10. The SBN pendant is double insulated. No metal part extends from inside of the enclosure to the

outside. Because of this, grounding inside the pendant is not necessary. However, because of the

possibility that water could enter the pendant through damaged parts or cable, it is recommended

that a ground wire be left extending to the bottom. Insulation should cover the conductor, but the

end can be left as cut so that it will contact any water that might build up in the lowest part of the

pendant. If there were water inside the pendant and it touched something “live”, the ground wire’s

end would also be contacting the water and would be able to conduct current away. Using a

ground fault circuit would alert the control system to the abnormal condition.

Enclosure Reassembly 

1. Ensure that there are no bare or loose conductor strands and that all conductors are insulated

from each other. Make sure that there are no loose pieces of insulation or wire inside the pendant

enclosure.

2. Make sure that the seal for the back cover is intact in the groove of the front of the enclosure and

not damaged.

3. Put the back cover on while making sure that the wires are tucked inside and do not get between

the cover and the enclosure.

4. The top cable gland provides the primary seal between the cable and the pendant. Security of the

seal may be augmented by applying a bead of silicone RTV in the area where the cable gland

and cable meet.

Figure 2: Auxiliary Cable Armor Installation 

Содержание SBIT-8-W

Страница 1: ...SBN Pendant Pushbutton Station Instruction Manual Part Number 126 11173 R2 October 2019 Copyright 2019 Magnetek Material Handling...

Страница 2: ...Page Intentionally Left Blank...

Страница 3: ...10 Precautions for Wiring 10 Enclosure disassembly 11 Wiring 11 Enclosure Reassembly 12 Strain Relief Installation when using cable with molded in strain relief cables 13 Strain Relief Installation w...

Страница 4: ...r technical information contact Magnetek Material Handling N49 W13650 Campbell Drive Menomonee Falls WI 53051 Distributed by Tri State Equipment Company Inc Telephone 314 869 7200 Website E mail Fax N...

Страница 5: ...x Regulations issued by the Occupational Health and Safety Administration OSHA x Applicable local state provincial or federal codes ordinances standards and requirements or x Safety standards and prac...

Страница 6: ...hazardous situation which if not avoided will result in death or serious injury This signal word is to be limited to the most extreme situations WARNING WARNING indicates a potentially hazardous situa...

Страница 7: ...of the pendant housing is possible Contaminants that enter the switch contacts may result in a potentially unsafe operating condition When cutting stripping and installing wires ensure that contaminan...

Страница 8: ...SBN Pendant Station Manual October 2019 Page 8 of 19 Product Overview and Features Figure 1 SBN 8 WHS Pendant...

Страница 9: ...ainless steel cover screws and molded in cover nuts x External key ring for strain relief cable attachment x Internal strain relief clamp x Pre wired common circuit x NEMA 4X rating see Table 1 for NE...

Страница 10: ...and proper lockout tagout procedures followed DO NOT make or break electrical connections for example plugs and receptacles without first disconnecting power at the source and following proper lockou...

Страница 11: ...land like a hat when wiring is complete This is an additional cover for the gland cable connection that can provide extra protection against water intrusion It should be trimmed with scissors in a sin...

Страница 12: ...cting the water and would be able to conduct current away Using a ground fault circuit would alert the control system to the abnormal condition Enclosure Reassembly 1 Ensure that there are no bare or...

Страница 13: ...ey ring in the top of the pendants and back through the strain relief collars Tighten the set screws until the strain relief cables are secure Trim off the strain relief wires so they are flush with t...

Страница 14: ...legend and replace with the selected word or symbol from the legend sheet Insert the lens over the legend and make sure it is secure Button Hood Replacement Remove the switch under the button hood by...

Страница 15: ...ove any dirt from the outside of the pendant x Ensure that the cable is not cut or damaged x Ensure that the cable entry point is well sealed x Ensure that there are no cracks cuts or openings in the...

Страница 16: ...or the operator and the load is clear x Face the load and stand such that it moves away from you Do not touch the load when it is being lifted x Stay far enough away from a load so that if it drops it...

Страница 17: ...e armor provides a steadfast seal For example if preparing cable armor for an SBN 2 W the type of cable armor the unit should come with is Type A The outer diameter of the cable is 11mm so the cable a...

Страница 18: ...tion Manual October 2019 Page 18 of 19 Appendix B Pendant Switch Schematics Distributed by Tri State Equipment Company Inc Email sales tsoverheadcrane com Web www tsoverheadcrane com PH 314 869 7200 F...

Страница 19: ...SBN Pendant Pushbutton Station Instruction Manual October 2019...

Отзывы: