TR30-G USERS MANUAL EM-8631-G Rev.16
(6) Click on the [Communication] button.
(7) The [Communication] screen is displayed. Click on the [Modbus/TCP slave] button. [Modbus/TCP slave]
screen is displayed.
Please set the parameters by referring to the table below.
Parameter
Description
Default value
Mode
To use the Modbus/TCP slave function, set as [Enable].
Disable
Allow access to internal
registers
To use internal registers, set as [Enable].
Disable
Port address
Set the port address for Modbus/TCP. (0 to 65535)
502
Linger time
Set the communication timeout duration. (0 to 3000 seconds)
180
(8) Once the setup is complete, press the [OK] button and temporarily store the setting.
To activate the setting, return to the [Configuration] and click on the [Upload to device] button.
After changing the setting, turn the power supply to the device OFF and ON.
NOTES
Please see [7.3.7 Modbus/TCP slave] for the register map, internal registers and available
commands.
Configuration
Communication
Modbus/TCP slave
1. Click
2. Click
3. Select [Enable]
4. Enter