9.6.1

 

Technical data pulse output 

Pulse output class

 

OA (electronic switch) according to EN 1434-2:2007 

Pulse value heat energy 

1 kWh/pulse 

Pulse value volume (optional) 

100 l/pulse 

Peak switching current 

 

300 mA ~/- 

 

Switching voltage, maximum 

 

35 V ~/- 

 

Switching power, maximum 

 

300 mW 

 

Contact isolation 

 

> 10

9

 

Ohm 

 

Contact resistance (on) 

 

max. 25 Ohm 

 

Contact capacity 

 

1.5 pF 

 

Maximum current 

 

120 mA 

 

Withstand voltage (open contact) 

 

350 V ~/- 

 

Closure time 

 

125 ms 

 

Interval between pulses 

 

125 ms

 

10

 

Information Messages  

When the instrument has detected an information message, the message symbol is displayed: 
The specific message can be found at the menu item 8 ‘Information message’ in Level 1/Main loop (see section 7 
“Display”). The instrument recognizes eight message causes, which can also occur in combination with each other. 
The messages are shown on the display. The message code is displayed alternately in binary and hexadecimal form.  

Binary display

 

Description 

Hexadecimal display 

1 at first place 

Low battery 

H 80 

1 at second place 

Check sum error 

H 40 

1 at third place 

E

2

PROM defective 

H 20 

1 at fourth place 

Instrument has been reset 

H 10 

1 at fifth place 

Time-out TDC (Time-to-digital 
converter) 

H 08 

1 at sixth place 

Internal calibration defective 

H 04 

1 at seventh place 

Return flow sensor defective 

H 02 

1 at eighth place 

Forward flow sensor defective 

H 01 

 
Example: Time-out TDC 

(Time-to-digital converter)

 

Message 
 

Lo

b

att

ery

 

Ch

eck

 su

m

 erro

E²P

R

OM

 faul

Rese

 

Tim

e

-o

u

TD

C

 

In

te

rn

al cali

b

rati

o

n

 

erro

Ret

u

rn

 fl

o

senso

fau

lt

 

Fo

rward

 fl

o

w

 

senso

fau

lt

 

 
 
 
 
 
Alternating  hexadecimal 
message displayed (LCD) 

Bit 

Display location 

Alternating binary 
message displayed (LCD) 

 

 

 
When a message appears in the standard display (total heat, or alternating total heat and cooling energy), with the 
exception  of  the  messages  ‘Reset’  (10)  and  ‘Time-out  TDC’  (08)  in  the  case  of  air  in  the  measuring  tube,  the 
instrument must be exchanged and sent to the supplier for examination. 
 

Содержание microCLIMA U

Страница 1: ...guarantee and the approved application of the instrument are no longer valid To achieve measurement stability of the meter is it necessary that the water quality meet the requirements of the AGFW reco...

Страница 2: ...up off the flow sensor For heat meter versions it is recommended to detach the calculator For heat cooling meters the calculator must be detached from the flow sensor 5 Mounting the Temperature Senso...

Страница 3: ...alues that can be shown are divided into three display loops All data is retrieved using the push button next to the display At the start you are automatically in the main loop 1st level By pressing t...

Страница 4: ...alternating with its value Alternatively the total volume or tariff values can be displayed 1 2 16 Monthly values dates alternating with their values Alternatively the total volume or tariff values ca...

Страница 5: ...ata storage E2 PROM daily Display 8 digits special characters Interfaces standard infrared optional M Bus galvanically isolated M Bus galvanically isolated 2 pulse inputs wireless M Bus wireless M Bus...

Страница 6: ...tallations of buildings Part 5 51 Selection and erection of electrical equipment Common rules IEC 60364 5 54 2011 03 Low voltage electrical installations Part 5 54 Selection and erection of electrical...

Страница 7: ...ection 9 4 3 Activation of the radio interface 9 4 1 Technical data radio Frequency 868 MHz Transmission power up to 12 dBm Protocol wireless M Bus based on EN 13757 3 Selectable modes S1 T1 C1 Telegr...

Страница 8: ...us or radio General information about pulse inputs It is important to note that the acknowledged state of the art technology rules and the relevant legal restraints international and local see 9 5 1 R...

Страница 9: ...pulse without unit Installation notes for pulse inputs It is important that the pulse cables not be affected by or exposed to the M Bus voltage Check the polarity of pulse generators with open collect...

Страница 10: ...tely in binary and hexadecimal form Binary display Description Hexadecimal display 1 at first place Low battery H 80 1 at second place Check sum error H 40 1 at third place E2 PROM defective H 20 1 at...

Страница 11: ...being stored A defect on the calculator circuit board Rf sensor fault No calculations are carried out The registers for flow and energy are not being updated no new data is being stored Sensor cable...

Страница 12: ...69168 Wiesloch Baiertal Germany Tel 49 0 6222 9800 0 Fax 49 0 6222 9800 50 E Mail info engelmann de www engelmann de 14 Contact Maddalena S p A Via G B Maddalena 2 4 33040 Povoletto UD Italy Tel 39 0...

Отзывы: