18/24/30VL Unvented Gas Logs

CLEARANCES

The minimum clearance to any combustible item in front of this appliance should be no less 
than 36 inches from the face of the fireplace in which this appliance is installed.
Any  combustible  mantel  present  on  the  fireplace  facing  of  any  fireplace  in  which  this 
appliance is installed must not extend more than 12 inches from the face of the fireplace. 
Also, the combustible mantel must be at least 28 inches above the fireplace opening as 
shown in Figure 2 unless a CABL/CABR fireplace canopy is installed as described.
If a combustible mantel is less than 28 inches above the fireplace opening of any fireplace 
in  which  this  appliance  is  installed,  obtain  a  CABL/CABR  fireplace  canopy  from  your 
appliance dealer and install it on the fireplace according to the instructions furnished with 
the CABL/CABR fireplace canopy. For any fireplace in which this appliance and canopy 
are  both  installed,  the  mantel  extensions  and  corresponding  mantel  clearances  are  as 
shown in Figure 2. The mantel must lie in or above the dashed line shown in Figure 2. (The 
mantel extension is the distance the mantel extends from the fireplace facing. The mantel 
clearance is the distance from the fireplace opening to the bottom of the mantel.)
Any other combustible or noncombustible extension or trim extending from the fireplace 
facing of any fireplace in which this appliance is installed must comply with (1) local codes 
or, in the absence of local codes, with the latest edition of ANSI/NFPA 211 if the fireplace 
is an at-site masonry solid-fuel burning fireplace, or (2) the instructions provided by the 
fireplace  manufacturer  if  the  fireplace  is  a  prefabricated  factory-built  solid-fuel  burning 
fireplace or is a listed ventless firebox enclosure.

CLEARANCE TO COMBUSTIBLES
Front:

  No  less  than  36  inches  from  the  face  of  the  fireplace  in  which  the  appliance  is 

installed.

Mantel:

 Must not extend more than 12 inches from the face of the fireplace and must be 

at least 28 inches above the fireplace opening (unless a CABL/CABR fireplace canopy is 
installed.) Figure 2

12”

12”

8”

2

1

/

2

10”

16”

18”

LG568

mantel clearances

11/08

28"

Mantel 

Clearance

Mantel Extension

Mantel 
Extensions

Canopy

Mantel 
Clearances

LG568

Minimum Mantel Clearances with 
CABL/CABR Canopy

Minimum Mantel Clearance

Figure 2
Mantel Clearances

Содержание 18VL

Страница 1: ...Refer to page 7 WARNINGS If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phon...

Страница 2: ... during and after the installation of the gas log appliance The installer of the gas log appliance should carefully study this manual before installing the appliance All people who will be operating the appliance should also carefully study this manual The installation of this appliance must conform with local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA ...

Страница 3: ...all not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air When properly installed used and maintained this appliance should not produce carbon monoxide in dangerous quantities However since carbon monoxide can be deadly poisonous the installer and all users of this appliance should read and follow these instr...

Страница 4: ... state or local codes to determine if unvented heaters are permitted in your area If unvented heaters are permitted in your area follow the instructions accompanying the ventless firebox enclosure Do not install this appliance in a bedroom or bathroom Do not install this appliance in a fireplace whose flue is serving a separate solid fuel burning appliance If this appliance is installed in a firep...

Страница 5: ... volt 28 000 18 000 24VLNV Milli volt 34 000 25 000 30VLNV Milli volt 34 000 25 000 18VLNT Thermostat 28 000 18 000 24VLNT Thermostat 38 000 25 000 30VLNT Thermostat 38 000 25 000 Propane LPG Note An external regulator is required to reduce supply pressure to a maximum of 13 w c Manual Pressure Milli Volt and T stat Pressure Regulator Pressure Setting 10 0 w c Regulator Pressure Setting 10 w c Gas...

Страница 6: ...tless firebox enclosure It has been design certified for these installations Exception DO NOT install this appliance in a factory built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs WARNING A B C D LG567 min fireplace dims 11 08 Minimum Fireplace Dimensions Model A B C D VL18 19 131 4 25 17 VL24 221 2 131 4 27 17 VL30 251 2 131 4 3...

Страница 7: ...dashed line shown in Figure 2 The mantel extension is the distance the mantel extends from the fireplace facing The mantel clearance is the distance from the fireplace opening to the bottom of the mantel Any other combustible or noncombustible extension or trim extending from the fireplace facing of any fireplace in which this appliance is installed must comply with 1 local codes or in the absence...

Страница 8: ...e control valve in the OFF position for a few minutes until the pilot valve closes should the knob be turned OFF while the pilot is burning This prevents escape of unburned gases The control system also regulates the pilot gas flow to that required for proper operation and provided for shutoff of the gas to the pilot burner and main burners should the oxygen in the area of the appliance be deplete...

Страница 9: ... is approved by the local code authority Unions in gas lines shall be of the ground joint type Compounds used on threaded joints of gas piping must be resistant to the action of liquefied petroleum gas For purpose of input adjustment the gas piping must be of sufficient size to provide a minimum natural gas pressure at the appliance of 5 inches water column or 11 inches for LP gases The maximum in...

Страница 10: ... space must not exceed 76 160 BTU per hour 3 808 divided by 50 x 1 000 equals 76 160 BTU per hour Normal air infiltration into an unconfined space will be adequate to supply the necessary fresh air for proper combustion and ventilation if the building is not constructed unusually tight However if the building is of unusually tight construction additional fresh air from outside will be required for...

Страница 11: ...ou have any questions about fresh air requirements for proper combustion and ventilation of gas fired appliances This appliance is equipped with an ODS oxygen depletion sensor pilot light safety system that turns off the appliance if not enough fresh air is available Never attempt to adjust this safety system It will not operate correctly if tampered with When used without fresh air appliance may ...

Страница 12: ...per ate Connecting Optional Wall Switch or Thermostat 1 Use 18 awg two wire cable 15 feet maximum length 2 At one end of the cable connect both wires to the wall switch or thermostat At the other end connect one wire to TP TH and one wire to TH or connect the wall switch thermostat to the two male 0 25 terminals on the left side of the unit The color of the wires does not matter Figure 19 Wiring D...

Страница 13: ...he wire harness to the wire harness attached to the unit located on the left side Do not let the wires touch the grate or burner 3 Stick velcro pads with self adhesive backing to the side of the remote receiver and to the left side of the unit Figure 20 4 Attach remote receiver with velcro pads Control switch must face forward Figure 18 Install Remote Receiver Note Heat reduces battery life You ca...

Страница 14: ...2 this appliance may be operated as an unvented heater when installed in a solid fuel burning fireplace with the flue damper closed or in an ANSI approved ventless firebox enclosure 2 WARNING If this appliance is to be installed in a previously used fireplace thoroughly clean the interior of the fireplace including any smoke shelf damper frame and chimney flue of soot creosote ashes loose paint or...

Страница 15: ...the gas line carefully with a soap and water or liquid gas leak solution for leaks Bubbles indicate leaks Repair any leaks before proceeding 8 It is most convenient to light the pilot burner and check the operation of the main burners with the logs not in place After carefully checking the gas line for leaks and correcting any found refer to the lighting and operation section of this manual Carefu...

Страница 16: ...econds after the top main burner ignites turn the control knob clockwise to pilot and read the troubleshooting section of this manual for help in determining why ignition did not occur Always follow this procedure when igniting the two main burners 10 With the pilot and main burners in operation check each connection in the gas supply system and control system for leaks with a soap and water or li...

Страница 17: ...bly as shown in Figure 12 Make sure the holes in the middle log fit onto the matching pins projecting from the log support assembly 4 Set the front log on the log support assembly Make sure the holes in the front log fit onto the matching pins projecting from the log support assembly 5 Set the straight left top log onto the back log middle log and front log Make sure the holes in the top log fit o...

Страница 18: ...he log stops The middle log can be identified by the burned area in its center Figure 13 3 Set the front log into position with the locating pads on each side of the middle log blocks Figure 14 4 Set the left and right twigs into their matching recesses Figure 15 LG576 refract back log plcmnt Locator Tabs for Log Placement LG576 Figure 13 Place Back and Middle Logs LG577 refract front log Figure 1...

Страница 19: ...ded the screen shall have an opening s for introduction of combustion air NOTICE This appliance will go through a curing process during its initial first 2 to 3 hours operating period and will emit some smoke and odor Oil and paint odors from a newly installed fireplace or soot creosote and ash odors from a previously used fireplace may also be noticeable during this initial operating period Be pr...

Страница 20: ...r because some gas is heavier than air and will settle on the floor OPERATING INSTRUCTIONS for your safety read before lighting warning If you do not follow these instruction exactly a fire or explosion may result causing property damage personal injury or loss of life WHAT TO DO IF YOU SMELL GAS Do not attempt to light any appliance Do not touch any electric switch do not use any phone in your bu...

Страница 21: ...left side of the heater behind the middle log and on the back of the rear burner If piezo ignitor does not light the pilot refer to Match Lighting Instructions 8 Hold the control knob in for an additional 10 seconds to prevent the ODS pilot from shutting off the gas while the thermocouple is warming up 9 Release the control knob If the knob does not pop out when released stop and immediately call ...

Страница 22: ...may be necessary to press in the control knob for 30 seconds or longer to allow air to bleed out of the gas piping 7 With the control knob pushed in push in and release the piezo ignitor button to light the pilot 8 Continue pushing the control knob in for a further 10 seconds to prevent the flame detector from shutting off the gas while the probe is warming up Release the control knob 9 Turn gas c...

Страница 23: ...If the knob does not pop out when released stop and immediately call your service technician or gas supplier If the ODS pilot will not stay lit after several tries push and turn the gas control knob clockwise to OFF and wait 15 seconds Repeat steps 6 through 9 10 Turn control knob to any position between LOW and HIGH The knob position controls the ther mostat temperature Figure 39 11 The heater is...

Страница 24: ...asoline and any flammable or explosive material 11 Do follow the lighting and operation procedures provided 12 Do periodically inspect the flames of the pilot burner and main burners as described by this manual 13 Do clean the appliance and fireplace as described by this manual 14 Do keep the logs properly placed 15 Do provide ample fresh air when operating the appliance 16 Do keep fireplace glass...

Страница 25: ...ch may have accumulated on each of the logs Do not remove the vermiculite particles glued to some of the logs these particles glow during operation of the appliance to produce ember effect After cleaning replace the logs and resume normal operation of the appliance according to the appliance s lighting and operation instructions After the cleaning operation the flames from the burners may have red...

Страница 26: ...as supply line must be performed by a qualified service person If the appliance is moved even slightly for any reason the gas supply lines must be rechecked for leaks immediately with a soap and water solution or a liquid gas leak detector If leaks are found turn the gas off at the shutoff valve until the leak is corrected Do not attempt to substitute control system components of any type other th...

Страница 27: ...ame Insufficient primary air Clean burner s air intake area Delayed ignition of Pilot flame too small Clean pilot and pilot orifice top main burner Top main burner ports clogged Clean ports Low pressure Check pressure Adjust pressure regulator at gas supply Pilot burner won t Main gas OFF Open shutoff valve ignite or pilot flame Faulty ignition system Check for spark at pilot when pusing ignitor g...

Страница 28: ...28 53D0501 18 24 30VL Unvented Gas Logs replacement parts 530501 18 24 30VL parts 11 08 Refractory Log Set Fiber Log Set 1 2 3 4 5 6 7 8 11 12c 18 12b 12a 16 15 13 19 20 21 23 22 28 27 26 24 25 14 ...

Страница 29: ... 8 Front Cover Millivolt 1 53D0019 53D0019 53D0019 9 10 Manual Millivolt Knob 1 18D0603 18D0603 18D0603 11 Thermostat Knob 1 18D0602 18D0602 18D0602 12a Manual Valve Nat 1 30D0201 30D0201 30D0201 12a Manual Valve LP 1 30D0202 30D0202 30D0202 12b Millivolt Valve Nat 1 14D0467 14D0467 14D0467 12b Millivolt Valve LP 1 14D0468 14D0468 14D0468 12c T Stat Valve Nat LP 1 11V0701 11V0701 11V0701 13 Base W...

Страница 30: ...30 53D0501 18 24 30VL Unvented Gas Logs ...

Страница 31: ...iod of time as this written warranty Some states do not allow limitations on how long an implied warranty lasts so the above limitations may not apply to you 3 MHSC shall not be liable for incidental consequential special or contingent damages you might suffer as a result of its breach of written warranty or anyimplied warranty Some states do not allow the exclusion or limitation of indicental or ...

Страница 32: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com ...

Отзывы: