14
Network Installation
© 2020 MacroAir Technologies Toll Free: 866 668 3247 Fax: 909 890 2313 www.macroairfans.com
Controller 30 Operation Manual 90-30016-00 Rev A-01 Date: 031920
T-Splice Connection Method for AVD 370 Fans
1.
Take the incoming CAT5e from the
network, the 15ft [4.57m] CAT5e whip
from the fan, and the CAT5e going to
the rest of the network. Give some slack
(no more than 2ft / 0.6m) on each
CAT5e to strip the wires and splice them
together. Run the slack up towards the
ceiling and back down in a horseshoe
shape.
DO NOT roll the excess slack into a circle or coil because this creates a place for the
network to pick up noise on the lines.
2.
Strip jacketing off the three CAT5e
cables and separate each color wire
leaving approximately 2in [5cm] of each
wire exposed including the drain/shield
wire.
3.
Strip approximately 1/2in [1.3 cm] off
each color wire leaving the bare copper
exposed.
4.
Twist the 3 wires of same color from
each CAT5e together.