Magnetrol B73 Скачать руководство пользователя страница 5

5

PREVENTIVE MAINTENANCE (cont.)

TROUBLE SHOOTING

Usually the first indication of improper operation is failure of
the controlled equipment to function i.e. pump will not start
(or stop); signal lamps fail to light, etc. When these symp-
toms occur, whether at time of installation or during routine
service thereafter, check the following potential external
causes first.

– Fuses may be blown.

– Reset button(s) may need resetting.

– Power switch may be open.

– Controlled equipment may be faulty.

– Wiring or medium lines leading to control may be

defective.

If a thorough inspection of these possible conditions fails to
locate the trouble, proceed next to a check of the controls
switch mechanism.

CHECK SWITCH MECHANISM

1. Pull disconnect switch or otherwise assure disconnect

power to the control.

2. Remove switch housing cover.

3. Disconnect power wiring from switch assembly.

4. Swing magnet assembly in and out by hand to check

carefully for any sign of binding. Assembly should
require minimal force to move it through its full swing.

5. If binding exists, magnet may be rubbing enclosing tube.

If magnet is rubbing, loosen magnet clamp screw and
shift magnet position. Retighten magnet clamp screw.

6. If switch magnet assembly swings freely and mechanism

still fails to actuate, check installation of control to be
certain it is within the specified three (3°) degrees of ver-
tical (use spirit level on side of enclosing tube in two
places, 90° apart).

7. If mechanism is equipped with a mercury switch, exam-

ine glass mercury tube closely as previously described
in “Preventive Maintenance” section. If switch is dam-
aged, replace it immediately.

8. If switch mechanism is operating satisfactorily, proceed

to check sensing unit.

CHECK SENSING UNIT

1. Check to be certain liquid is entering float chamber. A

valve may be closed or piping plugged.

2. Proceed to check level sensing action.

3. Remove the switch housing assembly by loosening the

enclosing tube nut located immediately below the hous-
ing base.

4. Inspect attraction sleeve(s) and inside of enclosing tube

for excessive corrosion or solids build-up which could
restrict movement, preventing sleeve(s) from reaching
field of magnet(s).

5. Fill chamber with liquid at room pressure. Check float(s)

to be certain it is buoyant in the liquid (float chamber
must have adequate liquid level). If float is determined to
be filled with liquid or collapsed, entire float chamber
assembly (sensing unit) should be replaced.

CHECK COMPLETE UNIT

Reassemble the unit. Reconnect the power supply and
carefully actuate the switch mechanism manually (using a
non-conductive tool) to determine whether controlled
equipment will operate.

If all components in the control are in operating condition,
the trouble must be (and should be) located external to the
control. Repeat inspection of external conditions previous-
ly described.

NOTE:  If difficulties are encountered which can not be
identified, consult with the factory or your local representa-
tive for assistance. A complete description of the trouble
should be provided along with information concerning your
piping and mounting arrangement, plus a description of
your operation sequence. Sketches or photographs show-
ing the installation are also beneficial.
When communicating about your control, be certain always
to specify the complete Model and Serial numbers.

CAUTION: Unit must be normalized to atmospheric
pressure before removing switch housing assembly.

CAUTION: With electrical power “on”, care should be
taken to avoid contact with switch leads and connec-
tions at terminal block.

WHAT TO AVOID

1. NEVER  leave switch housing cover off the control
longer than necessary to make routine inspections.

2. NEVER  place a jumper wire across terminals to “cut-

out” the control. If a “jumper” is necessary for test pur-
poses, be certain it is removed before placing control
into service.

3. NEVER attempt to make adjustments or replace switch-

es without reading instructions carefully. Certain adjust-
ments provided for in Magnetrol controls should not be
attempted in the field. When in doubt, consult the facto-
ry or your local Magnetrol representative.

4. NEVER use lubricants on pivots of switch mechanisms.

A sufficient amount of lubricant has been applied at the
factory to ensure a lifetime of service. Further oiling is
unnecessary and will only tend to attract dust and dirt
which can interfere with mechanism operation.

Содержание B73

Страница 1: ...g in position Swing out position HL LL Enclosing tube non magnetic OPERATING CYCLE As the liquid level rises in the chamber refer to Figure 1 the float moves the magnetic attraction sleeve up within the enclosing tube and into the field of the switch mechanism magnet As a result the magnet is drawn in tightly to the enclosing tube causing the switch to trip making or break ing an electrical circui...

Страница 2: ... EX6 ED5 EW5 mercury switch Series F 230 C Snap switch 450 F SPDT FAP F2P F3P FKR FK8 FU8 FK7 FU7 FAQ F2Q F3Q FKY FK6 FU6 FK5 FU5 hermetically DPDT FDP F8P F9P FNR FN8 FX8 FD7 FW7 FDQ F8Q F9Q FNY FN6 FX6 FD5 FW5 sealed Series HS 230 C Snap switch 450 F SPDT HM2 H7A H6A HS3 HB1 HB2 HB3 HB4 hermetically sealed with DPDT HM6 H7C H6C HS7 HB5 HB6 HB7 HB8 terminal block Series U 120 C SPDT UAP U2P U3P U...

Страница 3: ...el in the vessel cable entry Pressure vessel Switch actuating level reference marks Drain valve Shutoff valve Max 305 mm Figure 3 WIRING Most mechanical control switch housings are designed to allow 360 positioning of the cable entries by loosening the set screw s See figure 4 On high temperature applica tions above 120 C 250 F high temperature wire should be used between control and first junctio...

Страница 4: ... and lever Such wear can cause false switch actuat ing levels Adjust switch mechanism to compensate if possible or replace switch DO NOT operate your control with defective maladjusted switch mechanisms refer to bulletin on switch mechanism furnished for service instructions Magnetrol controls may sometimes be exposed to excessive heat or moisture Under such conditions insulation on electrical wir...

Страница 5: ...ould restrict movement preventing sleeve s from reaching field of magnet s 5 Fill chamber with liquid at room pressure Check float s to be certain it is buoyant in the liquid float chamber must have adequate liquid level If float is determined to be filled with liquid or collapsed entire float chamber assembly sensing unit should be replaced CHECK COMPLETE UNIT Reassemble the unit Reconnect the po...

Страница 6: ...andard Construction 89 3410 009 Stainless Steel Connection Sleeve Kit 5 Guide Washer 6 Attraction Sleeve 7 Enclosing Tube Models with material code 1 2 Models with material code 3 4 Nema 4X Nema 7 9 Pneumatic Switch Housing 32 6302 031 32 6302 036 Baseefa Cenelec 32 6344 002 32 6344 001 12 1301 002 8 E Tube Gasket 9 Chamber Assembly Chamber assemblies are available as complete sensing units ONLY w...

Страница 7: ... 1 2 163 2 6 42 0 08 for material code 4 250 2 9 84 0 08 250 2 9 84 0 08 83 2 3 27 0 08 160 2 6 30 0 08 160 2 6 30 0 08 Housing A B Entry C max D IP 65 NEMA 4x 151 5 93 109 4 29 1 NPT M20 x 1 5 or PG16 2 entries 1 plugged 459 18 07 NEMA 7 9 IP 65 143 5 63 100 3 94 1 NPT 1 entry 453 17 83 CENELEC BASEEFA IP 66 143 5 63 110 4 33 3 4 NPT OR M20 x 1 5 2 entries 507 19 80 NEMA 3R IP 53 Pneumatic K 118 ...

Страница 8: ...E So that we may efficiently process any materials that are returned it is essential that a Return Material Authorisation RMA form will be obtained from the factory It is mandatory that this form will be attached to each material returned This form is avail able through Magnetrol s local representative or by contacting the factory Please supply the following information 1 Purchaser Name 2 Descript...

Отзывы: