background image

Page 2 of 16

507388-01

Issue 1732

Install operate and maintain unit in accordance with 

manufacturer’s instructions. The State of California has 

determined that this product may contain or produce 

chemicals, in very low doses, which may cause serious 

illness or death. It may also cause cancer, birth defects 

or reproductive harm.

 WARNING

Installation

General

These instructions must be hung on or near the furnace in 

a conspicuous place.

The HWC8 V-Series™ units are self-contained, gas-fired 

heating with electric cooling models. The unit design has 

been certified by Intertek Testing Services for compliance 

with the latest edition of the American National Standard 

ANSI Z21.47 for direct vent central furnaces. The HWC8 

models  are  certified  to  be  in  compliance  with  the  latest 

edition of A.H.R.I. Standard 390. All models are design 

certified  for  heating  operation  when  fired  with  natural  or 

propane gas.

These installation instructions are intended as a general 

guide only, for use by an experienced, qualified contractor.

Inspection

The unit is shipped in one package, completely assembled 

and wired. The Evaporator drain tubing is in the cooling 

compartment behind the filter access panel.

If any damage is found, proper notation should be made on 

the carrier’s freight bill. Damage claims should be filed with 

the carrier as quickly as possible.

Check  the  rating  plate  to  confirm  heating  and  cooling 

capacities. The unit should be operated only with the type 

of gas and electrical supply noted on the rating plate.

In the State of Massachusetts:

This product must be installed by a licensed Plumber 

or Gas Fitter. When flexible connectors are used, the 

maximum length shall not exceed 36”. When lever-type 

gas shutoffs are used, they shall be T-handle type.

 WARNING

NOTE: 

Remove the chassis hold down shipping bracket 

before installation. These brackets are located on the 

outdoor side of the unit below the louver panels.

Location

The  design  is  certified  for  indoor  installation  only.  The 

interior portions of the unit may be surrounded by a closet 

with minimum clearances to combustible material held 

to 0” sides, 2” top, and 1” front and plenum. Adequate 

clearance must be provided to install gas line union and 

manual shutoff valve as well as providing accessibility for 

field wiring. Do not install directly on carpeting, tile, or other 

combustible material other than wood flooring.

The  grille  side  of  the  unit  may  be  flush  with,  or  extend 

beyond, the face of the exterior wall, but should not be 

recessed more than 2” from the face of the building and 

should not be obstructed with trees, landscape materials, 

or building structure.

There is no minimum clearance required on locating the 

unit to an interior corner of a building.

If the unit is to be enclosed, provisions should be made 

allowing access to the indoor side of the unit for changing 

filters and for inspection. At least 29” of unobstructed space 

should be provided in front of the indoor side, whether 

enclosed or not, to permit removal of the cooling chassis 

should repairs or inspection be required.

If the unit is installed in a residential garage, it must be 

located or protected to avoid physical damage by vehicles. 

Unit must be installed so the burners and ignition source 

are not less than 18” (457 mm) above the floor. This unit 

must be installed so that no electrical components are 

exposed to water.

This appliance should be installed in a location such that 

the vent outlet is located in the following manner:
1.  Distances to windows that open, building openings, or 

public walkways should be consistent with the National 

Fuel Gas Code Z223.1.

2.  For U.S. installations, the vent system shall terminate 

a  minimum  horizontal  clearance  of  4’  from  electric 

meters, regulators, and relief equipment. 

3.  Flue products will not cause degradation to building 

materials.

This furnace design is not listed for installation in mobile 

homes, recreational vehicles, or outdoors.

Use of Furnace as a Construction Heater

Allied Air does not recommended the use of these units 

as a construction heater during any phase of construction. 

Very low return air temperature, harmful vapors and 

operation of the unit with clogged or misplaced filters will 

damage the unit.

Units may be used for heating of buildings or structures 

under construction, if the following conditions are met:

•  The unit must be permanently installed per these 

installation instructions.

Содержание HWC8 V Series

Страница 1: ...cinity of this or any other appliance Such actions could result in property damage personal injury or death WARNING Do not store combustible materials near the furnace or warm air ducts The material may ignite by spontaneous combustion creating a fire hazard WARNING These units are not approved for mobile home applications Such use could result in property damage personal injury or death WARNING I...

Страница 2: ...held to 0 sides 2 top and 1 front and plenum Adequate clearance must be provided to install gas line union and manual shutoff valve as well as providing accessibility for field wiring Do not install directly on carpeting tile or other combustible material other than wood flooring The grille side of the unit may be flush with or extend beyond the face of the exterior wall but should not be recessed...

Страница 3: ...opening with non hardening caulking compound The seal must be weather tight to prevent entrance of moisture and water into the building Assure that the unit is completely seated against the gaskets on the wall sleeve The sleeve is not intended as the sole support for the unit An additional support must be provided near the return opening on the unit for adequate support The use of vibration isolat...

Страница 4: ...a direct vent furnace which obtains all air needed for combustion from outdoors Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the heat exchanger resulting in rusting and premature heat exchanger failure Excessive exposure to contaminated combustion air will result in safety and performance related problems Avoid exposure to the ...

Страница 5: ...maller than the manual valve used Consult the local utility or National Fuel Gas Code for complete details on special requirements in sizing gas piping The units supplied for operation with natural gas contain a gas regulator which must be operated with inlet gas pressures specified on the rating plate If gas line pressure exceeds this figure an additional high pressure regulator must be installed...

Страница 6: ...e minimum circuit ampacity maximum fuse size and minimum voltage Units must never be installed where voltage exceeds 10 over the voltage indicated on the rating plate Units are factory wired for a 230 volt power supply If power supply is 208 volts it will be necessary to change a wire connection on unit transformer from 240 volt terminal to 208 volt terminal as shown on the wiring diagram Failure ...

Страница 7: ... The thermostat must be located on an inside wall where it will not be affected by drafts sunlight or any other heat producing appliances Connect the thermostat wires to the low voltage leads on top of the unit following the wiring diagram attached to the unit The heat anticipator setting is 0 50 amp Air Filter All indoor return air must be filtered A permanent type filter is furnished with the un...

Страница 8: ...hat all other gas appliances are turned off The test hand on the meter should be timed for at least one revolution Note the number of seconds for one revolution BTU HR Input Cubic Feet per Revolution x 3600 x Heating Value Seconds per Revolution Adjustments Cooling Section HWC models No adjustments are required or should be attempted regarding any of the components of the cooling chassis The chass...

Страница 9: ...4 750 36 HWC8 R N 480918A HWC8 R N 480924A 35 65 50 LOW 208 480 N A 465 N A 450 N A 435 N A 230 610 59 590 61 565 63 535 N A MED 208 750 48 715 50 685 52 655 55 230 810 44 770 46 735 49 700 51 HIGH 208 860 42 815 44 770 46 735 49 230 880 41 835 43 790 45 750 48 HWC8 R N 600918A HWC8 R N 600924A 45 75 60 LOW 208 480 N A 465 N A 450 N A 435 N A 230 610 73 590 N A 565 N A 535 N A MED 208 750 60 715 6...

Страница 10: ...rmostat system switch to COOL 3 Set thermostat to temperature desired Heating Sequence of Operation 1 Thermostat calls for heat 2 Combustion blower starts and proper air flow is proven by the pressure switch closing 3 Blower continues to operate for 30 seconds prior to the burners lighting 4 Ignition control begins spark and opens gas valve The burners are lit Ignition is proved through the flame ...

Страница 11: ...rary or short periods of shutdown set the thermostat system switch to OFF For a prolonged period of shutdown set the thermostat system switch to OFF and turn off the electrical power supply and the gas supply to the unit Maintenance Refer to Figure 8 for heating compartment component layout It is recommended that the furnace be inspected annually by a qualified service person ELECTRICAL SHOCK FIRE...

Страница 12: ... brackets The mounting brackets contain pins to locate the assembly and hold it in place after the screws are removed The mounting brackets are hidden until the burner assembly is removed 8 First carefully pull the burner assembly toward you until it is clear of the locating pins in the mounting brackets 9 Then move the assembly away from the vest panel 10 Finally pull the assembly from the unit 1...

Страница 13: ... the unit in case of overheating and automatically resets when temperature falls to an acceptable level It is not field adjustable 1 Remove the control board mounting bracket as described previously 2 Disconnect the two orange and yellow wires at the primary limit switch 3 Remove the three screws securing the primary limit switch to the vest panel 4 For reassembly follow the above steps in reverse...

Страница 14: ...limited to Cleaning the air filter Follow directions noted on the filter and label attached to the access panel Cleaning the condenser coil if covered with any foreign material lint leaves or other obstructions If servicing or major repairs are required the complete chassis can be removed from the unit To remove the chassis 1 Shut off the main power supply 2 Remove filter access panel and panel co...

Страница 15: ...Page 15 of 16 507388 01 Issue 1732 Figure 10 Wiring Diagrams ...

Страница 16: ...Page 16 of 16 507388 01 Issue 1732 Figure 11 ...

Отзывы: