G+ Mini Transition Guide September 2008
Page 7 of 24
Magnetek, Inc.
Product Transition Guide
G+ Mini Rev:
1.4 Terminals
Main Circuit Terminals
•
As the P3 Series 2 and G+ Mini may have different terminals sizes (depending on capacity), the terminals must be
carefully checked before replacement.
•
The main terminal functionality has not been changed between the P3 Series 2 and the G+ Mini drive.
Control Terminals, Signal Levels
•
The P3 Series 2 and G+ Mini initial settings for terminal function are shown below.
•
"—" indicates that an equivalent terminal on the other unit does not exist.
Main Terminals
Note
P3 Series 2
G+ Mini
R/L1
R/L1
Power supply connection
S/L2
S/L2
T/L3
T/L3
U/T1
U/T1
Drive output
V/T2
V/T2
W/T3
W/T3
B1
B1
Braking resistor or external braking unit connection
B2
B2
Braking resistor connection
+1
+1
DC Choke connection, DC power supply input
+2
+2
DC Choke connection
—
—
DC power supply input, external braking unit connection
Ground
Control
Terminals
Function
Signal Level
P3
Series
2
G+
Mini
P3 Series 2
G+ Mini
S1
Multi-Function input 1
(1: Run forward 0: Stop)
120 VAC
(Photocoupler 24 VDC, 8A
isolation*)
120 VAC
(Photocoupler 24 VDC, 8A
isolation*)
S2
Multi-Function input 2
(1: Run reverse 0: Stop)
S3
Multi-Function input 3
(External fault)
S4
Multi-Function input 4
(Fault reset)
S5
Multi-Function input 5
(Multi-step speed 1)
S6
Multi- Function input 6
(Multi-step speed 2)
S7
Multi-Function input 7
(JOG reference)
X2 (SC*)
Multi-Function
input
common
0V
0V
RP
Pulse input
(frequency reference)
Frequency range:
1.0~32 kHz
Frequency range:
0.5~32 kHz
* With 120 VAC interface card removed