R8-YS2
P. 3 / 4
EM-9745 Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
COMPONENT IDENTIFICATION
• Range
Same range for all channels. Use PC Configurator to set
independent ranges per channel.
OUTPUT RANGE
SW2-1
0 − 20 mA DC
OFF
4 − 20 mA DC (*)
ON
• Output at The Loss of Communication
Same output for all channels.
OUTPUT AT THE LOSS OF COMMUNICATION
SW2-5
Output Hold (*)
(last data correctly rerceived is hold)
OFF
Stop output
ON
[Note] For Stop output, output fixed at -5%, 0 mA min. when
configuration mode is DIP switch setting.
Output fixed at scaling value at the loss of communication
when configuration mode is PC.
• Terminator DIP SW
TERMINATOR SW
SW2-6
Without (*)
OFF
With
ON
• Configuration Mode
CONFIGURATION MODE
SW2-8
DIP switch setting (*)
OFF
PC Configurator and communication
ON
[Note] Be sure to set unused SW2-2 through 2-4 and 2-7 to
OFF.
■
PC CONFIGURATOR
The following parameters can be set with using PC Configu-
rator Software (model: R8CFG):
• Output setting by channels (range, scaling, zero/gain ad
-
justments, scaling value at power on, slaling value at the
loss of communication)
• Common setting (loss of internal bus communication de
-
tection time)
Turn SW2-8 ON to allow programming by the PC Configu
-
rator via the Power/Network Module.
Refer to the users manual for the R8CFG for detailed opera
-
tion of the software program.
■
INDICATOR LED
LED
OPERATION
FUNCTION
Status
OFF
Stopping
Green ON
Valid host communication
Green Blinking
Reading/writing configuration
Red ON
Setting error
Red Blinking
Parameter error
Output
Status
OFF
Output data in the range
Red Blinking
Output data out of range
■
OUTPUT CONNECTOR ASSIGNMENT
PIN
ID
FUNCTION
No.
1
+
Output (+)
2
NC
No connection
3
NC
No connection
4
−
Output (−)
1
2
3
4
■
OPERATING MODE
(*) Factory setting
• Module Address
The SW1-1, SW1-2, SW1-3, SW1-4 determines the tenth
place digit, while the SW1-5, SW1-6, SW1-7, SW1-8 does the
ones place digit of the address.
Address is selected between 0 to 31.
(Factory setting: 0)
MODULE ADDRESS
SW1
×10
1
2
3
4
×1
5
6
7
8
0
OFF
OFF
OFF
OFF
1
OFF
OFF
OFF
ON
2
OFF
OFF
ON
OFF
3
OFF
OFF
ON
ON
4
OFF
ON
OFF
OFF
5
OFF
ON
OFF
ON
6
OFF
ON
ON
OFF
7
OFF
ON
ON
ON
8
ON
OFF
OFF
OFF
9
ON
OFF
OFF
ON
AO_I2
AO_I1
8
7
6
5
4
3
2
1
SW1
SW2
On
RUN
Status Indicator LED
Output Status Indicator LED
Internal Bus Connector
Output Connector 1
Output Connector 2
Function Setting
DIP SW
■
FRONT VIEW
■
SIDE VIEW