7
57-651 Eclipse
®
SIL Certified Safety Manual for Enhanced Model 705-51AX-XXX
5.4
Storage
The device should be stored in its original shipping box and
not be subjected to temperatures outside the storage temper-
ature (-50 to +80 °C) shown in the ECLIPSE Enhanced
Model 705 Installation and Operating Manual, 57-600.
5.5
Installation
Refer to the Enhanced ECLIPSE Model 705 Installation
and Operating Manual 57-600 manual for the proper
installation instructions.
NOTES:
1) Ensure that the Model 705 transmitter and probe are installed
as a set matched by the Serial Number shown on the name
plates.
2) When replacing a transmitter or probe, configuration changes
must be performed with the transmitter and probe connected
together.
Section 2.6.4 of I/O Manual 57-600 contains information
regarding the use, changing, and resetting of the password
protection function.
Section 2.6.5.1 of I/O Manual 57-600 provides menu selec-
tion items for configuration of the transmitter as a Level
Only sensing device.
See Section 5.6 of this manual for configuration recommen-
dations with respect to using the Enhanced ECLIPSE
Model 705 in a SIS.
As stated in Section 2.0, this SIL evaluation has assumed
that the customer will be able to acknowledge an “over or
under” output current condition via the Logic Unit.
Refer to section 8.3 for Safety System Assumptions (SSA).
5.6
Configuration
5.6.1 General
The MAGNETROL Model 705 can be configured via the
local LCD/keypad, a HART compatible handheld terminal
or with a personal computer containing the proper HART
DTM and framework program such as PACT
ware
™
.
NOTE: Parameter changes should not be made through the local display
and the HART interface simultaneously. This is not a safety
consideration because the user of the safety device must
confirm parameter changes per SSA 7. (Refer to page 13.)