TERMINAL CONNECTIONS

Connect the unit as in the diagram below or refer to the con-
nection diagram on the side of the unit.

U(+)

V(–)

POWER

10

11

+

OUTPUT 1

7

8

+

3

6

OUTPUT 2

The section enclosed by broken line is only with 2nd output option.

1

2

A

B

B

RTD

4

CHECKING

1)  Terminal wiring:  Check that all cables are correctly con

-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

3)  Input:  Check voltage across the terminal 1 – 2 with a 

sensitive voltmeter.

  (With 20°C or 68°F, approx. 110mV with Pt 100Ω, approx. 

55mV with Pt 50Ω.)

  If RTD wires are broken, the output goes over 100% (be

-

low 0% with downscale) due to burnout function.  Check 

leadwires in such a case.

4)  Output:    Check  that  the  load  resistance  meets  the  de

-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory to meet the ordered 

specifications, therefore you usually do not need any cali-

bration.

The output signal can be finely adjusted to match it to a re

-

ceiving instrument, or to compensate input wire resistance 

when the unit is combined with a zenor barrier.  Follow the 

regular calibration procedure explained below:

 HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 

accuracy level.  Turn the power supply on and warm up for 

more than 10 minutes.

1)  ZERO:  Apply 0% input and adjust output to 0%.

2)  SPAN:  Apply 100% input and adjust output to 100%.

3)  Check Zero adjustment again with 0% input.

4)  When Zero value is changed, repeat the above procedure 

1) – 3).

5)  Go through the same procedure for the Output 2.

MAINTENANCE

Regular calibration procedure is explained below:

 CALIBRATION

Warm up the unit for at least 10 minutes.  Apply 0%, 25%, 

50%,  75%  and  100%  input  signal.    Check  that  the  output 

signal for the respective input signal remains within accu-

racy described in the data sheet.  When the output is out of 

tolerance,  recalibrate  the  unit  according  to  the “ADJUST

-

MENT PROCEDURE” explained earlier.

EXTERNAL DIMENSIONS

  unit: mm (inch)

4

8 7

10

21.5(.87)

88.5 (3.48)

84 (3.31)

10 (.39)

22 (.87)

59 (2.32)

DIN RAIL

35mm wide

[4 (.16)]

11–M3

SCREW

72 (2.83)

29.5 (1.16)

53 (2.09

)

2–4.2x5

(.17x.20)

MTG HOLE

6 (.24) deep

114 (4.49)

11

5

6

1

2

3

9

6 (.23)

• 

When mounting, no extra space is needed between units.