Majestic fireplaces FireStage UVHK23RP Скачать руководство пользователя страница 4

4

20008055

This appliance may be installed in an aftermarket, perma-
nently located, manufactured (mobile) home, where not 
prohibited by local codes.
This appliance is only for use with the type of gas indi-
cated on the rating plate.  This appliance is not convertible 
for use with other gases. 

INSTALLER:

 Please leave these instructions with the 

owner.

OWNER:

  Please retain these instructions for future 

reference.

Important Information

WARNING: Any change to this heater or its con-
trols can be dangerous.

IMPORTANT:

 READ THESE INSTRUCTIONS CARE-

FULLY BEFORE INSTALLING.

WARNING:  If the area in which the heater may be 
operated is smaller than that defined as an uncon-
fined space or if the building is of unusually tight 
construction, provide adequate combustion and 
ventilation air by one of the methods described in 
the National Fuel Gas code, ANSI Z223.1/NFPA 54, 
Section 5.3, (or applicable local codes).

NOTES

• 

Due to high temperatures, the appliance should be lo-

cated out of traffic and away from furniture and draperies.

• 

The appliance area must be kept clear and free from com-

bustible materials, gasoline and other flammable vapors and 
liquids.

• 

Children and adults should be alerted to the hazard of 

high surface temperatures and should stay away to avoid 
burns or clothing ignition.

• 

Installation and repair must be done by a qualified ser-

vice person or gas appliance installer.

• 

The appliance must be inspected before use and at least 

annually by a professional service person. More frequent 
cleaning may be required due to excessive lint from carpet-
ing, bedding material, dust and pet hair, etc. It is important 
that the control compartment, burners and circulating air 
passageways of the appliance be kept clean.

• 

DO NOT place clothing or other flammable material on or 

near the appliance.

• 

This appliance must only be used with pressures at the inlet 

as shown in Table 1, Page 13.

• 

The installation must conform with local codes or, in the 

absence of local codes, with the NATIONAL FUEL GAS CODE, 
ANSI Z223.1/NFPA 54, latest edition.

• 

Any safety screen or guard removed for servicing an ap-

pliance must be replaced prior to operating the heater.

• 

The appliance and its appliance main gas valve must be 

disconnected from the gas supply piping system during any 
pressure testing of that system at test pressures in excess of 
1/2 PSIG (3.5 kpa).

• 

The appliance must be isolated from the gas supply piping 

system by closing its equipment shut-off valve during any test-
ing of the gas supply piping system at test pressures equal to or 
less than 1/2 PSIG.

• 

DO NOT

 use this heater in recreational vehicles, bedrooms or 

bathrooms.

• 

If this is the ONLY gas appliance, we recommend a 

minimum 200 pound cylinder with a fill gauge.  Use of a 100 
pound cylinder is not recommended.  Other household gas 
appliances may require the tank size to be larger.  Do not 

operate the vent-free heater if the fuel level in the propane 
tank is below 1/4 full.  Use only with two-stage regulator.

• 

DO NOT

 use this heater if any part of it has been under 

water. Immediately call a qualified technician to inspect the ap-
pliance and replace any part of the control system and any gas 
control which has been under water.

• 

Any outside air ducts in the fireplace shall be permanently 

closed at the time of appliance installation.

• 

Check local, state or city codes to determine if unvented 

heaters are permitted.  If unvented heaters are not per-
mitted, the fireplace chimney damper must be fixed at a 
minimum dimension of 34 sq. inches.  This must be ac-
complished by a clamp or screw on the chimney damper 
to stop at the minimum vent area.  The fireplace must also 
have a minimum vent opening of 34 sq. ins., (Fig. 1)

• 

This appliance may be installed in an after-market* manu-

factured “mobile” home where not prohibited by state or local 
codes.
*After-market:  Completion of sale, not for purpose of re-sale 
from the manufacturer.

• 

OUTSIDE AIR DAMPER OR ASH DUMP (IF PRESENT) 

MUST BE CLOSED AND SEALED.

• 

Young children should be carefully supervised when they 

are in the same room with the appliance.

• 

An unvented room heater having an input rating of more 

than 10,000 btu per hour shall not be installed in a bedroom 
or bathroom.

• 

Keep the burner and control compartment clean.  See main-

tenance instructions in this manual.

• 

The appliance must be operated with glass doors fully 

open.

• 

DO NOT

 operate ceiling fan in room or area with logs when 

logs are on.

• 

Solid fuels (i.e. wood, paper, trash) shall not be burned in a 

masonry or UL 127 factory-built fireplace in which an unvented 
room heater is installed.

WARNING:  This appliance is for installation only in 
a solid-fuel burning masonry or UL 127 factory-built 
fireplace or in a listed ventless firebox enclosure.  It 
has been designed certified for these installations.  
Exception:  DO NOT install this appliance in a fac-
tory-built fireplace that includes instructions stating 
it has not been tested or should not be used with 
unvented gas logs.

WARNING: Do not allow fans to blow directly into the 
fireplace.  Avoid any drafts that alter burner flame pat-
terns.

Содержание FireStage UVHK23RP

Страница 1: ...te or local codes Split Bark Logs Charred Oak Logs This is an unvented gas fired heater It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Section Provisions For Adequate Combustion and Ventilation Air Page 6 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of thi...

Страница 2: ...Wall Switch 10 Gas Connection 11 Typical Gas Line Connection 12 Gas Line Pipe Sizing 13 Gas Pressure Check 13 Lighting Instructions for WRST 14 Lighting Instructions 14 Turning Off Gas to Appliance 14 Lighting Instructions for Millivolt Wall Switch 15 Lighting Instructions for WRD 15 Match Lighting 16 Flame Check 16 Managing Heat Output 16 Maintenance Cleaning 16 Positioning Logs 17 Fireplace Scre...

Страница 3: ...RN UVHK23RP BR BC36 BR BC36i X X X X SHR36 X X X X SR SC36A X X X X BR BC42 BR BC42i X X X X SHR42A 48 52 X X X X SR SC42A X X X X Vent Free Fireplace Series UVHK36RN UVHK31RP UVHK29RN UVHK23RP UVDC36 UVDR36 X X X X UV36 X X UVDC42 UVDR42 X X X X UVSRC36A X X X X UVSRC42A X X X X Log Usage Chart UVHK36RN UVHK31RP UVHK29RN UVHK23RP CVLS18 X X SLS18 X X CVLS24 X X X X SLS24 X X X X CVLS30 X X SLS30 ...

Страница 4: ...ts equipment shut off valve during any test ing of the gas supply piping system at test pressures equal to or less than 1 2 PSIG DO NOT use this heater in recreational vehicles bedrooms or bathrooms If this is the ONLY gas appliance we recommend a minimum 200 pound cylinder with a fill gauge Use of a 100 pound cylinder is not recommended Other household gas appliances may require the tank size to b...

Страница 5: ...ersonal injury do not touch hot surfaces when the appliance is operating Touch only the piezo button and control knob Avoid contact with the front screen canopy or any other part which will be very hot Always ensure that the fireplace screen is in place when the appliance is operating and unless other provisions for combustion air are provided the screen shall have opening s for introduction of com...

Страница 6: ...utdoors 4 Compare the maximum BTU Hr the space can support with the actual amount of BTU Hr used __________ BTU Hr maximum the space can support __________ BTU Hr actual amount of BTU Hr used Example 100 000 BTU Hr max the space can support 89 000 BTU Hr actual amount of BTU Hr used The space in the above example is an unconfined space because the actual BTU Hr used is less than the maximum BTU Hr ...

Страница 7: ...L x W must equal 30 sq in T104 Fig 1 Minimum flue diameter and flue damper positions vent370 2 Ventilation options 3 26 99 djt VO370 2 Fig 2 Ventilation options for confined space Option 1 Vents to Adjoining Room Option 2 Remove Door to Adjoining Room Option 3 Vents to Adjoining Room 12 12 WARNING Air openings that provide fresh air from an adjoining unconfined space shall not be blocked or obstructed...

Страница 8: ...ons on the fireplace floor Drill two holes approximately 1 2 deep Use the two screws to secure the brackets to the fireplace floor Fig 3 Clearances NOTE The following instructions regarding installation clear ances and the use and installation of a canopy apply to use of the appliances as an unvented space heater in permitting jurisdictions When installed as a vented decorative gas appli ance the clea...

Страница 9: ...o wires from the receiver can now be connected to the two outer terminals on the valve making sure it is the two outer terminals and not the center one see Figure 9 With these two connections made return the log set right side up You may now refer to the lighting instructions for use The log set should not be modified to accept any other type of remote control and no guarantee may be made regarding...

Страница 10: ... as shown in Figure 8 The two wires letter A should not be removed or changed Remove switch wires Letter B The two fe male ends of your wire can be connected to the two outer connections just below the screw terminals as shown in Figures 9 10 Now the wall switch can be wired as shown in Figure 11 The red and white wires can be connected to either poles as they carry only millivolt current No groun...

Страница 11: ...lated LP tank can cause an explosion Typical Gas Line Connection for UVHK23RP UVHK29RN UVHK31RP UVHK36RN MODELS Figs 13A and 13B Step 1 With the engine assembly free from the fireplace check tightness of flexible connector fittings You may now either at tach a valve shut off to the flex line or another 1 2 male NPT x flare to the supply line as shown in Figures 13A and 13B CAUTION Use one wrench to hol...

Страница 12: ...ated and emitted into the house Contact the dealer where the unit was purchased High Altitude CSA listed vent free gas fireplaces are tested and approved for elevations from 0 to 2 000 feet 0 610m with no change to the rated input When installing this fireplace at an elevation above 2 000 feet it may be necessary to decrease the input rating by changing the existing burner orifice to a smaller size I...

Страница 13: ...per Tubing Type L 1 000s BTU hr Tubing Length 1 2 5 8 3 4 7 8 Feet 0 43 0 545 0 666 0 785 10 110 206 348 536 20 76 141 239 368 30 61 114 192 296 40 52 97 164 256 50 46 86 146 224 60 42 78 132 203 80 36 67 113 174 100 32 59 100 154 WARNING Use only internally tinned copper tubing If correct copper tubing is not used tubing can deteriorate and develop gas leaks Gas Pressure Check The gas inlet press...

Страница 14: ...s This will cause a spark at the pilot which will ignite the pilot gas 7 Hold in the control knob for 60 seconds to prevent the flame failure detector from shutting off the gas while its probe is warming up 8 Release the control knob If the knob does not pop up when released stop and immediately call your service technician If the pilot will not stay lit after several tries push in and turn the gas...

Страница 15: ...does not pop up when re leased stop and immediately call your service technician If the pilot will not stay lit after several tries turn the gas control knob clock wise to OFF Fig 20 and call your service technician or gas sup plier 9 When the pilot remains lit turn the control knob counterclockwise to the ON position Fig 23 10 Lighting Instructions for Millivolt Wall Switch After the pilot is lit...

Страница 16: ...re not permitted the fireplace vent damper must be locked at a minimum vent area of 34 sq ins Whenever the appliance is operated with the fireplace s flue damper closed glass doors if present must be open and the outside air damper and the ash dump if the fireplace is equipped with either one must be closed Maintenance CLEANING CAUTION Before cleaning or moving logs or other parts of the unit be sure ...

Страница 17: ... peg fits into the hole in the top of the front log The top log when properly positioned establishes the correct spacing between the front and rear logs The left and right twigs are to be placed into the appropriate notches provided in the front and rear logs as shown Figs 26 27 28 When using the Charred Oak log set the rear standoff must be cut to allow the rear log to be positioned properly Fig 3...

Страница 18: ...ING Failure to position the parts in accordance with this diagram or failure to use only parts specifically ap proved with this heater may result in property damage or personal injury Do not alter the logs Charred Oak Logset Fig 28 Charred oak logset correct potitions LG448 ...

Страница 19: ...el quality are pilot not staying lit burners producing abnormal flames and or soot unit back firing when lit 1 Pilot will not light a Air in the line Bleed the line of air b Low gas pressure Have gas company check and adjust c Wrong gas type Have gas company confirm 2 Insufficient pilot flame a Pilot orifice is dirty Clean the dust lint from the unit b Drafty around the unit Eliminate drafts 3 Burners w...

Страница 20: ...efer to Page 3 for correct log set number Right Hand Grate Assy 72006 72006 72006 72006 Left Hand Grate Assy 72005 72005 72005 72005 Front Grate Assy 69649 69649 69305 69305 Base Plate 71149 71149 71150 71150 Ceramic Fiber Base 71579 71579 71578 71578 Rear Burner 76440 76440 72689 72689 Main Burner 69956 69956 69340 69340 Pilot Natural 78167 78167 Pilot Propane 78169 78169 Piezo Ignitor 65180 6518...

Страница 21: ...NSEQUENTIAL DAMAGES EXCEPT TO THE EX TENT PROVIDED BY LAW THERE ARE NO IMPLIED WAR RANTIES WITH RESPECT TO THE GAS APPLIANCE ITS COMPONENTS AND ACCESSORIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ALL OF WHICH ARE HEREBY EXPRESSLY INCLUDED IN NO EVENT SHALL ANY IMPLIED WARRANTY PRESCRIBED BY LAW NOTWITHSTANDING THE FOREGOING EXPRESS EXCLUSION REMAIN IN EF...

Страница 22: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Отзывы: