Stop Multiplier and Stop Time.  Even if integrator mode is not used, the

STOP MULT

 pot can be used to

increase the torque while the machine is stopping.  The increased torque is applied when the RUN/STOP
input is closed (terminals 17 and 18).  The length of time the increased torque is applied is adjusted by
the

STOP TIME

 pot.  Using the stop multiplier feature in dancer mode could cause the dancer to oscillate

while the machine is stopping.

6.0   Optional Dancer Optimization

After tuning of the dancer, the following method will usually optimize the stability and responsiveness of
the dancer.  The method begins by placing the dancer in PD mode with a roll diameter near core and
reducing the gain to a level which the user may consider unacceptable.  Gain will subsequently be
increased to a more desirable level.  If using PID mode, the dancer is placed in PID mode with a roll
diameter near full roll and the integrator is reduced to a level which the user may consider unacceptable.
Then, the integrator will be increased to a more desirable level.  Sometimes, it may be necessary to first
make the PD mode adjustment at a larger roll diameter, and then refine the adjustment near core.

Do not switch between PD/ PID while the machine is running since this may result in a large transient
jump in the output.

1)  With a roll diameter near core and the machine stopped, set the

F

 switch  to

PD

 mode.

2)  Run the machine and adjust the

POS1

 pot to center the dancer arm.

3)  Decrease the

P

pot by rotating Counter Clockwise until the dancer stabilizes.  The

POS1

 pot may

require readjustment several times in order to keep the dancer roll centered.

DEFINITION:  In the following steps the user will have to determine if the dancer is overshooting.  To do
this, move the stable dancer away from its set position by pushing on the dancer, by bumping the
unwind/rewind roll, or by some similar means.  If the dancer goes past the set position before settling to
the set position, it is overshooting.  If the dancer goes straight to the stable position without going past it,
the dancer is not overshooting.

4)  Increase the

 P

pot by rotating Clockwise in small steps checking for dancer overshoot at each step.

Do this until overshoot is obtained.

5)  Adjust the

 D

 pot in small steps checking for dancer overshoot at each step.  Do this until the

overshoot is eliminated.  The direction to adjust

 D

 for no overshoot is system dependent.

6)  Repeat steps (4) and (5) until the overshoot cannot be eliminated using the

D

 pot, or until the

 P

 pot is

full Clockwise.

7)  Decrease the

 P

 pot by the amount necessary to eliminate the overshoot.

Adjustment is now complete for the dancer operating in PD mode.  The next steps complete the tuning of
the dancer operating in PID mode.

8)  With a roll diameter near full roll and the machine stopped, set the

F

 switch to

PID

 mode.

9)  Run the machine and adjust the            pot to center the dancer roll.

10) Decrease the     pot by rotating Counter Clockwise in small steps checking for dancer overshoot at

each step.  Do this until overshoot is obtained.

11) Increase the     pot by the amount necessary to eliminate the overshoot.

Adjustment is now complete for the dancer operating in PID mode.

POS2

I

I

Содержание DFC-A

Страница 1: ...m or Dancer control applications The DFC A provides a 0 to 10 vdc or 4 to 20 ma output to control a current to pressure transducer or a motor drive in torque mode Terminals are provided for the connec...

Страница 2: ...r DFP 2 roll diameter sensor 10 kohm tension potentiometer All inputs and outputs have the negative lead referenced to ground 4 2 Sensor Setup See Figure 3 The DFP or DFP 2 position sensor should be a...

Страница 3: ...ME full Counter Clockwise STOP MULT full Counter Clockwise 2 Set the external TENSION pot full Clockwise 3 Position the follower arm on an empty core 4 Adjust the CORE pot to obtain zero on the remote...

Страница 4: ...E may be adjusted from 0 2 to 60 seconds 5 0 Dancer Applications 5 1 Electrical Connections Figure 5 shows the connections that are required for the basic dancer system They are 24 vdc power Current T...

Страница 5: ...peat step 3 Calibration is complete and the DFC A is ready for operation Optional Adjustments Integrator Many machines run quite successfully after the above adjustments have been made If the dancer a...

Страница 6: ...ating Counter Clockwise until the dancer stabilizes The POS1 pot may require readjustment several times in order to keep the dancer roll centered DEFINITION In the following steps the user will have t...

Страница 7: ...for the Remote tension control DFP DFP 2 position sensor not wired properly or wires shorted Verify position sensor is wired properly and follow the calibration procedure in section 4 3 Voltage betwe...

Страница 8: ...alibrated Follow the calibration procedure in section 5 3 Output full on or full off DFC A in PID mode and RUN STOP switch is not wired properly Verify RUN STOP switch wiring PID mode needs a RUN STOP...

Страница 9: ...tude 0 to 2000 m Compatible Residual Current Device Types A or B IEC755 Worst Case Fault Current 2 0 amp dc Inputs Signal DFP or DFP 2 Potentiometer 1 to 10 kohm watt minimum Tension Potentiometer 10...