WIRING INSTRUCTIONS

 

SCREW TERMINAL 

Torque: 0.8 N·m

 

SOLDERLESS TERMINAL

Refer to the drawing below for recommended ring tongue 
terminal size.  Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm

2

 (AWG 22 to 16)

Recommended manufacturer: Japan Solderless Terminal 
MFG.Co.Ltd, Nichifu Co.,ltd

6 (.24) max

3.3 (.13) max

mm (inch)

CHECKING

1) Terminal wiring:  Check that all cables are correctly con-

nected according to the connection diagram.

2)  Power input voltage:  Check voltage across the terminal 

10 – 11 with a multimeter.

3) Input:  Check that the input frequency is 30 Hz or less 

for mechanical contact, 10 kHz or less for other types of 

input.   

 

Check also that the input pulse is of 10 msec. or wider 

for mechanical contact, 10 µsec. or wider for other types 

of input. 

4) Output:  Check that the load resistance meets the de-

scribed specifications as shown below.

OUTPUT

OUTPUT LOAD

Low freq. open collector

50 V DC @ 100 mA max.

High freq. open collector

50V DC @ 100 mA max.

Voltage pulse

5V

250 Ω minimum

12V

600 Ω minimum

24V

1200 Ω minimum, output 1
2400 Ω minimum, output 2

Dry contact AC/DC switch 132 V AC @ 200 mA (cosø=1)

30 V DC @ 200 mA (resistive load)

LIGHTNING SURGE PROTECTION

M-System offers a series of lightning surge protector for 
protection against induced lightning surges.  Please contact 
M-System to choose appropriate models.