Macurco CD-xx H/MC Manual
REV
–
1.1
[34-2900-0510-8]
21
|
P a g e
4.5.5
Alarm Relay Setting
–
“ArS”
To select the Alarm Relay Setting, in normal mode, push the
Next
button to get to “Con” or the Configuration menu. Then push
the
Enter
button to enter the Con menu. The fifth selection is the “ArS” or Alarm Re
lay Setting. Push
Next
three times to get to
“ArS” then
Enter
. If the display is “dIS” (disabled) push
Next
to change it to 900, 1000, 1100, 1200, …, 4000 (default), …, 4800,
4900, 5000 ppm (flashing) then push
Enter
to confirm the change (solid) and push
Enter
again to return to “ArS” in the Con
menu. Push
Next
until “End” is displayed then push
Enter
to get back to normal operation.
4.5.6
Alarm Relay Configuration
–
“Arc”
To select the Alarm Relay Configuration, in normal mode, push the
Next
button to get to “Con” or the Configuration menu. Then
push the
Enter
button to enter the Con menu. The sixth selection is the “Arc” or Alarm Relay Configuration. Push
Next
four
times to get to “Arc” then
Enter
. If the relay is “nO” (normally open) push
Next
to turn it to “nC” (flashing) then push
Enter
to
confirm the change (solid) and push
Enter
again to return to “Arc” in the Con menu. Push
Next
until “End” is displayed then
push
Enter
to get back to normal operation.
4.5.7
Fan Relay Setting
–
“FrS”
To select the Fan Relay setting, in normal mode, push the
Next
button to get to “Con” or the Configuration menu. Then push the
Enter
button to enter the Con menu. The seventh selection is the “FrS” or Fan Relay setting. Push
Next
five times to get to “FrS”
then
Enter
. If the fan relay is “dIS” (disabled) push
Next
to change it to 600, 700, 800, 900…, 1000 (default)…, 4800, 4900, 5000
ppm (flashing) then push
Enter
to confirm the change (solid) and push
Enter
again to return to “FrS” in the Con menu. Push
Next
until “End” is displayed then push
Enter
to get back to normal operation.
4.5.8
Fan Relay Delay Setting
–
“Frd”
To select the Fan Relay Delay setting, in normal mode, push the
Next
button to get to “Con” or the Configuration menu. Then
push the
Enter
button t
o enter the Con menu. The eighth selection is the “Frd” or Fan Relay Delay. Push
Next
six times to get to
“Frd” then
Enter
. If the delay is “0” (disabled) push
Next
to change it to 1, 3, 5, or 10 minutes (flashing) then push
Enter
to
confirm the change (solid) and push
Enter
again to return to “Frd” in the Con menu. Push
Next
until “End” is displayed then
push
Enter
to get back to normal operation.
4.5.9
Fan Relay Minimum Runtime Setting
–
“Frr”
To select the Fan Relay Minimum Runtime setting, in normal mode, push the
Next
button to get to “Con” or the Configuration
menu. Then push the
Enter
button to enter the Con menu. The ninth selection is the “Frr” or Fan Minimum Run Time. Push
Next
seven times to get to “Frr” then
Enter
. If the runtime is “0” (disabled) push
Next
to change it to 3, 5, 10 or 15 minutes (flashing)
then push
Enter
to confirm the change (solid) and push
Enter
again to return to “Frr” in the Con menu. Push
Next
until “End” is
displayed then push
Enter
to get back to normal operation.
4.5.10
Fan Relay Latching Setting
–
“FrL”
To select the Fan Relay Latching Option, in normal mode, push the
Next
button to get to “Con” or the Configuration menu. Then
push the
Enter
button to enter the Con menu. The tenth selection is the “FrL” or Fan Relay Latching Option.
Push
Next
nine
times to get to “FrL” then
Enter
. If latching is “OFF” push
Next
to turn it to “ON” (flashing) then push
Enter
to confirm the
change (solid) and push
Enter
again to return to “FrL” in the Con menu. Push
Next
until “End” is displayed then push
Enter
to
get back to normal operation.
4.5.11
Trouble Fan Setting
–
“tFS”
To select the Trouble Fan Setting Option, in normal mode, push the
Next
button to get to “Con” or the Configuration menu.
Then push the
Enter
button to e
nter the Con menu. The eleventh selection is the “tFS” or Trouble Fan Setting Option. Push
Next
ten times to get to “tFS” then
Enter
. If Trouble Fan Setting is “OFF” push
Next
to turn it to “ON” (flashing) then push
Enter
to
confirm the change (solid) and push
Enter
again to return to “tFS” in the Con menu. Push
Next
until “End” is displayed then
push
Enter
to get back to normal operation.
Содержание CD Series
Страница 31: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 31 P a g e 9 Appendix B Menu Structure 9 1 Main Menu ...
Страница 32: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 32 P a g e 9 2 Auto Test Menu bUZ ...
Страница 33: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 33 P a g e 9 3 Configuration Menu CON ...
Страница 34: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 34 P a g e ...
Страница 35: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 35 P a g e ...
Страница 36: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 36 P a g e ...
Страница 37: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 37 P a g e ...
Страница 38: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 38 P a g e ...
Страница 39: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 39 P a g e 9 4 Select Test Menu tst ...
Страница 40: ...Macurco CD xx H MC Manual REV 1 1 34 2900 0510 8 40 P a g e 9 5 CAL Menu CD xxMC Only ...