Majestic • QUARTZ32, QUARTZ36 Installation Manual • 2412-980 Rev. H • 10/16
H
2
H
1
V
2
V
1
Figure 4.12
Top Vent - Horizontal Termination - (continued)
Three Elbows
Note
: Use SLP Series
components only.
Note
: There MUST be a 25%
reduction in total H when
using
fl
ex vent except when
using the simple up and out
installation. See Figure 4.8.
Fire Risk.
• When using SLP-HRC-SS termination cap
on top vented
fi
replaces, a one foot minimum
vertical vent section is required before installing
fi
rst elbow.
WARNING **
V
1
Minimum
H
1
+ H
2
Maxi-
mum
ALL MODELS
V
2
V
1
+ V
2
Min.
90 Elbow **
2 ft.
610 mm
*
*
1/2 ft.**
152 mm
6 ft.
1.8 m
*
*
1-1/2 ft.** 457 mm 10 ft.
3.0 m
*
*
2-1/2 ft.** 762 mm 12 ft.
3.7 m
*
*
3-1/2 ft.
1.1 m
14 ft.
4.3 m
*
*
H
1
+ H
2
MAX. =14 ft. (4.6 m)
V
1
+ V
2
+ H
1
+ H
2
MAX. = 40 ft. (12.2 m)
*No speci
fi
c restrictions on this value EXCEPT V
1
+ V
2
+ H can-
not exceed 40 ft. (12.2 m)
** See warning below