25
TROUBLESHOOTING cont.
SYMPTOM
PROBLEM
SOLUTION
CCO/PROBE
Various
Consult Extended Errors section on page 23 of
(1) or (2) FAIL
this manual.
The real time clock was not found on the board.
If you need the real time functions, contact
NO CLOCK PRESENT
No data logging or time sampling is allowed.
the factory to determine if your unit was ordered
with the data logging option.
If the level is within a normal operating
The calculated value for the loop output is
range, adjust the loop parameters to allow
LOOP > 20 mA
greater than 20 mA. The loop output will be in
proper tracking of the level. If the level is out of
its fail-safe mode.
the normal 4–20 mA range, then correct the
problem with the level.
If the level is within a normal operating
The calculated value for the loop output is less
range, adjust the loop parameters to allow
LOOP < 4 mA
than 4 mA. The loop output will be in its
proper tracking of the level. If the level is out of
fail-safe mode.
the normal 4–20 mA range, then correct the
problem with the level.
DISPLAY IS TOO
Turn R11(contrast adjustment) clockwise to
DIM OR TOO LIGHT
darken the display or counterclockwise to lighten
the display until the desired contrast is obtained.
SPECIFICATIONS
ELECTRICAL SPECIFICATIONS
Description
Specification
120 VAC, 50-60 Hz
Supply Voltage
240 VAC, 50-60 Hz
24 VDC
Analog
4–20 mA (Isolated), reversible
1000 ohms max. loop resistance
Output
Digital
RS-232
Range
5 pF minimum
50,000 pF maximum
Accuracy
Better than 1.0% of span
Repeatability
± .1%
Linearity
± .5%
Entry
Full numeric keypad
Data
16 character alphanumeric
Indication
LCD display
AC
10A @ 120/240 VAC resistive
DC
10A @ 30 VDC resistive
0.5A @ 125 VDC resistive
Relays
Set Point
0-50,000 pF
4 SPDT
Range
Differential
0.50 pF minimum,
Range
50,000 pF maximum
0-120 Seconds
Time Delay
Level Rising, Falling, Both
Description
Specification
Power Consumption
15 VA maximum
Humidity
99% Non-condensing (electronics)
Operating Pressure
Dependent upon probe selection
and Temperature
See Bulletin 50-125.
Electrostatic Discharge
Per IEC specification 801-2.
Protection
0.5 to approx. 2 seconds,
Response Time
depending upon probe
capac-
itance and damping value
-20° F to +160° F without heaterAmbient
Temperature
(-29° C to +71° C) and thermostat
(Electronics)
-40° F to +160° F with heater and (-40° C
to +71° C) thermostat
Temperature Coefficient
± .01%/degree F
of Set Point
(± .018%/degree C)
-20° F to +160° F
(-29° C to +71° C)
Maximum Remote
Standard: 2500 Feet (760 M)
Mount Distance
Intrinsically Safe: 800 Feet (240 M)