VENTILATOREN
FR
MDR .. EC
FIG
UK
DE
1.
Wire the fan electrically according to the
wiring diagram
Sticker in terminal box or
corresponding wiring diagram in the appen
-
dix. Tightening torque of terminals
1
Nm. Ensure PE conductor connection.
2.
Check that the technical data (
rating
plate) matches.
3.
Fit terminal box/service switch cover and
screw it on.
NOTICE:
Risk of short-circuits if
terminal box not watertight. Ensure correct
cable screw connections and tight elbows/
cable screw connections/blind plugs.
4.
Switch the mains fuse on.
5.
Commissioning MDR unit:
•
Service switch in position (1/On).
•
For MDR-PG variants, adjust the
setpoints on the pressure controller
Chapter 13.
•
For MDR-VG variants, set the setpoint on
the speed setpoint generator
Chapter
14.
6.
Fit roof [1] and screw it with both ring nuts
[2]
– tightening torque 10 Nm.