Intelli-Protect User Manual
April 2023
If the first limit switch test displayed a Bridge slowdown FWD, this limit switch test should display a Bridge
stop FWD, for example.
A single Trolley slowdown and stop output pair should be active. The direction of travel should match.
A single Bridge slowdown and stop output pair should be active. The direction of travel should match.
Corrective Action:
If the stop output direction of travel does not match the slowdown direction, the stop
wires should be reversed.
Figure 5-3: Intelli-Protect
®
Outputs