26
MAGNUM DIGITAL CONTROLLER (MDC) – HISTORY
The Magnum Digital Controller (MDC) controller stores a record of each important event into the history file of
the controller. The history file seats 118 records. When the history file is full, the oldest records are removed.
No.
Record Structure
Abbreviation
Historical value
1
AIM1
IG-IOM, IGS-PTM Analog input 1 value (when configured IG-IOM, IGS-PTM)
2
AIM2
IG-IOM, IGS-PTM Analog input 2 value (when configured IG-IOM, IGS-PTM)
3
AIM3
IG-IOM, IGS-PTM Analog input 3 value (when configured IG-IOM, IGS-PTM)
4
AIM4
IG-IOM, IGS-PTM Analog input 4 value (when configured IG-IOM, IGS-PTM)
5
BIM
IG-IOM, IGS-PTM Binary inputs (when configured IG-IOM, IGS-PTM)
6
BIN
Binary inputs IL-NT
7
BOM
IG-IOM, IGS-PTM Binary outputs (when configured IG-IOM, IGS-PTM)
8
BOUT
Binary inputs IL-NT
9
Date
Date of historical event in format DD/MM/YY
10
EngT
IL-NT Analog input 2 value (default Water temperature)
11
FC
ECU alarm FailureCode
12
FLvl
IL-NT Analog input 3 value (default Fuel level)
13
FMI
ECUalarm Failure Mode Identifier
14
Gfrg
Generator frequency
15
Ig1
Generator current L1
16
Ig2
Generator current L2
17
Ig3
Generator current L3
18
LChr
Character of the load
19
Num
Number of historical event
20
OilP
IL-NT Analog input 1 value (default Oil pressure)
21
PF
Generator PF
22
Pwr
Generator active power
23
Reason
Event specification
24
RPM
Engine Speed
25
Time
Time of historical event in format HH:MM:SS
26
Ubat
Battery voltage
27
Vg1
Generator voltage L1
28
Vg2
Generator voltage L2
29
Vg3
Generator voltage L3
ADJUSTING THE DISPLAY BACK LIGHTING
The backlighting on the Liquid Crystal Display (LCD) window may be adjusted brighter or darker by the operator
whenever the Magnum Digital Controller (MDC) is powered up.
1.
Press and hold “Enter” and press “
S
” or “
T
” on the Diagnostics keypad to increase or decrease the
display contrast as needed.
2.
Release the “Enter” button and the “
S
” or “
T
”buttons when the desired backlighting is attained.
Note:
Anytime an “*” is displayed on the LCD, the text or set point cannot be changed with out the use of a
password. Contact Magnum Products Technical Support for assistance.
Содержание MMG 230
Страница 1: ...230 www m p llc com DIESEL GENERATORS MMG 125 MMG 155 MMG 180 MMG 230 OPERATING MANUAL...
Страница 14: ...SERVICE LOCATIONS 14...
Страница 45: ...TRAILER LIGHTS WIRING DIAGRAM 45...
Страница 46: ...46 NOTES...
Страница 47: ...47 SERVICE LOG OIL GRADE AND TYPE BRAND COOLANT MIXTURE BRAND...
Страница 48: ...REV J PART NO 22070 10 20 08...