Macurco CD-6B Manual (Rev-1.0) Eng
REV – 1.0
[34-2900-0510-2 ]
26
|
P a g e
•
A1rt
– Alarm 1 Relay Test, energized for 5 seconds, display flashing A1rt
•
A2rt
– Alarm 2 Relay Test, energized for 5 seconds, display flashing A2rt
•
A3rt
– Alarm 3 Relay Test, energized for 5 seconds, display flashing A3rt
•
gtS
– Gas Test, 3 minutes, display flashes between gtS and current gas reading, green LED blinking, relays are
not triggered by gas reading, green LED continues blinking for another minute then becomes solid green
NOTE:
If an alarm relay setting has been disabled “diS”, the test selection will not be displayed in the test menu.
To perform a manual operation test,
1.
From normal operation mode press the
NEXT
button 2 times to get to the Test Mode (tSt).
2.
Press the
ENTER
button once to get into the Test Menu.
3.
Press the
NEXT
button to scroll through the five test options.
4.
Press
ENTER
to initiate the selected test.
5.
Once the test is complete, the display will return to a steady display.
6.
Press
NEXT
until “End” is displayed to exit the test menu.
7.
Press
ENTER
to return to normal mode.
7.2
Calibration Kit
WARNING
The following steps must be performed when conducting a calibration verification test (bump
test) and calibration to ensure proper performance of the monitor. Failure to do so may
adversely affect product performance.
•
When performing a calibration verification test (bump test) and calibration only use
certified calibration gas at the required concentration level.
•
Do not test with expired calibration gas.
•
Do not cover or obstruct display or visual alarm cover.
•
Ensure sensor inlets are unobstructed and are free of debris
Failure to follow instructions outlined in this user manual can result in sickness or death.
A Field Calibration Kit, CD6B-FCK, is needed to complete a field calibration. These are available through local
distribution.
•
Gas cylinder –
o
17L 400 ppm carbon dioxide (CO
2
) in air
o
17L 5% volume carbon dioxide (CO
2
) in air
•
Gas regulator 0.2 LPM
•
About two feet of tubing
•
CD-6-CH calibration hood
•
Carry case
FCK Information
Several detectors can be calibrated with one FCK. The only limitation is the amount of gas in the cylinder. The 17-
liter cylinder has approximately 85 minutes of continuous calibration run time. Replacement cylinders are available.
Содержание CD-6B
Страница 32: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 32 P a g e 9 2 Auto Test bUZ Menu ...
Страница 33: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 33 P a g e 9 3 Configuration CON Menu ...
Страница 34: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 34 P a g e ...
Страница 35: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 35 P a g e ...
Страница 36: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 36 P a g e ...
Страница 37: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 37 P a g e ...
Страница 38: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 38 P a g e ...
Страница 39: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 39 P a g e 9 4 Select Test tst Menu ...
Страница 40: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 40 P a g e 9 5 Calibration CAL Menu ...
Страница 41: ...Macurco CD 6B Manual Rev 1 0 Eng REV 1 0 34 2900 0510 2 41 P a g e 9 6 Sensor Reset SEN Menu ...