R9EWTU
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-6224 Rev.9 P. 14 / 21
■
DEVICE INFORMATION
ADDR.
WORD
PARAMETER
9601
1
Device ID
9901 : R9xWTU
9602
1
Device version
Version number × 100 (e.g. Version 1.00 = 100)
9603
4
Serial No.
Each character is stored in the following address:
Address
Upper Byte
Lower Byte
9603
2nd
1st
9604
4th
3rd
9605
6th
5th
9606
8th
7th
9607
8
Tag name
This register is writable.
Each character is stored in the following address:
Address
Upper Byte
Lower Byte
9607
2nd
1st
9608
4th
3rd
9609
6th
5th
9610
8th
7th
9611
10th
9th
9612
12th
11th
9613
14th
13th
9614
16th
15th
9623
1
Extension function flag
Reading the following values depending upon the function:
0002H : RS-485 (Modbus RTU)
0080H : L
ON
W
ORKS
0100H : CC-Link
2000H : Modbus/TCP
9624
1
Number of discrete input
0 : None
8 : 8 points (with the R9WTU-ED16)
9625
1
Number of discrete output
0 : None
8 : 8 points (with the R9WTU-ED16)
9626
1
Reserved
9627
1
Number of circuits
8 : 8 circuits
16 : 16 circuits (with the R9WTU-EP8)
9628
1
Number of counters
0 : None
8 : 8 points (with the R9WTU-ED16)