NV360/580 Series

20003565

Troubleshooting

 

SIT NOVA 820 MILLIVOLT VALVE

NOTE: Before troubleshooting the gas control system, be sure external gas shut off is in the "ON" position.

WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.

SYMPTOM

1.  Spark ignitor will not light.

2.  Pilot will not stay lit after 

carefully following lighting 
instructions.

3.  Pilot burning, no gas to 

main burner.

4.  Frequent pilot outage 

problem.

POSSIBLE CAUSES

A.  Defective or misaligned elec-

trode at pilot.

B.  Defective ignitor (push button)

A.  Defective pilot generator (ther-

mocouple), remote wall switch.

B.  Defective automatic valve.

A.  Wall switch or wires defective.

B.  Thermopile may not be gener-

ating sufficient millivoltage.

C.  Plugged burner orifice.
D.  Defective automatic valve op-

erator.

A.  Pilot flame may be too low or 

blowing (high) causing the pilot 
safety to drop out.

B.  Possible blockage of the vent 

terminal.

CORRECTIVE ACTION

Using a match, light pilot. If pilot lights, turn off pilot and 
push the red button again. If pilot will not light - check gap 
at electrode and pilot -should be 1/8" to have a strong 
spark.
Push piezo ignitor button. Check for spark at electrode 
and pilot. If no spark to pilot, and electrode wire is prop-
erly connected, replace ignitor.
Check pilot flame. Must impinge on thermocouple/ther-
mopile. 

NOTE:

 This pilot burner assembly utilizes both - a 

thermocouple and a thermopile. The thermocouple oper-
ates the main valve operation ("ON" and "OFF"). Clean 
and/or adjust maximum flame impingement on thermopile 
and thermocouple.
Turn valve knob to "PILOT". Maintain flow to pilot; millivolt 
meter should read greater than 10 mV. If the reading 
is okay and the pilot does not stay on, replace the gas 
valve. 

NOTE: 

An interrupter block (not supplied) must be 

used to conduct this test.
Check wall switch and wires for proper connections. 
Jumper wire across terminals at wall switch, if burner 
comes on, replace defective wall switch. If okay, jumper 
wires across wall switch wires at valve. If burner comes 
on, wires are faulty or connections are bad.
1.  Be sure wire connections from thermopile at gas valve 

terminals are tight and thermopile is fully inserted into 
pilot bracket.

2.  One of the wall switch wires may be grounded. 

Remove wall switch wires form valve terminals if pilot 
now stays lit, trace wall switch wiring for ground. May 
be grounded to fireplace or gas supply.

3.  Check thermopile with millivolt meter. Take reading at 

thermopile terminals of gas valve. Should read 250-
300 millivolts (minimum 150) while holding valve knob 
depressed in pilot position and wall switch "OFF". 
Replace faulty thermopile if reading is below specified 
minimum.

Check burner orifices for debris and remove.
Turn valve knob to "ON", place wall switch to "ON". Milli-
volt meter should read greater than 100 mV. If the reading 
is okay and the burner does not come on, replace the gas 
valve.
Clean and/or adjust pilot flame for maximum flame im-
pingement on thermopile and thermocouple.

Check the vent terminal for blockage (recycling the flue 
gases).

Содержание NV360 Series

Страница 1: ...e must be per formed by a quali ed installer service agency or the gas supplier What to do if you smell gas Do not try to light any appliance Do not touch any electric switch do not use any phone in y...

Страница 2: ...as Speci cations 6 Gas Inlet Manifold Pressures 6 High Elevations 6 Gas Line Installation 6 Remote Switch Installation 7 Alternate Switch Location 7 EB 1 Electrical Box 7 Install the Venting System Fl...

Страница 3: ...d not be used as a drying rack for clothing nor should Christmas stock ings or decorations be hung in the area of it 9 Under no circumstances should any solid fuels wood coal paper or cardboard etc be...

Страница 4: ...mm 47 1194 mm B 37 953 mm 41 1048 mm C 36 914 mm 42 1067 mm D 24 622 mm 28 724 mm E 7 179 mm 7 179 mm F 6 152 mm 6 152 mm G 1 32 mm 1 32 mm H 19 489 mm 23 591 mm I 5 140 mm 5 140 mm J 25 641 mm 31 79...

Страница 5: ...G 12 305 mm L 12 305 mm H 10 254 mm M 10 254 mm I 8 203 mm N 8 203 mm J 1 38 mm O 1 38 mm Fig 2b Combustible mantel leg minimum installation CFM170 DV Builder Front View O N M L K J F G H I Mantel Le...

Страница 6: ...con rm the nal depth Finishing Noncombustible materials such as brick and tile can be extended over the face of the unit Do not cover the glass door or grille If a trim kit is to be installed brick an...

Страница 7: ...4 9 WIRING DIAGRAM 1 8 99 djt 11 9 99 added thermopile Thermopile W584 9 Fig 5 Remote switch wiring diagram for R models FP1024 alternate remote switch location 1 27 00 djt FP1024 Fig 6 Alternate swit...

Страница 8: ...er frame NOTE A restop is not required at the roof Fig 8 Firestop draftstop positions FP384 FIRESTOP 11 21 96 adapted from IGF53 FP384 Attic Installation Firestop position when area above ceiling is a...

Страница 9: ...in height Up to an 8 ft horizontal vent run can be installed within the vent system using a maximum of two 2 90 degree elbows or four 4 45 degree elbows B Vertical installations up to 40 feet 12m in...

Страница 10: ...monia household cleaner and warm water gas replace glass cleaner is recommended After initial use the glass should be cleaned two or three times during each heating season depending on the circumstanc...

Страница 11: ...logs by placing a small piece of wool on your ngertip and pushing it onto the log Do not place ember material in the inside corners of the front logs Lava Rock The lava rock provided with this replace...

Страница 12: ...n and bathroom 2 Light unit and operate for 5 minutes 3 Hold an ignited match cigarette or smoke match in front of the unit Refer to Figure 17 for location of the draft hood opening 4 Check to make su...

Страница 13: ...down the main burner assembly The sensor is located above the rebox behind the top louvre assembly It is accessible by removing the top louvre assembly CAUTION The rebox Vent Safety Switch sensor and...

Страница 14: ...HITE WHITE WHITE WHITE WHITE WHITE BLACK FP670 NOVA SIT 822 VALVE WIRING DGRM w Honeywell S8600 B Ignition Module 4 30 98 PILOT H I L O H I LO E A P I L O T 1 5 3 4 GREEN MV MVPV PV GND BURNER 24V GND...

Страница 15: ...all around the heater area for gas Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor WHAT TO DO IF YOU SMELL GAS Do not try to light any replace Do not t...

Страница 16: ...height All Wiring connections Replace thermopile Thermocouple needs a minimum 14mV Defective valve Turn to pilot meter should read greater than 100mV If not replace Pilot Lights with Piezo Ignitor YE...

Страница 17: ...le oper ates the main valve operation ON and OFF Clean and or adjust maximum ame impingement on thermopile and thermocouple Turn valve knob to PILOT Maintain ow to pilot millivolt meter should read gr...

Страница 18: ...crews A pressure regulator tower B and the spring and diaphragm assembly C Fig 22 FC107 SIT820 valve conversion 10 03 A B C OFF P I L O T O N FC107 Fig 22 Remove mounting screws pressure regulator tow...

Страница 19: ...Burner Pan NV580 CO110 Front View Top View Front View Fig 27 Install conversion air shutters NOTE It is not necessary to remove the pilot tube for conversion 7 Remove pilot hood by lifting up Fig 28 8...

Страница 20: ...alve Most of these components may require only an oc casional checkup and cleaning and some may require adjustment If repair is necessary it should be per formed by a quali ed technician Logs May Be H...

Страница 21: ...e Log Top Right B29 E7 1f Log Top Center Left E5 1g Log Top Center Right E6 2 Volcanic Rock 20000376 20000376 3 Ember Package 51915 51915 4 Lava Rock Burner 57897 57897 5a Burner Housing Assembly Natu...

Страница 22: ...000616 21d Ori ce Rear Burner Natural 20002498 20003611 22 Switch ON OFF 51842 51842 23a Valve Honeywell VS8421 Natural 10001782 10001782 23b Valve Honeywell VS8421 LP 10001759 10001759 24a Valve SIT...

Страница 23: ...ell Valve not shown 20000062 20000062 45 Vent Safety Switch 10002013 10002013 46a Regulator Head Natural 10001006 10001006 46b Regulator Head LP 10001007 10001007 Fuel Conversion Kits Conversion Kit N...

Страница 24: ...eed control can be installed in an electrical box at normal wall switch height for conve nient access 4 The power supply may be connected in 2 ways Method A Route the 6 1 8m lead tted to the unit to a...

Страница 25: ...H102 rear ceramic support 2 23 99 djt Rear Ceramic Panel Back of Firebox Burner Rear Log Support H102 Fig 37 Rear ceramic panel placement Decorative Frame Trims A selection of decorative frame trim ki...

Страница 26: ...26 NV360 580 Series 20003565...

Страница 27: ...tion the damage is found to be the fault of the manufacturer repairs will be authorized at no charge to the customer parts and or labor Any part and or component replaced under the provisions of this...

Страница 28: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: