4. Assembling the ventilation unit (Specialist installer)
4.7 Settings at the switchable power unit
DIP switches 3 +4 for fan level 2 (normal ventilation/daytime operation)
Volumetric flow
Switch 3
Switch 4
1= ON
135 m³/h
1
1
0 = OFF
120 m³/h
1
0
100 m³/h (factory
0
1
setting)
85 m³/h
0
0
DIP switches 5 +6 for fan level 1 (basic ventilation/nighttime operation)
Volumetric flow
Switch 5
Switch 6
1= ON
105 m³/h
1
1
0 = OFF
95 m³/h
1
0
85 m³/h
0
1
70 m³/h (factory
0
0
setting)
Anti-frost protection:
The ventilation unit is fitted with a frost protection, as any condensation
in the heat exchanger could freeze in the case of low, outside
temperatures.
The outside air flow is reduced so that there is no further risk of freezing.
The frost protection is fixed at the factory setting.
Adjusting the volumetric flow on the exhaust air side
There is a potentiometer (P2) on the ventilation unit's switchable power unit for
adjusting the exhaust air volumetric flow to the supply air volume flow. This
setting may only be made by MAICO Customer service.
■
Anticlockwise = Reducing the exhaust air volumetric flow
■
Clockwise = Increasing the exhaust air volumetric flow
17
i
Содержание Aeronom WS 150
Страница 1: ...Wärmerückgewinnungs system WS 150 Einbau Bedienungs und Wartungsanleitung www maico ventilatoren com ...
Страница 6: ...2 Das Lüftungssystem 4 ...
Страница 10: ...2 Das Lüftungssystem 2 8 Lüftungsgerät Übersicht 8 ...
Страница 23: ......
Страница 30: ...2 The ventilation system 4 ...
Страница 34: ...2 The ventilation system 2 8 Ventilation unit Overview 8 ...
Страница 54: ...2 Le système de ventilation 4 ...
Страница 58: ...2 Le système de ventilation 2 8 Appareil de ventilation Vue d ensemble 8 ...
Страница 71: ......