R80NCIT1

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7026-B  P. 7 / 15

• Data Error Status

  RX(n+3)0 to RX(n+3)F indicate data error status for each module of R80 series.
  The bit corresponding to such module turns to “1”, as described below.
    R80US4T burnout detecting, or input value error.
    (-15% or less, +115% or more, or lower than lower imit, higher than upper limit of measuring range)
    R80FST4NJ input value error (lower than lower imit, higher than upper limit of measuring range)
    R80YS4T output value error (lower than lower imit, higher than upper limit of measuring range)

     

RX(n+1)0, RX(n+2)0, RX(n+3)0 

R80 series slot 0

     

RX(n+1)1, RX(n+2)1, RX(n+3)1 

R80 series slot 1

     

RX(n+1)2, RX(n+2)2, RX(n+3)2 

R80 series slot 2

 

 

    

:

     

RX(n+1)F, RX(n+2)F RX(n+3)F 

R80 series slot F

I/O DATA DESCRIPTIONS

 

OPERATION IN CASE OF A COMMUNICATION ERROR WITH I/O MODULES

When the communication between the network module and the I/O modules is lost due to an error in an input module, the 
last process values are held until the communication is re-established.

 

MODULE STATUS, ERROR STATUS, DATA ERROR STATUS

0

15

Module 0 (Module address 0)
Module 1 (Module address 1)
Module 2 (Module address 2)
      :
Module 15 (Module address F)

 

ANALOG DATA (16-bit data, models: R80UST4, R80FST4NJ, etc.)

16-bit binary data.
Basically, 0 to 100% of the selected I/O range is converted into 0 to 10000 (binary).
Negative percentage is represented in 2’s complements.

0

15

 

ANALOG DATA (16-bit data, models: R80UST4, etc.)

16-bit binary data.
With °C temperature unit, raw data is multiplied by 10. For example, 25.5°C is converted into 255.
With °F temperature unit, the integer section of raw data is directly converted into the data.  For example, 135.4°F is con-
verted into 135.
Minus temperature is converted into negative values, represented in 2’s complements.

0

15

 

DISCRETE DATA (models: R80DAT16A2, R80DCT16A2, etc.)

0

15

Input 1   (Output 1)
Input 2   (Output 2)
Input 3   (Output 3)
     :               :
Input 16 (Output 16)

0 : OFF
1 : ON 

Содержание R80NCIT1

Страница 1: ...info m system co jp EM 7026 B P 1 15 OPERATING MANUAL POWER NETWORK MODULE CC Link IE TSN MODEL R80NCIT1 CONTENTS BEFORE USE 2 POINTS OF CAUTION 2 INSTALLATION 2 COMPONENT IDENTIFICATION 3 TERMINAL C...

Страница 2: ...DC 10 approx 12W internal power max current 1 6 A Excitation supply excitation for I O module 24V DC 10 operational current 10 A From power supply excitation supply connector via con nector for inter...

Страница 3: ...OFF Link down L ER Red CN2 Receiving Data ON Abnormality receiving data OFF Normality receiving data 1 Setting as reservation area stop linking and etc 2 Host communication error internal bus communic...

Страница 4: ...N No 1 24V Power supply 24V DC 2 0V Power supply 0V DC 3 Excitation supply 24V DC 4 Excitation supply 0V DC 5 FE1 Grounding 1 2 3 4 5 PC CONFIGURATOR The following parameter items can be configured wi...

Страница 5: ...XC SUPPLY 24V 24V 0V FE1 POWER EXC SUPPLY Regarding CN1 and CN2 of RJ 45 connector for CC Link IE TSN network there is no restriction for connection order CONNECTOR CONNECTOR WIRING INSTRUCTIONS TENSI...

Страница 6: ...H1 CH2 CH3 CH4 Module address 3 R80UST4 CH1 CH2 CH3 CH4 CH1 CH2 CH3 CH4 Module address 4 R80YST4N 0 15 RWw n 0 2 4 6 8 10 12 Module address 0 Module address 1 R80DAT16A2 R80DCT16A2 Di16 points Do16 po...

Страница 7: ...TH I O MODULES When the communication between the network module and the I O modules is lost due to an error in an input module the last process values are held until the communication is re establish...

Страница 8: ...GX Works3 REGISTRATION FOR PROFILE This unit supports CC Link Family system profile CSP CSP can be downloaded from the M System s web site https www msystem co jp or CC Link Partner Association s web...

Страница 9: ...on Local Station and Remote Station R30NCIT1 are connected by Ethernet cable CN1 and CN2 of CC Link IE TSN Network RJ 45 modular jacks can be connected in any order Before wiring make sure to turn off...

Страница 10: ...x 81 6 6659 8510 E mail info m system co jp EM 7026 B P 10 15 4 In the following window when Module Label Not use is displayed in Module Setting click Setting Change to open the option window and chan...

Страница 11: ...Double click Module Configuration in the Navigation window to open the Module Configuration window According to the real PLC configuration select the module from POU List of the Element Selection wind...

Страница 12: ...6 6659 8201 Fax 81 6 6659 8510 E mail info m system co jp EM 7026 B P 12 15 7 Set Station Type to Master Station Network No to 1 in Required Settings 8 Click Detailed Setting of Network Configuration...

Страница 13: ...6 B P 13 15 According to the real system configuration select the device from Module List and drag and drop it to the device configura tion diagram Click Close with Reflecting Setting When CSP not reg...

Страница 14: ...7 0063 JAPAN Phone 81 6 6659 8201 Fax 81 6 6659 8510 E mail info m system co jp EM 7026 B P 14 15 Assign link devices RX RY RWr RWw to devices of the CPU unit click Apply to close the window Click 10...

Страница 15: ...u Osaka 557 0063 JAPAN Phone 81 6 6659 8201 Fax 81 6 6659 8510 E mail info m system co jp EM 7026 B P 15 15 11 Click Write to PLC in Online on menu bar to open Online Data Operation window Select Chec...

Отзывы: