background image

5.6.2 SIS Configuration Requirements

Ensure the GWR transmitter parameters have been properly
configured for the specific application and probe.

Special consideration should be given to the following con-
figuration parameters:

FAULT

DO NOT

choose HOLD for this parameter as a

Fault will not be annunciated on the current loop.

PASSWORD

: The Password (default = 0) should be

changed to a specific value other than 0 to ensure the neces-
sary SIS Write/Lock protection.

The following list represents the parameter configuration
required for a Model 705 GWR transmitter intended to
measure overall product level in a SIL 2/3 application.

Please ensure that all Probe-specific parameters are correct
for the GWR probe being used.

PROBE MODEL = As indicated on probe nameplate

PROBE MOUNT = As indicated on probe nameplate

MEASUREMENT TYPE = Level Only

LEVEL UNITS = As indicated on probe nameplate

PROBE LENGTH = As indicated on probe nameplate

LEVEL OFFSET = As required by application

DIELECTRIC = As required by application. (Suggest 1.7–3
for typical hydrocarbon application)

LOOP CONTROL = Level

LOOP CONTROL MODE = Enabled

SET 4mA/SET 20mA = As required by application

DAMPING = As required by application (Default value is 1)

FAULT = As required by application (Default value is
22 mA—do not set to Hold).

BLOCKING DISTANCE = 0 inches

THRESHOLD = Fixed

5.6.3 Write Protection / Locking

Only authorized personnel should be able to change the
transmitter configuration in a device installed in a SIS system.
This requires setting a user password.

The ECLIPSE Model 705 is password protected with a
numerical password between 0 and 255. (Default = 0 means
password is disabled).

The default password must be changed so that password
protection is enabled in a SIS system.

8

57-651 Eclipse

®

SIL Certified Safety Manual for Enhanced Model 705-51AX-XXX

Содержание eclipse 705

Страница 1: ...omer specified out of range signal i e less than 3 8 mA or greater than 20 5 mA The Enhanced Model 705 is certified for use in low or high demand level measurement applications Application The Enhance...

Страница 2: ...l Level of Personnel 6 5 3 Necessary Tools 6 5 4 Storage 7 5 5 Installation 7 5 6 Configuration 7 5 6 1 General 7 5 6 2 SIS Configuration Requirements 8 5 6 3 Write Protecting Locking 8 5 7 Site Accep...

Страница 3: ...ssified as a Type B Device as defined by IEC61508 NOTE Please ensure that the Model 705 transmitter and probe are installed as a set matched by the Serial Number shown on the name plates 1 3 Determini...

Страница 4: ...This SIL 2 3 certified device is only available with an analog signal 4 20 mA with HART digital communications The measurement signal used by the logic unit must be the generated analog 4 20 mA signa...

Страница 5: ...equipment etc with smaller transient volt ages than those characteristic of Overvoltage Category III This category applies from the wall plug to the power sup ply isolation barrier or transformer The...

Страница 6: ...ildup on the probe Refer to Section 3 3 3 of Installation and Operating Manual 57 600 for more detailed application information regarding media buildup and bridging 5 1 2 Environmental Refer to Sectio...

Страница 7: ...nd resetting of the password protection function Section 2 6 5 1 of I O Manual 57 600 provides menu selec tion items for configuration of the transmitter as a Level Only sensing device See Section 5 6...

Страница 8: ...eplate MEASUREMENT TYPE Level Only LEVEL UNITS As indicated on probe nameplate PROBE LENGTH As indicated on probe nameplate LEVEL OFFSET As required by application DIELECTRIC As required by applicatio...

Страница 9: ...ete a site acceptance test should be performed to ensure proper opera tion This procedure is identical to the Proof Test Procedure described in Section 6 1 4 of this manual Record the results for futu...

Страница 10: ...in the Safety Integrity Level of a Safety Instrumented System it is imperative that specified manual proof testing be completed at the time intervals specified The user must select the type of inspect...

Страница 11: ...level from the probe The Status parameter should say Dry Probe and the level reading should be equal to the value in the Level Offset parameter 5 Perform a two point calibration check of the transmit...

Страница 12: ...ilistic calculation method is meaningless as the probability of failure significantly increases with time The useful lifetime is highly dependent on the component itself and its operating conditions t...

Страница 13: ...endently verify all changes to end user configured parameters and validate the safety functionality prior to reliance on the product for safety protection End user s responsibility SSA 8 The end user...

Страница 14: ...14 57 651 Eclipse SIL Certified Safety Manual for Enhanced Model 705 51AX XXX 8 2 FMEDA Report exida Management Summary...

Страница 15: ...15 57 651 Eclipse SIL Certified Safety Manual for Enhanced Model 705 51AX XXX...

Страница 16: ...al Procedure So that we may efficiently process any materials that are returned it is essential that a Return Material Authorization RMA number be obtained from the factory prior to the material s ret...

Отзывы: