background image

Page 8 of 16

507388-01

Issue 1732

Supply and Return Duct(s)

Provide duct(s) sized sufficiently to handle the larger of the 

air volumes for heating or cooling provided by this model.

Connect the supply duct to the top of the unit using canvas 

connections or other flexible connections to prevent noise 

transmission into the duct system.

To connect the return duct to the system, use a straight 

piece of duct 22” wide by 6” deep. Insert the duct into the 

return  opening  in  the  bottom  of  the  unit  and  flange  the 

duct over the existing flanges around the opening inside 

the unit. Make sure that all sides of the duct are flanged 

over to permit removal of the cooling chassis if required. 

Use a flexible connection to attach the remainder of the 

return duct. The return duct should be sealed to the unit 

casing and must terminate outside the space containing 

the furnace.

Adjustments – Heating Section

Temperature Rise

At time of installation, the temperature rise must be 

adjusted to be within the range specified on the unit rating 

plate. See Table 2. Select a lower blower speed to increase 

rise. Select a higher blower speed to reduce rise.

Pressure Regulator

The gas input must not exceed the figures shown on the 

rating plate. The unit is equipped for rated inputs with 

manifold pressures of: 3.5” W.C. for natural gas and 10.5” 

W.C. for propane.

The manifold pressure can be measured by removing the 

pipe plug in the automatic gas valve. Connect a water 

manometer and measure the pressure. See Figure 9.

Only small variations in gas input may be made by adjusting 

the regulator. 

In  no  case  should  the  final  manifold 

pressure vary more than 0.3” W.C. for natural gas or 

0.7” W.C. for propane.

To adjust the regulator, turn the adjusting screw on the 

regulator  clockwise  to  increase  pressure  and  input  or 

counterclockwise  to  decrease  pressure  and  input.  See 

Figure 9.

For  natural  gas  installations,  check  the  burner  rate  by 

observing  the gas meter (making sure that all other gas 

appliances are turned off). The test hand on the meter 

should be timed for at least one revolution. Note the 

number of seconds for one revolution.

BTU/HR 

Input

=

Cubic Feet per 

Revolution

x 3600 x Heating 

Value

# Seconds per 

Revolution

Adjustments – Cooling Section (HWC models)

No adjustments are required or should be attempted 

regarding any of the components of the cooling chassis. 

The  chassis  should  be  checked  to  see  that  none  of  the 

wiring is loose or missing.

Cooling chassis is charged with R410A refrigerant.

Blower

The unit contains a direct-drive, multispeed blower. The 

proper speeds have been preset at the factory for heating 

and cooling. Refer to the wiring diagram or Table 2 for 

recommended heating/cooling speeds for specific models. 

Direct-drive blower motors are permanently lubricated and 

do not require oiling.

Limit Control

A fixed temperature limit control is provided which will shut 

off the gas to the main burners if the unit is overheated for 

any reason. The control must not be adjusted or relocated.

High Altitude Adjustments (U.S. Installations)

Ratings shown on the rating plate are for elevations up to 

2000 feet. For elevations above 2000 feet, ratings should 

be reduced at a rate of 4% for each 1000’ above sea level. 

Refer to the National Fuel Gas Code Z223.1 (latest edition) 

for further explanation.

Installation and Operation in Extremely Cold 

Weather Areas

In areas where extremely cold (below – 20°F) outdoor 

temperatures can be expected, some additional installation 

and operating precautions should be taken. The following 

precautions  are  taken  to  prevent  possible  vent  system 

ice  blockage  that  could  result  in  safety  shutdown  of  the 

burners:

1.  Adjust to the highest achievable temperature rise 

within  the  rise  and  static  pressure  ranges  specified 

on  the  rating  plate.  Depending  on  specific  model,  it 

may be possible to change to a lower heating blower 

speed tap to get a higher temperature rise. This also 

increases comfort.

2. 

Make sure there are no leaks of outside air into the 

return air system.

3.  Keep the outside louver grille as free as possible of 

any ice that may form and obstruct the flue outlet.

Содержание HWC8 V Series

Страница 1: ...cinity of this or any other appliance Such actions could result in property damage personal injury or death WARNING Do not store combustible materials near the furnace or warm air ducts The material may ignite by spontaneous combustion creating a fire hazard WARNING These units are not approved for mobile home applications Such use could result in property damage personal injury or death WARNING I...

Страница 2: ...held to 0 sides 2 top and 1 front and plenum Adequate clearance must be provided to install gas line union and manual shutoff valve as well as providing accessibility for field wiring Do not install directly on carpeting tile or other combustible material other than wood flooring The grille side of the unit may be flush with or extend beyond the face of the exterior wall but should not be recessed...

Страница 3: ...opening with non hardening caulking compound The seal must be weather tight to prevent entrance of moisture and water into the building Assure that the unit is completely seated against the gaskets on the wall sleeve The sleeve is not intended as the sole support for the unit An additional support must be provided near the return opening on the unit for adequate support The use of vibration isolat...

Страница 4: ...a direct vent furnace which obtains all air needed for combustion from outdoors Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure Excessive exposure to contaminated combustion air will result in safety and performance related problems Avoid exposure to the ...

Страница 5: ...maller than the manual valve used Consult the local utility or National Fuel Gas Code for complete details on special requirements in sizing gas piping The units supplied for operation with natural gas contain a gas regulator which must be operated with inlet gas pressures specified on the rating plate If gas line pressure exceeds this figure an additional high pressure regulator must be installed...

Страница 6: ...e minimum circuit ampacity maximum fuse size and minimum voltage Units must never be installed where voltage exceeds 10 over the voltage indicated on the rating plate Units are factory wired for a 230 volt power supply If power supply is 208 volts it will be necessary to change a wire connection on unit transformer from 240 volt terminal to 208 volt terminal as shown on the wiring diagram Failure ...

Страница 7: ... The thermostat must be located on an inside wall where it will not be affected by drafts sunlight or any other heat producing appliances Connect the thermostat wires to the low voltage leads on top of the unit following the wiring diagram attached to the unit The heat anticipator setting is 0 50 amp Air Filter All indoor return air must be filtered A permanent type filter is furnished with the un...

Страница 8: ...hat all other gas appliances are turned off The test hand on the meter should be timed for at least one revolution Note the number of seconds for one revolution BTU HR Input Cubic Feet per Revolution x 3600 x Heating Value Seconds per Revolution Adjustments Cooling Section HWC models No adjustments are required or should be attempted regarding any of the components of the cooling chassis The chass...

Страница 9: ...4 750 36 HWC8 R N 480918A HWC8 R N 480924A 35 65 50 LOW 208 480 N A 465 N A 450 N A 435 N A 230 610 59 590 61 565 63 535 N A MED 208 750 48 715 50 685 52 655 55 230 810 44 770 46 735 49 700 51 HIGH 208 860 42 815 44 770 46 735 49 230 880 41 835 43 790 45 750 48 HWC8 R N 600918A HWC8 R N 600924A 45 75 60 LOW 208 480 N A 465 N A 450 N A 435 N A 230 610 73 590 N A 565 N A 535 N A MED 208 750 60 715 6...

Страница 10: ...rmostat system switch to COOL 3 Set thermostat to temperature desired Heating Sequence of Operation 1 Thermostat calls for heat 2 Combustion blower starts and proper air flow is proven by the pressure switch closing 3 Blower continues to operate for 30 seconds prior to the burners lighting 4 Ignition control begins spark and opens gas valve The burners are lit Ignition is proved through the flame ...

Страница 11: ...rary or short periods of shutdown set the thermostat system switch to OFF For a prolonged period of shutdown set the thermostat system switch to OFF and turn off the electrical power supply and the gas supply to the unit Maintenance Refer to Figure 8 for heating compartment component layout It is recommended that the furnace be inspected annually by a qualified service person ELECTRICAL SHOCK FIRE...

Страница 12: ... brackets The mounting brackets contain pins to locate the assembly and hold it in place after the screws are removed The mounting brackets are hidden until the burner assembly is removed 8 First carefully pull the burner assembly toward you until it is clear of the locating pins in the mounting brackets 9 Then move the assembly away from the vest panel 10 Finally pull the assembly from the unit 1...

Страница 13: ... the unit in case of overheating and automatically resets when temperature falls to an acceptable level It is not field adjustable 1 Remove the control board mounting bracket as described previously 2 Disconnect the two orange and yellow wires at the primary limit switch 3 Remove the three screws securing the primary limit switch to the vest panel 4 For reassembly follow the above steps in reverse...

Страница 14: ...limited to Cleaning the air filter Follow directions noted on the filter and label attached to the access panel Cleaning the condenser coil if covered with any foreign material lint leaves or other obstructions If servicing or major repairs are required the complete chassis can be removed from the unit To remove the chassis 1 Shut off the main power supply 2 Remove filter access panel and panel co...

Страница 15: ...Page 15 of 16 507388 01 Issue 1732 Figure 10 Wiring Diagrams ...

Страница 16: ...Page 16 of 16 507388 01 Issue 1732 Figure 11 ...

Отзывы: