STR/CVR Series Woodburning Fireplaces

7412961

WARNING:  DO NOT PACK REQUIRED AIR SPACES 
WITH INSULATION OR OTHER MATERIALS.

Mark an outline of the roof hole around the center of the 
point nail.  

NOTE:

 Hole dimensions given in the chim-

ney top installation instructions are 

horizontal 

dimen-

sions; therefore, the hole size must be marked on the 
roof accordingly.
Cover the opening of the installed chimney so debris 
cannot get into the system.
Cut and frame the hole.  It is good practice to use fram-
ing lumber that is the same size as the rafters.  Install 
the frame securely because the chimney top and flash-
ing anchored to the frame must be able to withstand 
heavy winds.

Install Remainder of Chimney Sections

Since you have already preplanned the height of your 
termination according to the 

Ten Foot Rule

, continue to 

install pipe to the predetermined height.
Check the chimney top installation instructions for 
details on how high above the roof top the chimney sec-
tions (all pipes) should extend.

Installing Top Housing or Termination

Follow the installation instructions provided with the  
chimney termination you have selected.

Installing Chimney In a Chase

Refer to Page 5, Figure 4 for an illustration of a typical 
chase installation.

CAUTION:

  Treatment of firestop spacers and construc-

tion of chase may vary with type of building.  These 
instructions are not a substitute for local building codes.  
You 

must

 check your local building codes to determine 

specific requirements for your city or state. 

NOTE:  

Other building materials may be required in addition to 
Firestop Spacers.

Finishing

CAUTION:  

All joints between the finished wall and the 

fireplace surround (top/sides) must be sealed with non-
combustible material to prevent cold air leakage into the 
room.  Only noncombustible material may be applied 
to the facing of the fireplace surround.  (Black painted 
area) (Fig. 20)

Finish Wall

Finish the wall with material of your choice.  

Do not 

install a combustible mantel shelf less than 12" 
(305mm) above the front opening. Do not install a 
mantel face plate less than 6" (159mm) from top of 
fireplace opening. (Fig. 21)  

If a combustible mate-

rial is used below a flat mantel shelf, consult your local 
building codes for minimum clearance from top of fire-
place opening to bottom of mantel shelf.

NOTE:

  No side wall protection is required for fireplaces 

installed at 45° to two (2) side walls (corner installation).
Adjacent combustible side walls that are within 16" 
(406mm) (STR33/36 and CVR36) and 20" (508mm) 
(STR42 and CVR42) of fireplace opening must be pro-
tected with CFM Corporation Wall Shield Model SP40 
or a specifically built wall shield described in Figure 20 
& 24.
Often a decorative surround or vertical portion of the 
mantel is desired. If this is constructed of any combus-
tible material, it must be within the safe zone indicated 
in Figure 24.

FP717

Fig. 20 

  Minimum clearances to combustibles.

Front View

Side View

Standoff

Combustible framing material 

MUST NOT

 

penetrate AIR SPACE (shaded areas).

Air Space Clearances

Only noncombustible

material may be applied 

as facing to the black 

fireplace surround.

Wall 

Shield

Hearth 

Extension

0" Clearance

to Floor

Firestop

OUTER

DOME

���

" (13mm) 

Air Space

to Sides

���

" (13mm) 

air space

 to sides

FP717

STR/CVR

AIR SPACES

9/23/98

1

���

" (38mm) 

������

������

1" 

(51mm) 

�����������

����

Maintain

����

" (13mm) 

air space

to sides 

Содержание CVR36

Страница 1: ...replace For Models STR33 STR36 STR42 CVR36 CVR42 For use in U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 7412961 3 06 Rev 15 Homeowner s Inst...

Страница 2: ...eplaces replace system notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a re hazard Consult loca...

Страница 3: ...3 470mm 508mm 584mm D 49 49 53 1267mm 1267mm 1368mm E 52 52 56 1340mm 1340mm 1442mm F 11 11 13 279mm 279mm 343mm G 8 8 11 203mm 203mm 279mm J 26 29 35 680mm 741mm 894mm Fig 2 CVR Series speci cations...

Страница 4: ...r Standoffs Flue Damper Control Inside Flue Damper Flue Collar Outer Collar Screen Gas Line Knock out Both Sides Brick liner on Sides and Hearth Air Inlet Hearth Wood Grate Firebox Metal Safety Strips...

Страница 5: ...ace and chase parts identi cation FP704 STR from FP528 7 28 98 Termination Cap Storm Collar Pan Flashing Draftstop Finish Wall Batt Insulation cut out around restop Firestop Ceiling Level Outer Dome R...

Страница 6: ...imney exit CVR STR Series Maximum 90 0 Minimum Without Elbows 15 6 With 2 Elbows 17 6 With 4 Elbows 21 0 B Do not use more than 4 elbows per chimney Attach the straps of the return top elbow to a stru...

Страница 7: ...from the chimney to the peak of the roof is 10 3m or less the top of the chimney must be at least 2 610mm above the peak of the roof but never less than 3 914mm in height above the highest point where...

Страница 8: ...ON WHEN INSTALLING A FIREPLACE IN AN INSULATED ENCLOSURE BE SURE ALL REQUIRED AIR SPACES ARE MAINTAINED Page 14 Fig 20 Installation Chimney Supports The chimney system is supported by the replace for...

Страница 9: ...on SK8 2 wall chimney systems STR CVR42 Fireplaces use only model 11CF chimney system Straight Up Chimney Installation To locate the centerline of the ue put the replace in nal position and place a pl...

Страница 10: ...evel The following table gives restop spacer model num bers The inside dimension of the frame must be the same as the hole size selected from Figure 12 in order to provide the required air space 1 38m...

Страница 11: ...lace are noncombustible Eight 8 nailing anges are supplied with the replace found on the replace hearth To level the box and secure it rmly in place remove the nailing anges from the hearth and instal...

Страница 12: ...ngled restop spac ers provide minimum required air space to chimney pipe for ceiling thickness up to 8 203mm When combined thickness of ceiling material ceiling joists and ooring material exceeds 8 20...

Страница 13: ...In Canada an attic insulation shield is required to pre vent attic insulation from contacting the chimney sec tion Framing dimensions for the chimney hole should measure 14 x 14 368 x 368mm SK8 An att...

Страница 14: ...required in addition to Firestop Spacers Finishing CAUTION All joints between the nished wall and the replace surround top sides must be sealed with non combustible material to prevent cold air leaka...

Страница 15: ...2 12 305mm Min 12 305mm Max 6 159mm Min FP721 Fig 21 Fireplace surround ush with nished wall Mantel Clearance No Noncombustible Facing Material Finished Wall Standoff 2 x 4 Stud Noncombustible Mate r...

Страница 16: ...26 K 27 1 2 inches thick 2 CFM Corporation EH2416 K 458 1 inch thick required FP723 Fig 23 Minimum rebox dimensions from combustible materials FP723 STR CVR Side Wall clearances 6 21 98 A A B B C C C...

Страница 17: ...Fig 24 Secure the hearth extension to the oor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the replace hearth and hearth extension with a non...

Страница 18: ...X of listed thickness K of listed material per inch material Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in new required thickness Majestic Safety Strips Must be Overlapped 1 2 Min Minimum...

Страница 19: ...NOTE When installing an ANSI Z21 11 2 ventless ap pliance the fninshing material used for the mantel must be rated at 250 F or greater BTU input of a gas appliance installed in replace should be rate...

Страница 20: ...y End 7554342 7554342 5a Screen Assembly Side four per replace 7554338 7554340 5b Screen Assembly End 7554340 7554340 6 Screen Pulls four per replace 5584139 5584139 7a Firebrick Hearth 3102103 310110...

Страница 21: ...Rod Assembly two per replace 3049122 3030126 3032112 5 Screen Assembly four per replace 7554338 7554338 7554340 6 Screen Pulls four per replace 5584139 5584139 5584139 7a Firebrick Hearth 3100103 310...

Страница 22: ...ing accessories for this appliance are available from your local Majestic Fireplaces distributor Should you need additional information beyond what your distributor can furnish contact CFM Corporation...

Страница 23: ...of a square cap Adaptor required Square Termination Top housing with simulated brick pattern T20B Red Tan or Black Proper adapter must be used Includes ashing Adapter Required adapters for T20B top ho...

Страница 24: ...ical SKCS8 SK8 height and 6 of angled chimney run 11CS 11CF U S Chimney Components cont d Model Number Description Component Attic Insulation Shield Used to prevent insulation from coming in AIS SK SK...

Страница 25: ...25 STR CVR Series Woodburning Fireplaces 7412961...

Страница 26: ...26 STR CVR Series Woodburning Fireplaces 7412961...

Страница 27: ...anty is extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instructi...

Страница 28: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: