57-645 Eclipse Guided Wave Radar Transmitter - PROFIBUS PA

Read this Manual Before Installing

This  manual  provides  information  on  the  Enhanced
Eclipse  Model  705  transmitter  with  PROFIBUS  PA

Output and should be used in conjunction with Eclipse
I&O  manual  57-600.  It  is  important  that  all  instruc-
tions are read and followed carefully.

Safety Messages

The  Eclipse  system  is  designed  for  use  in  Category  II,
Pollution  Degree  2  installations.  Follow  all  standard
industry procedures for servicing electrical and computer
equipment  when  working  with  or  around  high  voltage.
Always  shut  off  the  power  supply  before  touching  any
components. Although high voltage is not present in this
system, it may be present in other systems.

Electrical  components  are  sensitive  to  electrostatic  dis-
charge.  To  prevent  equipment  damage,  observe  safety
procedures  when  working  with  electrostatic  sensitive
components.

This  device  complies  with  Part  15  of  the  FCC rules.
Operation  is  subject  to  the  following  two  conditions:
(1) This device may not cause harmful interference, and
(2)  This  device  must  accept  any  interference  received,
including interference that may cause undesired operation.

WARNING!

Explosion  hazard.  Do  not  connect  or  dis-

connect designs rated Explosion proof or Non-incendive
unless  power  has  been  switched  off  and/or  the  area  is
known to be non-hazardous

Low Voltage Directive

For use in Installations Category II, Pollution Degree 2.
If  equipment  is  used  in  a  manner  not  specified  by  the
manufacturer, protection provided by equipment may be
impaired.

Notice of Copyright and Limitations

Magnetrol and Magnetrol logotype, and Eclipse are reg-
istered trademarks of Magnetrol International.

Copyright © 2015 Magnetrol International
All rights reserved

Performance specifications are effective with date of
issue and are subject to change without notice.
Magnetrol reserves the right to make changes to the
product described in this manual at any time without
notice. Magnetrol makes no warranty with respect to the
accuracy of the information in this manual.

Warranty

All Magnetrol electronic level and flow controls are war-
ranted free of defects in materials or workmanship for one
full  year  from  the  date  of  original  factory  shipment.  If
returned  within  the  warranty  period;  and,  upon  factory
inspection of the control, the cause of the claim is deter-
mined to be covered under the warranty; then, Magnetrol
will  repair  or  replace  the  control  at  no  cost  to  the  pur-
chaser (or owner) other than transportation.

Magnetrol  shall  not  be  liable  for  misapplication,  labor
claims, direct or consequential damage or expense arising
from the installation or use of equipment. There are no
other warranties expressed or implied, except special writ-
ten warranties covering some Magnetrol products.

Quality assurance

The quality assurance system in place at Magnetrol
guarantees the highest level of quality throughout the
company. Magnetrol is committed to providing full
customer satisfaction both in quality products and
quality service.

Magnetrol’s quality assurance system is
registered to ISO 9001 affirming its
commitment to known international
quality standards providing the strongest
assurance of product/service quality
available.

Содержание eclipse 705

Страница 1: ...Guided Wave Radar Level Transmitter Enhanced Model 705 with PROFIBUS PA Digital Output 705 software v3 x PROFIBUS PA Operating Manual...

Страница 2: ...ovided by equipment may be impaired Notice of Copyright and Limitations Magnetrol and Magnetrol logotype and Eclipse are reg istered trademarks of Magnetrol International Copyright 2015 Magnetrol Inte...

Страница 3: ...Installing the Transmitter 19 3 4 5 1 Integral Mount 19 3 4 5 2 Remote Mount 19 4 0 Function Blocks 20 4 1 Overview 20 4 1 1 Standard Profibus Block Parameters 20 4 2 Physical Block 21 4 3 GWR Transdu...

Страница 4: ...le the varying 4 20 mA current a dig ital communications scheme such as PROFIBUS PA con siders the two wires as a network The network can carry many process variables as well as other information The...

Страница 5: ...to the control room for additional trending and reporting 3 Maintenance The self diagnostics residing in the smart field devices minimizes the need to send maintenance personnel to the field 1 3 Devi...

Страница 6: ...he Physical Block must be set to the profile specific ident number The default selection of the Ident Number Selector parameter is the manufacturer specific ident number A Device Description is availa...

Страница 7: ...g the Eclipse level transmitter These procedures are intended for experi enced installers of electronic level measurement instruments See Complete Installation Section 3 0 for detailed installa tion i...

Страница 8: ...s of probe model number _____________ Level Offset The desired level reading when the liquid is at the end of the probe _____________ Dielectric What is the dielectric constant range of the process me...

Страница 9: ...venient position for wiring configuring and viewing Using a 11 2 38 mm wrench tighten the universal connection on the transmitter 1 4 to 1 2 turn beyond hand tight A torque wrench is highly recommende...

Страница 10: ...cept a value and move to the next step of the configuration program the default password is 0 7 After entering the last value allow 10 seconds before removing power from the transmitter The following...

Страница 11: ...e reference when ordering parts Model Number Serial Number 3 2 Electrostatic Discharge ESD Handling Procedure Magnetrol s electronic instruments are manufactured to the highest quality standards These...

Страница 12: ...and type Coaxial probe 11 2 38 mm twin rod probe 17 8 47 mm transmitter 11 2 38 mm A torque wrench is highly desirable Flat blade screwdriver Fieldbus compatible power supply with proper termination 3...

Страница 13: ...sure probe Model 7xP High Pressure probe Model 7xR Overfill probe Model 7xS Steam probe and Model 7xT Interface probe require added clearance Process temperature pressure dielectric and viscosity are...

Страница 14: ...tc a bare tank wall parallel to the probe is acceptable 3 4 2 1 To install a rigid twin rod probe Make sure the process connection is at least 2 NPT or a flanged mounting Make sure that there is at le...

Страница 15: ...es 2 b Loosen the two 10 32 set screws 3 on both securing devices using a 3 32 2 5 mm hex wrench and slide the securing devices off of the probe c Slide the TFE weight off of the probe d Cut and remov...

Страница 16: ...ss connection For flanged connections tighten flange bolts Probe can be stabilized by placing into a non metallic cup or bracket at the bottom of the probe A TFE bottom spacer P N 89 9114 001 is optio...

Страница 17: ...robes The Model 7x2 and 7x5 Bulk Solids probes are designed for a 3000 lb 1360 kg pull down force for use in applications such as sand plastic pellets and grains It is offered with a maximum 75 foot 2...

Страница 18: ...s of coating from the two cables f Slide the weight back on to the probe g Reinstall the two cable clamps and tighten h Enter the new probe length inches or cm in software 3 4 4 4 To install a Model 7...

Страница 19: ...r wiring configuration and viewing When the transmitter is facing the desired direction use a 11 2 38 mm wrench to tighten the universal connection on the transmitter to 15 ft lbs A torque wrench is h...

Страница 20: ...lowing are general descriptions of the parameters common to all blocks Additional information for a given parameter is described later in that specific block section BLOCK_OBJECT Contains the characte...

Страница 21: ...he field device HARDWARE_REVISION Revision number of the hardware of the field device DEVICE_MAN_ID Identification code of the manufacturer of the field device DEVICE_ID Manufacturer specific identifi...

Страница 22: ...SET_ADDRESS_TO_DEFAULT Other parameter unchanged DESCRIPTOR User definable text string to describe the device within the application DEVICE_MESSAGE User definable message string used to describe the d...

Страница 23: ...d by these addi tional required parameters for a Level Transducer Block Corresponding parameter names from Profile specification are shown parenthetically if different from parameter names used by Mod...

Страница 24: ...r in the TRANS DUCER block list is DEVICE_STATUS which displays the status of the device If more than one message exists then the messages are displayed in priority order Refer to Section 7 1 2 Error...

Страница 25: ...nameplates attached to the transmitter and probe PROBE_LENGTH is shown in SENSOR_UNITs LEVEL_OFFSET Enter the distance from the probe tip to the desired 0 reference in PROBE_LEVEL_UNITs The acceptabl...

Страница 26: ...e probe 10 inches above the bottom of the tank The user wants the 0 point at 24 inches and the 100 point at 60 inches as referenced from the bottom of the tank When the Eclipse transmitter is mounted...

Страница 27: ...ither troubleshooting or are parameters adjusted at the factory They should never be changed in the field The factory adjustable calibrated parameters are WINDOW CONVERSION_FACTOR and SCALE_OFFSET WIN...

Страница 28: ...mal point to be used in displaying the OUT parameters LIN_TYPE Type of linearization No linearization is sup ported in the AI function blocks CHANNEL Selects the measurement value from an active trans...

Страница 29: ...eter can be used to dampen out fluctuation in level due to excessive turbulence The AI Block has multiple ALARM functions that monitor the OUT parameter for out of bound conditions 4 5 2 Local Display...

Страница 30: ...four Analog Input blocks any or all of which may be used in particular applica tions a Transducer block parameter controls which AI block Out values will be displayed The fieldbus presentation of this...

Страница 31: ...column provides the actions to take when config uring the transmitter Additional information or an explana tion of an action is given in the fourth column Shaded sections are factory menu items Displa...

Страница 32: ...0 to 126 21 AIDisp select User Select AI Block Out values to be displayed 22 LvlTicks xxxxx User Diagnostic Display Time of flight from fiducial to level signal 23 New Pass xxx User Enter new passwor...

Страница 33: ...Comment 41 Compsate Superuser Superuser Parameter Select from None Manual Auto 42 DrateFct xxxx None Diagnostic Display Compsate Auto velocity derating factor 43 TargAmpl xxxx None Diagnostic Display...

Страница 34: ...probe is not known The TRANSDUCER BLOCK output is calculated as LEVEL_OFFSET When in the dry probe condition the Model 705 compares the measured length of the probe to the value entered into the PROB...

Страница 35: ...If probe is not flooded full scale level near very top of probe Check for buildup or obstructions near top of probe Select higher dielectric range Check for condensation in probe connection Add Blocki...

Страница 36: ...ited Fault Lvl Probe Length 23 0x00800000 Bad Sensor Failure Constant Limited Fault No Fiducial 21 0x00200000 Bad Device Failure Constant Limited Fault Safety Zone FLT 20 0x00100000 Bad Non Specific N...

Страница 37: ...k entered Probe Length 2 Change Threshold to Fixed EOP High End of Probe signal is out of range 1 Ensure Probe Length is entered correctly 2 Consult factory High Volume Flt Level more than 5 above hig...

Страница 38: ...m of 32 VDC Total current draw of a given segment cannot exceed the rating shown on the power conditioner and or barrier Device polarity must be correct Two 100 1 F terminators must be connected to th...

Страница 39: ...s B C D 705 53XX 4XX with Intrinsically Safe probe Class II Div 1 Group G T4 Class III Type 4X 705 53XX XXX Non Incendive Class I Div 2 Groups A B C D 705 53XX XXX Suitable for Class II Div 2 Group G...

Страница 40: ...40 57 645 Eclipse Guided Wave Radar Transmitter PROFIBUS PA 7 2 1 Agency Specifications PROFIBUS PA System...

Страница 41: ...Housing Material Aluminum A356T6 0 20 copper optional 316 stainless steel Cable Entry 3 4 NPT and M20 Environment Operating Temperature 40 to 175 F 40 to 80 C Display Function Operating Temperature 5...

Страница 42: ...d Warm up Time 5 seconds Operating Temp Range 40 to 175 F 40 to 80 C LCD Temp Range 5 to 160 F 20 to 70 C Ambient Temp Effect Approximately 0 02 of probe length C Process Dielectric Effect 0 3 inch wi...

Страница 43: ...inch clean distinct interface required Upper Layer Dielectric 1 4 5 0 Interface Layer Dielectric 15 Resolution 0 1 inch Repeatability 0 5 inch Hysteresis 0 5 inch Response Time 1 second Warm up Time 5...

Страница 44: ...d PROFIBUS PA Z30 9151 003 O ring VITON 012 2201 237 Consult Factory for alternative O ring materials Housing cover without glass 004 9193 003 Housing cover with glass GP IS 036 4410 001 XP 036 4410 0...

Страница 45: ...ntrinsically Safe ATEX JIS EEx ia IIC T4 C Integral Explosion Proof ATEX EEx d ia IIC T4 must be ordered with Conduit Connection Codes 0 and 1 D Remote Explosion Proof ATEX EEx d ia IIB T4 must be ord...

Страница 46: ...unit of measure 7M Eclipse GWR probe Metric unit of measure PROCESS CONNECTION SIzE TYPE BASIC MODEL NUMBER CONFIGURATION STYLE O RINGS LENGTH PROBE MODELS 7xA 7xB 7xD 7xF 7XJ 7xP 7xQ 7xR 7xS LENGTH...

Страница 47: ...ANSI Raised Face Flange 23 1 150 ANSI Raised Face Flange 24 1 300 ANSI Raised Face Flange 25 1 600 ANSI Raised Face Flange 27 1 900 1500 ANSI Raised Face Flange 28 1 2500 ANSI Raised Face Flange 33 11...

Страница 48: ...nge TU 31 2 600 Fisher Proprietary 316 Stainless Steel 249C Torque Tube Flange UT 21 2 600 Masoneilan Proprietary Carbon Steel Torque Tube Flange UU 21 2 600 Masoneilan Proprietary 316 Stainless Steel...

Страница 49: ...PING_TABLE_PT10 StrappingTbl Pt10 85 STRAPPING_TABLE_PT11 StrappingTbl Pt11 INDEX PARAMETER NAME PARAMETER LABEL 86 STRAPPING_TABLE_PT12 StrappingTbl Pt12 87 STRAPPING_TABLE_PT13 StrappingTbl Pt13 88...

Страница 50: ...robe Serial Working Value Non Working Value LvlUnits VolUnits opt IfcUnits opt IfcVolUn opt PrbModel PrbMount MeasType SnsrUnit Probe Ln PrbLvlUn Lvl Ofst TblVolUn opt StrapTbl opt Upr Diel opt Dielct...

Страница 51: ...ooting Item Value Value Value TROUBLESHOOTING Correct Value Incorrect Value Neg Ampl Ifc Ampl opt Pos Ampl Compsate Targ Cal opt OperMode opt 7xK Corr opt SnrCalLo SnrCalHi PrLvl Lo PrLvl Hi SZ Hyst S...

Страница 52: ...he basis of the applicability of our warranty No claims for misapplication labor direct or consequen tial damage will be allowed Return Material Procedure So that we may efficiently process any materi...

Отзывы: