CX300 MODULE – User manual
Doc.2016002
-22-
Spectrum LPF
Spectrum frequency range (in Hz)
Selected from a list: 200 Hz to 6400 Hz
Value cannot be more than
Max. Freq. Range
(See Table 4)
Use measured
speed
Enabled or disabled. If this is enabled, the speed value will be transferred in
CXSpectra
©
database, together with the total value, BE and spectrum
Total HPF
High Pass Filter for Total Value calculation (in Hz)
Selected from a list: (none), 5 Hz or 10 Hz
Total LPF
Low Pass Filter for Total Value calculation (in Hz)
Selected from a list: 200 Hz to 6400 Hz
This vale cannot be greater than
SpectrumLPF
Alarm vibration
Enabled or disabled. Trigger measurement alarm condition.
Warning Vib
Warning level for vibration (in Show Unit)
Danger Vib
Danger level for vibration (in Show Unit)
Measure BE
Enable/Disable BE measurement for this channel
Alarm BE
Enabled or disabled. Trigger measurement alarm condition.
Warning BE
Warning level for BE (in "gBE")
Danger BE
Danger level for BE (in "gBE")
Delay RLY
Delay in Relay action (seconds)
Selected from a list: 1 to 10 seconds
Map Warning Vib
Map vibration Warning Alarm to a specific Relay
Selected from a list: (none), RLY1, RLY2, RLY3 or RLY4
Map Danger Vib
Map vibration Danger Alarm to a specific Relay
Selected from a list: (none), RLY1, RLY2, RLY3 or RLY4
Map Warning BE
Map BE Warning Alarm to a specific Relay
Selected from a list: (none), RLY1, RLY2, RLY3 or RLY4
Map Danger BE
Map BE Danger Alarm to a specific Relay
Selected from a list: (none), RLY1, RLY2, RLY3 or RLY4
mA Output
Enable/Disable current output (4 to 20 mA) for this measurement
8.3.
TEMPERATURE MEASUREMENTS
Table 6
Configuration
Description
Show Unit
Temperature show unit, either ºC or ºF (or set to NOT CONNECTED)
Scale LO
Scale LO value, from selection: -50, -25, 0 (in
Show Unit
)
Scale HI
Scale HI value, from selection: 100, 125, 150, 200 or 300 (in
Show Unit
)
Alarm temperature
Enable/Disable temperature alarms.
Trigger measurement alarm condition.
Warning Temperature Warning level for temperature (in
Show Unit
)
Danger Temperature
Danger level for temperature (in
Show Unit
)
Map Warning Temp
Map temperature Warning Alarm to a specific Relay
Selected from a list: (none), RLY1, RLY2, RLY3 or RLY4
Map Danger Temp
Map temperature Danger Alarm to a specific Relay
Selected from a list: (none), RLY1, RLY2, RLY3 or RLY4