CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2) Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

3) Input:  Check that the input signal is within 0 – 100% of 

the full-scale.

4) Output:  Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

Input and Output 1 of this unit are calibrated at the factory 
to the default setting (1 – 5V input/4 – 20mA output).  You 
do not need any calibration unless you need to change these 
ranges.
Furthermore, the unit is designed to maintain the described  
I/O range setting accuracy (2%: input range setting accura-
cy + output range setting accuracy) even after I/O ranges 
have been changed.  If these I/O errors need to be compen-
sated, adjust the output as explained in the following.
Output 2 of this unit is calibrated at the factory to meet 
the ordered specifications, therefore you usually do not need 
any calibration.
For matching both outputs to a receiving instrument or in 
case of regular calibration, adjust the output as explained 
in the following.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.

1) ZERO:  Apply 0% input and adjust output to 0%.
2) SPAN:  Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-

dure 1) – 3).

5) Go through the same procedure for the output 2.

MAINTENANCE

Regular calibration procedure is explained below:

 

CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 
50%, 75% and 100% input signal.  Check that the output 
signal for the respective input signal remains within accu-
racy described in the data sheet.  When the output is out of 
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.