3.5.2. Physical Barrier
Any physical barrier should meet the
following requirements:
1.
Provide at least the equivalent level of
warning to the approach of an open fire,
to that of a hearth.
2. Define a clear zone where occupants
must exercise additional caution.
3. Should be constructed of non-
combustible material, of robust design
and fixed in such a way so as to provide
a secure boundary and be mechanically
fixed to prevent accidental and/or
unintentional removal.
Such a device could take the form of a
fender, a shelf, a wall mounted decorative
bar, etc.
All
Elite
Models
W
Must project a minimum of
150mm either side of any naked
flame or incandescent material
D
Must project a minimum of
300mm in front of any naked
flame or incandescent material
The height of any physical barrier must
be a minimum of 50mm above the
finished floor level.
Table 2 – Protected Area
Figure 37
and
Figure 38
show examples of
area to be protected by the physical barrier.
Figure 39
,
Figure 40
and
Figure 41
show
methods for calculating the barrier width, but
must remain at least the width of the
fireplace opening.
W
D
Fire
bed
Figure 37
D
Fire
bed
Figure 38
Fire Bed
X
X
Y
X=150mm, less dimension Y
Figure 39
Fire Bed
X
X
Y
X=150mm, less dimension Y
Figure 40
Fire Bed
X
X
X=150mm
Figure 41