background image

010-200002-000

Page 27

HB IOM 1.1 2-13-2014

EXPANSION VALVE PIPING — Distributor nozzles and
expansion valves sized for acceptable performance for a
range of conditions are factory supplied. Use the AHU (air-
handling unit) selection program in the electronic catalog to
select optimal nozzle sizes.
Circuiting selection should result in a circuit loading of 0.8
to 2.0 tons per circuit at design load. Circuit loading must
be evaluated at minimum load to ensure that it does not
drop below 0.6 tons per circuit. Solenoid valves may be
used, if necessary, to shut off the refrigerant supply to indi-
vidual expansion valves to maintain adequate coil circuit
loading.
Compressor minimum unloading and TXV quantity is nec-
essary to determine minimum tonnage per circuit.
Minimum Unloading Equation:

Example:
Condensing Unit:

38ARS012

Minimum Unloading:

33%

Coil:

6 row, 11 FPI, Half Circuit

Coil Tons per Circuit:

1.68

Total TXVs:

2

In the first example we will determine the tons per circuit

when both TXVs are active and the compressor is unload-
ed to its minimum of 33%

= .55 tons per circuit at minimum unloading UNACCEPTA-
BLE

If we install a liquid line solenoid valve before one of the

TXVs and close it so that only one TXV is active when the
compressor is unloaded to its minimum of 33%, we see the
following:

= 1.10 tons per circuit at minimum unloading ACCEPTABLE

There are three different options to control
tons per circuit when using an unloading
compressor. The first is to use drop solenoid
valve control as illustrated above and let the
suction cutoff unloaders “ride” with the load.
The second is to use drop solenoid valve
control as illustrated above with electric un-
loaders and let the control algorithm deter-
mine the combination of solenoid valves and
unloaders to limit tons per circuit to accepta-
ble limits. The third is to limit the minimum
amount of unloading so that tons per circuit
is within acceptable limits.
TXV SENSING BULB—sensing bulb for
TXV is shipped coiled up inside cabinet.
Remove coil connection panel, route sens-
ing bulb out through suction line hole in pan-
el, reinstall panel. Locate sensing bulb on
horizontal section of suction line , and attach
to tubing using copper plated strap. Attach
sensing bulb between but no lower than the
4-o’clock and 8-o’clock positions. Make
sure that there is good contact between the
bulb cylinder and tubing. INSULATE the
sensing bulb to insure that it reads the tem-
perature of the suction line. For dual-circuit
DX coils, make sure to locate the sensing
bulb on the correct suction line.

Electric Heaters —

Electric heaters may be

factory installed or factory-supplied for field
installation. Refer to AEH (auxiliary electric
heat) accessory installation instructions.

All field-installed wiring, including the electri-
cal ground, MUST comply with the National
Electrical Code (NEC) as well as applicable
local codes. In addition, all field wiring must
conform to the Class II temperature limita-
tions described in the NEC.
Refer to INSTALLATION-ELECTRICAL and
following for optional factory-installed motor
start/stop station wiring diagrams.

CAUTION

Use only copper conductors for field
-installed electrical wiring. Unit ter-
minals are not designed to accept
other types of conductors.

WARNING!

To avoid possible injury or death
due to electrical shock, open the
power supply disconnect switch and
secure it in an open position during
installation.

Содержание HB Series

Страница 1: ...zed condensate trap present Is the condensate disposal system operating correctly Is auxiliary external condensate drain pan installed as recommended by IOM not required for valid warranty DX Sys tems...

Страница 2: ...010 200002 000 Page 2 HB IOM 1 1 2 13 2014 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 3: ...it Suspension 7 External Vibration Isolators 7 Ductwork 8 Electrical 9 14 Service Clearance 15 Condensate Drain 16 Mixing Box Actuator 16 17 Mixing Box Air Sensor 18 Mixing Box 18 Mixing Box Linkage 1...

Страница 4: ...ppropriate instructions including but not limited to those instructions supplied with the outdoor unit if applicable Installation must comply with all applicable local codes GENERAL Installation and m...

Страница 5: ...ators are disconnected BE SURE that fans are properly grounded before working on them Failure to follow these warnings could result in per sonal injury or equipment damage DANGER NEVER enter an enclos...

Страница 6: ...ective cover or grease from fan shaft until ready to install sheave Lay rigid temporary protection such as ply wood walkways in unit to prevent damage to insulation or bottom panel during installa tio...

Страница 7: ...entirely through their associated fasteners It is recommended that framing be constructed from angle iron or formed strut materials Fig 3 Unit Suspension With Mixing Boxes HB units sizes 30 80 with mi...

Страница 8: ...nit Attach the other side to the supply ductwork Seal the connec tions using duct mastic or HVAC tape Refer to Figure 5 Supply Ductwork Unit Sizes 60 80 Install supply ductwork by attaching a field pr...

Страница 9: ...alled electric heat ers have fan starter and overload if required located inside the electric heat control box DANGER NEVER enter an enclosed fan cabinet or reach into a unit while the fan is running...

Страница 10: ...used disconnect switch 75VA 24V control transformer fan relay or contactor or starter with overload if required low voltage terminal block and indoor enclosure 3 Typical wiring is shown For exact wir...

Страница 11: ...rangement similar to MSS wiring see typical wiring diagrams previous page may be field provided and installed to allow the customer s con trols to start and stop the fan Selection of field pro vided a...

Страница 12: ...S INSTALLATION ELECTRICAL cont d NOTES 1 Motor Start Stop Station MSS not required when factory installed electric heat is selected The electric heater contains the fan motor starter and low voltage c...

Страница 13: ...S INSTALLATION ELECTRICAL cont d NOTES 1 Motor Start Stop Station MSS not required when factory installed electric heat is selected The electric heater contains the fan motor starter and low voltage c...

Страница 14: ...tage controls with single point line power connection 2 Units will have Full Line Break heater contactor HC1 starting in 2012 See the unit wiring diagram for actual wiring 3 NOT ALL POSSIBLE WIRING AR...

Страница 15: ...010 200002 000 Page 15 HB IOM 1 1 2 13 2014 HB Series Service Clearances...

Страница 16: ...T condensate drain connection Measure maximum design negative static pressure up stream from the fan Referring to Fig 7 height H must be equal to or larger than negative static pressure at design oper...

Страница 17: ...n actuator arm and link age arm on DR4 See Fig 11 Linkage rod may need to be cut to length Ensure actuator arm and linkage arm are parallel 4 Ensure linkage assemblies are properly secured as shown in...

Страница 18: ...to mixed air sensor 6 Place enthalpy sensor shown in Fig 16 in location suitable to meet manufacturer s requirements 7 Connect all sensors to logic module per manufacturer s instructions 8 Test to ens...

Страница 19: ...nstalled directly on the damper shaft if required If a factory supplied actuator is ordered for the mixing box refer to Mix ing Box Actuator 3 Orientate actuator to avoid interference with linkage ass...

Страница 20: ...14 The actuator should now be able to power the dampers fully open and fully closed without interference Adjust linkage assemblies as need Fig 22 Area A Detailed View Fig 23 Area A Detailed View Insta...

Страница 21: ...channel See Fig 24 Adjustable pitch sheaves are installed on the motor shaft 3 Rotating each sheave a half revolution will determine whether the sheave is wobbly or the drive shaft is bent Correct any...

Страница 22: ...determine correct belt tension use the deflection formula given below and the tension data from Fig 26 as follows EXAMPLE Given Belt Span 16 in Belt Cross Section A Super Belt Small Sheave Pitch Diam...

Страница 23: ...o the condensate line between the trap and the gate valve instead of open to the atmosphere Figure 28 illustrates the typical piping at the end of eve ry steam supply main Omitting this causes many fi...

Страница 24: ...or any trap which has provision for passing air The great majority of high pressure return mains terminate in hot wells or deaerators which vent the air Fig 29 Multiple Coil High Pressure Piping NOTES...

Страница 25: ...as an inner tube pierced to facilitate the distribution of the steam along the tube s length The outer tubes are expanded into plate fins The completed assembly includes the supply and condensate head...

Страница 26: ...eaving side See unit label or certified drawing to assure con nection to matching suction and liquid connec tions The lower split of face split coils should be first on last off Row split coils utiliz...

Страница 27: ...drop solenoid valve control as illustrated above with electric un loaders and let the control algorithm deter mine the combination of solenoid valves and unloaders to limit tons per circuit to accepta...

Страница 28: ...ct insulation Remove all construction debris from unit interior Remove walkway before starting unit FILTERS Install unit filters in all filter sections Protect open filters from drywall dust and const...

Страница 29: ...ervoir Method II Make connection to auxiliary drain valves 4 Fill reservoir with any inhibited antifreeze ac ceptable to code and underwriter authority 5 Open service valve and circulate solution for...

Страница 30: ...supply line and the dirt leg ahead of the trap 2 Use a vacuum breaker in the return 3 Do not use overhead returns from the coil A floodback can occur 4 An immersion thermostat to control outdoor air d...

Страница 31: ...lear space 3 Remove the flat coil stubout panel Refer to Figure 35 and 36 Note that there is another coil access panel on the opposite side of the unit SERVICE Coil Drainpan Removal and Reinstallation...

Страница 32: ...l panel Figure 42 and 43 8 Remove coils from unit along with drainpan Drainpan will slide out of unit Figure 44 or 45 To remove coils and drainpan top will need to be lifted up as shown in Figure 40 9...

Страница 33: ...nation up to 24 hours after sampling A low pH and high alkalinity cause system problems even when both values are within ranges shown The term pH refers to the acidity basicity or neutrality of the wa...

Отзывы: