Industrial HMI Touch Panel Hardware Manual
M2I Corporation
11-35, Simin-daero 327beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do 14055, Korea, Tel: +82-70-465-3366, Fax: +82-31-465-3355, www.m2i.co.kr
15 / 22
6.4.1 RTD Input Contact Terminal
No.
Name
Description
1
RTD0A
PT100 No.0 Channel A Terminal Input (WHITE)
2
RTD0B
PT100 No.0 Channel B Terminal Input (RED)
3
RTD0B’
PT100 No.0 Channel B’ Terminal Input (RED)
4
RTD1A
PT100 No.1 Channel A Terminal Input (WHITE)
5
RTD1B
PT100 No.1 Channel B Terminal Input (RED)
6
RTD1B’
PT100 No.1 Channel B’ Terminal Input (RED)
7
AGND
Analog Ground
8
AGND
Analog Ground
9
AGND
Analog Ground
10
AGND
Analog Ground
6.4.2 RTD Input Terminal Specification
Item
Description
Number of Inputs
2 channels analog RTD Type
Sensor Type and Input Range
PT100 / -200.0 to +850.0°C
DATA Format
16bits Integer
Resolution
0.0312ºC/1bit
Conversion Time
Approx.70ms, All channel @50hz
Module Error
±0.1% Full Scale @25℃, ±0.3% Full Scale @0℃, 60℃
Isolation
Capacitive isolation
Common Type
2 COM (1 common / 1 channel)
System Power Dissipation
Max. 70mA
Field power
N/A
Pin No.
Removable Terminal Block 10P (3.5mm pitch)
* 3-wire Only.
** Compatible only for “PT100”, “PT1000” is not available.
*** A lead wire’s color is defined by IEC 60751-2008 Standard (*Request for Industrial Platinum Temperature
Sensor), and all of wire colors are shown as below.
Unavailable Available Unavailable