24
48-618 ES/EZ Modulevel Displacer Level Transmitter (Top Hat Assembly Design)
1
4 mA
apply new 4 mA input
2
20 mA
apply new 20 mA input
3
20 mA by %
enter % of span vs.
actual level
4
End
1
Set Dry Point
for use when SG will be changed,
dry point set with displacer hanging free
completely out of liquid.
2
LVDT %
read out %
3
Spec Grav
set SG value
4
Error Codes
if value other than 0000, consult factory
5
New password
enter new password, or enter value “0”
to disable password function
6
Trim 4 mA Point
factory set
7
Trim 20 mA Point
factory set
8
4 mA Trim Point
factory set
9
20 mA Trim Point
factory set
10
Set Serial Number
factory set
1
Model
2
Manufacturer
3
Set Magnetrol S/N
4
Dev id
5
Tag
6
Descriptor
7
Message
8
Damping
9
Fault State
10
Date
11
Final Assembly
12
Universal rev
13
Fld dev rev
14
Software rev
15
Poll addr
16
Number req preams
1
4 mA
unit blocks at 4 mA
2
20 mA
unit blocks at 20 mA
3
Other
enter a value between 3.6 and 22 mA
4
End
1
Set as 4 mA value
current level will be new 4 mA level
2
Read new value
introduce a value that will match 4 mA
3
Leave as found
keep old 4 mA level
1
Set as 20 mA value
current level will be new 20 mA level
2
Read new value
Introduce a value that will match 20 mA
3
Leave as found
keep old 20 mA value