background image

WL40EW2F

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-9080-A  P. 6 / 8

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

105 (4.13)

[260 (10.24)]

60 (2.36)

107 (4.21)

107 (4.21)

3 (.12)

3 (.12)

45 (1.77)

[200 (7.87)]

20

(.79)

approx. 2500 (98.4)

ø27

(1.06)

ø3 (.12)

ø1.2 (.05)

36 (1.42)

80 (3.15)

5 (.20)

[155 (6.10)]

 [R165 (6.50)] 

• 

W

ith sleeve antenna

• 

W

ith r

ooft

op antenna

DIN RAIL

35mm wide

DIN RAIL

35mm wide

8 (.31) Hex.

Содержание WL40EW2F

Страница 1: ...t be within 20 to 60 C 4 to 140 F with relative humidity within 10 to 90 RH in order to ensure adequate life span and operation Attach the antenna to the unit Attachment and adjustment of sleeve antenna Loosen the connector See the top right figure and rotate the antenna Holding the antenna vertical tighten the con nector by hand Make sure to fix the antenna firmly Connector Attachment of rooftop ...

Страница 2: ...eping the radiator at least 20 cm or more away from person s body FCC ID 2AOTF 0000001 Contains FCC ID 2AKGW 1TD3016A1 COMPONENT IDENTIFICATION Network Status Indicator LED Power input defers depending on the power input code you select Status Indicator LED Antenna Connector Maintenance Connector Connector for Power Input Power 920Link 920Run CFG 24V 0V NC NC FE1 RJ 45 Modular jack Link Link100 Et...

Страница 3: ...nit side connector MSTBV2 5 5 GF 5 08AU Phoenix Contact Cable side connector TFKC2 5 5 STF 5 08AU Phoenix Contact Power input code R 24 V DC Power input code S 12 V DC 24V 0V NC NC FE1 ID FUNCTION 12V 0V NC NC FE1 ID FUNCTION 24V Power input 24 V 12V Power input 12 V 0V Power input 0 V 0V Power input 0 V NC Not used NC Not used NC Not used NC Not used FE1 Power input earth FE1 Power input earth ...

Страница 4: ...0 0000 0000 Transmitter power output 0 16mW 1mW 20mW 20mW Device type in a network Number of devices in a network Child fixed 1 to 30 devices Child fixed 31 to 60 devices Child fixed 61 to 100 devices Child fixed child moving Child fixed 1 to 30 devices Set network quality Standard recommended Frequency of route switching and delay higher Frequency of route switching and delay highest Standard rec...

Страница 5: ...jp EM 9080 A P 5 8 INSTALLATION DIN RAIL MOUNTING A Hang the upper hook at the back of the unit on the DIN rail B Push the lower part of the unit to fit in the DIN rail A B DEMOUNTING A Pull down the DIN rail adaptor using a minus screw driver B Pull out the lower part of the unit C Remove the upper part from the DIN rail A B C ...

Страница 6: ...8 TERMINAL CONNECTIONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch 105 4 13 260 10 24 60 2 36 107 4 21 107 4 21 3 12 3 12 45 1 77 200 7 87 20 79 approx 2500 98 4 ø27 1 06 ø3 12 ø1 2 05 36 1 42 80 3 15 5 20 155 6 10 R 1 6 5 6 5 0 With sleeve antenna With rooftop antenna DIN RAIL 35mm wide DIN RAIL 35mm wide 8 31 Hex ...

Страница 7: ...FOR NETWORK CONNECTION To configure the settings for the device WL40EW2F via a network a Windows PC which can be connected to the network is required Confirm the settings of destinations such as the PC 1 Connect the device and the PC with a LAN cable STP cable 2 Set PC s IP address 192 168 0 xxx which is not the same as the device example 192 168 0 10 Set subnet mask 255 255 255 0 Factory default ...

Страница 8: ...ead Input Status Status of digital inputs to the slave read only 03 Read Holding Registers General purpose register within the slave read write 04 Read Input Registers Collected data from the field by the slave read only 05 Force Single Coil Digital output from the slave read write 06 Preset Single Registers General purpose register within the slave read write 15 Force Multiple Coils Digital outpu...

Отзывы: