height All Wiring Connections Replace Thermopile Thermocouple Needs A Min Of 14mv...

Страница 29: ...umper wire accross terminals at wall switch if burner comes on replace defective wall switch If okay jumper wires across wall switch wires at valve if burner comes on wires are faulty or connections a...

Страница 30: ...rt conversion screw supplied in conversion kit in center of HI LO knob Blue for natural gas red for LP 6 Tighten screw replace cap Valve conversion is complete Valve Conversion SIT Valve 1 Using the T...

Страница 31: ...s not necessary to remove the pilot tube for conversion Pilot Conversion PSE 1 Loosen pilot hood turning counterclockwise using a 7 16 end wrench Fig 67 2 Remove pilot ori ce with needlenose pliers Fi...

Страница 32: ...thermopile millivolt gas valve Most of these components may require only an oc casional checkup and cleaning and some may require adjustment If repair is necessary it should be per formed by a quali e...

Страница 33: ...right to make changes in design materials speci cations prices and discontinue colors and products at any time without notice DVBR36 42 Ref Description DVBR36 DVBR42 1 Log Set Complete 20008744 200087...

Страница 34: ...a Pilot Assembly PSE Nat 20000540 20000540 19b Pilot Assembly Nat SIT 10002264 10002264 20 Electrode Ignitor SIT 52465 52465 21 Sensing Electrode 57886 57886 22 Thermocouple RN RP EN EP 53373 53373 23...

Страница 35: ...ox Base Pan Base Pan Hearth Pan Hearth Pan Hearth Support Hearth Support See Detail Detail FK 12 Fan FK 12 Fan Access Cover EB 1 Re ceptacle Fig 72 FK 12 Fan Kit placement 584 10 Top View Side View Re...

Страница 36: ...s A selection of decorative frame trim kits are available for mounting around the outside of the appliance to en hance its visual effect on the room Installation instruc tions for each decorative fram...

Страница 37: ...37 DVBR Series Direct Vent Gas Fireplace 20000584...

Страница 38: ...38 DVBR Series Direct Vent Gas Fireplace 20000584...

Страница 39: ...poninspection thedamageisfoundtobethefaultofthemanufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this w...

Страница 40: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: