Maintronic Casambi CBA UP Скачать руководство пользователя страница 17

Manual english                     Casambi blind actuator

17

4.4  

Calibration  

Once the device is added into a Casambi network, 

a calibration can be performed..

Perform calibration drive (Drive time)

To  ensure  proper  operation,  a  calibration  drive 

must be performed during initial startup.

1. 

Therefore, run a complete cycle (0% fully open 

to 100% fully closed) and measure the drive 

time.

2. 

In order to take into effect deviations in the 

travel  time  from  bottom  to  top,  the  cycle 

(from 100% completely closed to 0% comple-

tely open) can be measured again. 

3. 

Enter  the  measured  time  plus  approx.  1  se

-

cond (as a buffer) in the device settings under 

parameter 

„Drive Time“

.

Setting the slat position (Angle time)

The „Angle Time“ is the aperture angle of the 

blind slats, this time must be measured and set in 

the parameters

1. 

Move the blind up a little until the slats are in 

a horizontal position.

2.  Now move the blind downwards and stop the 

time until the slats are closed.

3. 

Set the measured time in ms in the parame

-

ters under „Angle Time“.

Set drive direction

If the drive direction is not correct, the parameter 

„Swap Controls Up/Down“ can be used to swap 

the direction.

Содержание Casambi CBA UP

Страница 1: ...CBA UP Casambi blind actuator Valid from version H Hardware F Firmware 10 750 CBA UP H2 F2 5 10 752 CBA UP H1 F2 5 10752_MA_en_A4_CBA UP_20210310 Manual EN EN...

Страница 2: ...o a network 11 4 3 1 Profile A CBA Blind Drive blind Adjust slats 12 4 3 2 Profile B CBA Blind Buttons Drive blind Adjust slats additional switches 13 4 3 3 Profile C CBA Shutter Roller blind drive 14...

Страница 3: ...maintronic assumes no liability or warranty regar ding this document or the products described 1 1 About this Document Congratulations and thank you for choosing this maintronic product and the trust...

Страница 4: ...that can lead to material damage Either to the product itself or to other objects in the environment WARNING The signal word WARNING indicates a possibly imminent danger If it is not avoided death or...

Страница 5: ...the time they are placed on the market DANGER The unit must only be installed and serviced by a proven electrican specialist in accordance of all relevant regulations safety and accident preven tion d...

Страница 6: ...s allow e g to group 5 blinds on one side of a building and to operate them together In addition automated up and down movements can be programmed as a time controlled scene If you need help with conf...

Страница 7: ...e actuator once and then recalled see 4 4 Driving to an absolute position With a drive to an absolute position any hori zontal position can be approached The absolute position is controlled by a slide...

Страница 8: ...commended to use the dee pest junction boxes possible Depending on which pushbutton attachments are used up to 30 mm of additional installation space is required For installation in cavity or switch b...

Страница 9: ...re with ferrule Figure CBA UP 10 750 Figure CBA UP 10 752 NOTE The relay outputs are mutually locked to ensure that only one drive path is active at a time motor protection 1 N Neutral conductor 4 Rel...

Страница 10: ...mined Before programming a Casambi profile must be selected by default the profile CBA Blind But tons is set Profiles for venitian blinds CBA Blind Operation via APP Move blind to absolute position Ad...

Страница 11: ...or your ap plication from the following pages the device will be added to a Casambi network Tap on the menu item Change profile Tap on the menu item Add to Network The selected profile is now loaded S...

Страница 12: ...e Drive time for blind operation 0 255s seconds 60s default Angle Time Drive time for slat adjustment 0 65535ms milliseconds 2000ms default Swap Controls Up Down Logical invert of drive direction No Y...

Страница 13: ...e Down ON OFF Toggle Angle Slat angle Push Button Profile parameter Parameter Casambi Description parameter Value Default Notes Drive Time Drive time for blind operation 0 255s seconds 60s default Ang...

Страница 14: ...tion Slider 0 100 Profil Parameter Parameter Casambi Description parameter Value Default Notes Drive Time Drive time for roller blind 0 255s soconds 60s Default Swap Controls Up Down Logical invert of...

Страница 15: ...drive Up ON OFF Toggle Down Single drive Down ON OFF Toggle Profil parameter Parameter Casambi Description parameter Value Default Notes Drive Time Drive time for roller blind operation 0 255s second...

Страница 16: ...Notes Drive Time Drive time for roller blind operation 0 255s seconds 60s default Function A Function B Function for button A Function for button B Not in Use Not in Use Blind Up Roller blind Up Blin...

Страница 17: ...letely closed to 0 comple tely open can be measured again 3 Enter the measured time plus approx 1 se cond as a buffer in the device settings under parameter Drive Time Setting the slat position Angle...

Страница 18: ...as a group one device of the group must be defined as the master For the desired master the push button style must be set to Group Button The other maintronic devices in the group are automatically sl...

Страница 19: ...signed with desired functions In order to do this the following steps are necessary 1 Open Casambi app and tap on More 2 Open item Switch 3 Select device 4 For example program switch with single funct...

Страница 20: ...indication of the horizontal position is no longer correct Only a travel to one of the end points OT UT via the control from Casambi synchronizes the display with the real position again As soon as a...

Отзывы: