Majestic fireplaces CR36L Скачать руководство пользователя страница 14

14

CR Series Woodburning Fireplaces

20001316

Finish Wall

Finish the wall with material of your choice. 

Do not 

install a combustible mantel shelf less than 12” 

(305mm) from the top of the fireplace opening. Do 

not install a mantel face plate less than 6” (159mm) 

from top of fireplace opening. (Fig. 18)

 If a combus-

tible material is used below a flat mantel shelf, consult 

your local building codes for minimum clearance from 

top of fireplace opening to bottom of mantel shelf.
When finishing the fireplace, a combustible facing ma-

terial (i.e. drywall or wood paneling) may be installed 

at the fireplace surround top as shown in Figure 20. 

This material may rest on the ledge brackets (brackets 

on the front and side edges of the fireplace), but must 

NOT be notched to fit around them. (Fig. 20)
All joints (top, bottom and sides), where the wall or 

decorative facing material meets the fireplace sur-

round must be completely sealed with a noncombus-

tible material. (Fig. 17, 18, 20)
Only noncombustible material may be applied as fac-

ing to the black fireplace surround. 

When finishing the fireplace, never obstruct or 

modify the air inlet grille in any manner.
When finishing the fireplace, use the material of 

your choice. If you decide to cover the fireplace 

surround, noncombustible materials must be 

used.

Side Wall Protection

All walls constructed closer than 16” (406mm) from the 
fireplace opening must be protected with CFM Corpo-
ration Wall Shield Model SP40 or a built-up wall shield 
described in Figure 17.

(ANY PERPENDICULAR SIDE WALL MUST NOT BE 
CLOSER THAN 40” (1016mm) TO THE OPEN END 
OF AN OPEN END FIREPLACE.)

The built-up wall shield design described in Figure 17 
is an alternate method for adding protection to side 
walls and can be used in place of the SP40 with the 
same wall clearances specified for the SP40.

EXAMPLES OF INSULATION:

1.  Manville - CERAFORM 126, K = .27, 1/2” thick 

required.

2.  CFM Corporation Building Products - EH2416, K = 

.458, 1” thick required.

Hearth Installation

A hearth extension is required to protect a combustible 
floor in front of the fireplace. Refer to Figure 20 for 
minimum dimensions and mounting detail.

NOTE:  Hearth Extension must not cover the air 
inlet opening of a fireplace.

The hearth extension described in Figure 20 must be a 
durable non-combustible material with a minimum (to-
tal) Rt value of 1.09; refer to Figure 21 for examples. 
The overall height (above a combustible floor), depth 
and width must be as indicated, with the extension 
centered to the fireplace opening.
The top of the insulation material must be covered with 
a noncombustible decorative covering 

or

 a piece of 

.018” minimum sheet metal, to protect hearth exten-
sion material. (Fig. 23)
Secure the hearth extension to the floor to prevent 
shifting, using trim molding or other similar means at 
three (3) outer edges. Seal crack between the fire-
place hearth and hearth extension with a noncombus-
tible material. (Figs. 22,23)

WARNING:  HEARTH EXTENSION MUST BE 
INSTALLED IN ACCORDANCE WITH FIGURES 20 
AND 21.

Alternate noncombustible materials may be used pro-
viding the (total) thermal resistance (Rt value) of the 
alternate material employed is greater than or equal to 
R =  1.09. Thermal resistance (R) or thermal conduc-
tivity (K), may be obtained from manufacturer of the 
material.  Factors are related by the formula K = 1/R.
T = given thickness

R = thermal resistance for a given thickness (T)

K = thermal conductivity
Noncombustible material with a lower R value may 
be used, provided thickness of material is sufficiently 
greater to maintain an equivalent (total) thermal resis-
tance (Rt).

Example of Determining Hearth Extension 
Equivalents

To determine the thickness required for any 

new

 mate-

rial:

NEW 

  K of new material (per inch)    thickness

required  = 

  X   of listed

thickness    K of listed material (per inch)    material

Example for Common Brick

T (new) = 5.0/0.458 x .5 in. = 

5.46 in.

 (new required 

thickness).

Содержание CR36L

Страница 1: ...ls CR36R CR36L CR Series Corner Woodburning Fireplace DO NOT DISCARD THIS MANUAL Retain for future use For use in U S Canada Underwriter s Laboratories Report No MH6018 20001316 3 06 Rev 13 Homeowner...

Страница 2: ...sembly with a CFM Corporation replace system notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a...

Страница 3: ...21 545mm 6 172mm 36 914mm 40 1019mm 41 1054mm Gas Line Access 9 241mm 8 203mm 7 178mm 14 362mm 4 Dia Outside Air Collar Rough Opening Height CR36R L Series Woodburning Fireplace Fig 1 CR36R L Series...

Страница 4: ...n Grate Firebox Outside Air Control Outside Air Cover Plate Gas Access See Figure 20 on page 15 for clearance information Outer Dome Ceiling Level Firestop Batt Insulation cut out around restop Fig 2...

Страница 5: ...himney exit at top CR36L R Series Maximum 90 0 Minimum Without elbows 14 0 With 2 elbows 15 0 With 4 elbows 21 0 B Do not use more than four elbows per chimney Attach the straps of the top elbows to a...

Страница 6: ...on the surface of the roof a distance of 10 3m from the chimney in a horizontal plane The top of the chimney must be at least 2 610mm above the reference point but never less than 3 914mm in height a...

Страница 7: ...ssible Insulate base of replace with a non combus tible insulation rated for a minimum of 300 F Insulating is very important for outside wall installations over a concrete slab If replace is installed...

Страница 8: ...ox and indicate dimension X to locate the side wall framing Fig 8 Be sure to observe clear FP555CR Insulation 2 26 99 djt Hard Flat Surface Insulation Platform FP555CR Fig 7 Insulation between platfor...

Страница 9: ...trip must be fabricated and used to protect combustible surfaces in front of the replace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1...

Страница 10: ...igure 15 for appro priate spacer orientation Installing the Firestop Spacer in the Ceiling Hole A restop spacer is used to keep pipe spaced properly and required for safety Nail the restop spacer at e...

Страница 11: ...he framing hole Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Ru...

Страница 12: ...predetermined height Check the chimney top installation instructions for details on how high above the roof top the chimney sections all pipes should extend Installing Top Housing or Termination Foll...

Страница 13: ...159mm Min 12 305mm Max 12 305mm Max 7 16 1 1 Fig 18 Fireplace surround ush with nished wall FE101a Combustible Mantel and Trim Mantel Clearance No Noncombustible Facing Material Mantel Clearance with...

Страница 14: ...ille CERAFORM 126 K 27 1 2 thick required 2 CFM Corporation Building Products EH2416 K 458 1 thick required Hearth Installation A hearth extension is required to protect a combustible oor in front of...

Страница 15: ...bustible deco rative covering OR 018 Min Sheet Metal Combustible Floor Minimum Insulation Value R Fireplace Hearth FS108 Sealing Sides 6 22 99 djt Safety Strips must be Overlapped Min Seal Crack Betwe...

Страница 16: ...seal between the pipe and the tube NOTE The gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from the replace side NOTE Local codes m...

Страница 17: ...83 5a Screen Rod Finished 90 7554156 7554155 5b Screen Rod Finished Straight 7554181 7554181 6 Screen Pulls two per replace 5584139 5584139 7a Firebrick Side 20000793 20000794 7b Firebrick Back 200007...

Страница 18: ...f the system If you use an unapproved component or make any modi cations you may possibly cause a re hazard and will void the CFM Corporation warranty In addition such action may void the coverage pro...

Страница 19: ...alvanized steel unit Roof ashing is included Appropri ate adapter is required See Sections 2 and 3 Required to extend Traditional Top Housings on steeply pitched roofs Used to terminate chimney at the...

Страница 20: ...n the roof Flashing not included For use with CFM Corporation Type SK8 Chimney Systems Used to terminate chimney at the top of a chase Adapter kit included Flashing not included 8 6 12 8 ue 0 to 6 12...

Страница 21: ...25r Adapter kit CTSK42 3 5 99 djt Chase Top Adapter Kit Hearth Patching Kit 325p r P325p Chase top housings SKDSBL PKDSBL 4 28 99 djt Accessories for Canada Accessory Description Model No Attic Insula...

Страница 22: ...22 CR Series Woodburning Fireplaces 20001316...

Страница 23: ...y is extended only to a Fireplace installed in the continental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instructions...

Страница 24: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation...

Отзывы: