8

EN

5.2 - Adjusting the outlet pressure (Pa)

The outlet pressure Pa (unless specifically requested) is factory-set with the regulator installed as indicated in 3.4 and with the 

adjustment screw (

2

) set approximately at the minimum setting value. The relief valve is set accordingly. 

If the regulator is installed in different positions, check and reset the outlet pressure Pa, and consequently the devices 

incorporated in the regulator;
Adjust the outlet pressure as follows:
• Unscrew the cap (

1

);

• Unscrew the adjustment screw (

2

) and set it to the minimum setting allowed (threaded end of the top cover (

3

));

• Start the system or make sure there is a minimum flow downstream of the regulator;
• To increase the pressure calibration downstream of the regulator, tighten the adjustment screw (

2

) to the desired value. 

Perform the reading with a calibrated pressure gauge, installed downstream of the regulator to at least 5 DN (see example 

in 3.3);

• Screw the cap (

1

) back on and if necessary, seal it in that position using the appropriate seal holes (if any);

• Use pressure outlets (

15

) on the device only for zero flow or very low flow measurements. 

  6.0 - RECOMMENDED PERIODIC CHECKS

• Use a suitable calibrated tool to ensure the bolts are tightened as indicated in 3.2;

• Check the tightness of the flanged/threaded connections on the system;

• Check the tightness and operation of the regulator/relief valve;

The final user or installer is responsible for defining the frequency of these checks based on the severity of the service conditions.

6.1 - CHECK THAT THE RELIEF VALVE IS WORKING PROPERLY

• Start the system as described in point 4.0;

• Slowly close the valve downstream of the regulator;

• Loosen and remove the cap (

1

);

• Use an 8 mm socket spanner to press the adjustment nut (

20

) to increase the pressure Pa above the preset value. Use a 

calibrated pressure gauge for the reading;

• Remove the socket spanner. The generated overpressure will be discharged outwards and the Pa will begin to decrease to 

the relief valve setting value. Relief valve operation is verified;

• Close the cap (

1

);

• Open the relief valve to discharge the created overpressure; 

• Close the relief valve (the regulator goes to the closing pressure) and open the ball valve downstream of the regulator.

 

 7.0 - MAINTENANCE

• No maintenance operations need to be carried out inside the device. If operations must be carried out inside the 

device (changing the spring, replacing the filter, etc.), it is advisable to contact the Technical Department. In any 
case, before carrying out any dismantling operation on the device, make sure that there is no pressurised gas inside. 

8.0 - TRANSPORT, STORAGE AND DISPOSAL

•  During transport the material needs to be handled with care, avoiding any impact or vibrations to the device;
•  If the product has any surface treatments (ex. painting, cataphoresis, etc) it must not be damaged during transport;
•  The transport and storage temperatures must observe the values provided on the rating plate;
•  If the device is not installed immediately after delivery it must be correctly placed in storage in a dry and clean place;
•  In humid facilities, it is necessary to use driers or heating to avoid condensation;
•  At the end of its service life, the product must be disposed of in compliance with the legislation in force in the country where 

this operation is performed.

Содержание FRG/2MCS9

Страница 1: ...GAS PRESSURE REGULATOR FRG RG 2MCS9 Pe 0 5 9 bar DN15 DN 20 DN 25 EN...

Страница 2: ...2 EN INDEX pag English 3 Drawings 10 Flow data table 1 13 Dimensions table 2 14 Regulation spring data table 3 15...

Страница 3: ...if the installation is in a poorly ventilated environment They can also be supplied without the relief valve outlet pressure socket 1 2 KEY TO SYMBOLS ATTENTION Attention is drawn to the technical det...

Страница 4: ...ion RG 2MCS9 Pressure regulator without filter Standard version 3 0 COMMISSIONING THE DEVICE 3 1 OPERATIONS PRIOR TO INSTALLATION It is necessary to close the gas upstream of the device prior to insta...

Страница 5: ...to prevent damage to the flanges during tightening When tightening be careful not to pinch or damage the gasket Tighten the nuts or bolts gradually in a cross pattern see the example at the side Tight...

Страница 6: ...2 EC In particularly critical installation conditions unattended areas poor maintenance or poor ventilation and especially if there are potential sources of ignition and or hazardous equipment near th...

Страница 7: ...ator Open the downstream shut off valve very slowly Check the operation of the regulator 5 0 CALIBRATION Before carrying out the operations make sure that the supplied spring s is are suitable for the...

Страница 8: ...NG PROPERLY Start the system as described in point 4 0 Slowly close the valve downstream of the regulator Loosen and remove the cap 1 Use an 8 mm socket spanner to press the adjustment nut 20 to incre...

Страница 9: ...Manufacturer s name logo and address possible distributor name logo Mod name model of the device followed by the connection diameter PS Allowable pressure Pe Inlet pressure range that product operatio...

Страница 10: ...10 EN fig 1 FRG 2MCS9 RG 2MCS9 8mm For relief valve setting Top part of the regulator with relief valve G 1 4...

Страница 11: ...11 EN fig 2 FRG 2MCS9 RG 2MCS9 DN 15 DN 20 DN 25 Top part of the regulator with or without relief valve RG FRG 2MCS9 Required tool for setting Pa with relief without relief 13mm...

Страница 12: ...ng screws 7 Compensation diaphragm 8 Filter element only on FRG 9 Bottom 10 Bottom fastening screws 11 Centre pin 12 Obturator 13 Bottom sealing O Ring 14 Body 15 Pressure test nipple optional 16 Flan...

Страница 13: ...00 200 160 2 270 340 370 340 340 50 50 2 5 80 100 3 300 300 300 300 300 90 105 150 4 300 300 300 300 300 115 150 230 5 300 300 300 300 300 140 190 290 6 300 300 300 300 300 220 320 320 7 300 300 300 3...

Страница 14: ...ble 2 Overall dimensions in mm RG FRG 2MCS9 Threaded connections Flanged connections A B C DN 15 DN 20 DN 25 120 194 140 DN 25 191 225 140 The dimensions are provided as a guideline they are not bindi...

Страница 15: ...900 MO 2550 4x29x98x8 900 1500 MO 1305 3 5x29 8x98x11 5 1400 2000 MO 2550 4x29x98x8 1800 3600 MO 2590 4 5x29 5x94x10 DIFFERENTIAL RELIEF VALVE SPRINGS 40 200 MO 2155 2x17x29x6 200 800 MO 2155 2x17x29x...

Страница 16: ...oratello 5 6 7 37045 Z A I Legnago VR Italy Unit locale Via M Hack 1 3 5 37045 Z A I Legnago VR Italy Tel 39 0442 23289 Fax 39 0442 27821 http www madas it e mail info madas it We reserve the right to...

Отзывы: