035-000029-001
Page 21
HHA IOM 1.4 10/11/2021
NOTES:
1.
This diagram represents the factory-installed electrical option with constant CFM control using the pres-
sure transducer mounted inside the unit. Control loop logic is contained in the VFD programming. VFD
keypad is mounted on outside of unit.
2.
Typical wiring is shown. For exact wiring, refer to the wiring diagram provided with the unit.
3.
Field wiring includes power wiring (upper left hand corner) and low voltage control wiring (terminal block
TB1).
4.
Selection of field provided and installed electrical components is the responsibility of the installer, in-
cluding branch circuit protection and wiring.
5.
To start the fan, connect R and G to energize fan relay FR1. Fan speed is controlled by the VFD using
the pressure transducer signal to maintain a fixed airflow (constant pressure difference across the cali-
brated fan nozzle). See “VFD Parameter” section for airflow adjustment.
6.
The control power (R and C at terminal block TB1) can be used to power a standard 24VAC thermo-
stat , DX relay and up to 2ea control valves.
INSTALLATION-ELECTRICAL (cont’d)
TYPICAL WIRING DIAGRAMS—
Control Option “D”, Constant CFM Control
277V—1
ø
Содержание HHA Series
Страница 2: ...035 000029 001 Page 2 HHA IOM 1 4 10 11 2021 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 24: ...035 000029 001 Page 24 HHA IOM 1 4 10 11 2021 Service Clearances Arrangement B No integral Final Filter...
Страница 25: ...035 000029 001 Page 25 HHA IOM 1 4 10 11 2021 Service Clearances Arrangement D with integral HEPA Filter...
Страница 55: ...035 000029 001 Page 55 HHA IOM 1 4 10 11 2021...
Страница 56: ...035 000029 001 Page 56 HHA IOM 1 4 10 11 2021...
Страница 57: ...035 000029 001 Page 57 HHA IOM 1 4 10 11 2021 B...
Страница 58: ...035 000029 001 Page 58 HHA IOM 1 4 10 11 2021 D...
Страница 63: ...035 000029 001 Page 63 HHA IOM 1 4 10 11 2021 THIS PAGE INTENTIONALLY LEFT BLANK...