PC CONFIGURATOR

The following parameter items can be configured with PC Configurator Software (model: R8CFG).
Refer to the users manual of the software for detailed operations.

 

CHANNEL INDIVIDUAL SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

Input Range

-20 to +20 (mA DC)

-20 to +20 (mA DC)

Lower range value

-20.00 to +20.00 (mA)

4.00 (mA)

Upper range value

-20.00 to +20.00 (mA)

20.00 (mA)

Fine zero adjustment

-320.00 to +320.00 (%)

0.00 (%)

Fine gain adjustment

-3.2000 to +3.2000

1.0000

Scaled range Zero

-32000 to +32000

0

Scaled range Span

-32000 to +32000

10000

 

CHANNEL BATCH SETTING

PARAMETER

SETTING RANGE

DEFAULT SETTING

Loss of internal bus communication detection time

0.0 to 99.9 (sec.)

1.0 (sec.)

Moving average (ver. 2.00 or later)

Disable/Enable (8 times)

Disable

Configuration mode

DIP switch (OFF), 
PC (ON)

DIP switch (OFF)

Note: Turn SW4-8 ON to allow programming by the PC Configurator via the Power/Network Module.

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.

 

EXTERNAL DIMENSIONS  unit: mm (inch)

115 (4.53)

6 (.24)

7 (.28)

6 (.24)

7 (.28)

DIN RAIL
(35 mm wide)

[3 (.12)]

[4 (.16)]

12 (.47)

59 (2.32)

55 (2.17)