manualshive.com logo in svg
background image

R8-SS4N

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-9728  Rev.2  P. 3 / 5

COMPONENT IDENTIFICATION

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

RUN

AI_I1

AI_I2

Module Address Setting

Rotary SW

Function Setting

DIP SW

Terminator DIP SW

SW1

x10

1 2 3 4 5 6 7 8

x1

SW2

SW4

SW3

Term

On

On

Status Indicator LED

Input Status Indicator LED

Internal Bus Connector

Input Connectors

   

FRONT VIEW

   

SIDE VIEW

CARD ADD.

AI̲I1

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

 

INDICATOR LED

ID

OPERATION

FUNCTION

Status

OFF

Stopping

Green ON

Valid host communication

Green Blinking

Reading/writing configuration

Red ON

Setting error

Red Blinking

Parameter error

Input

Status

OFF

Input data in the range

Red Blinking

Input data out of range

 

INPUT CONNECTOR ASSIGNMENT

1

2

3

4

PIN

No.

ID

FUNCTION

1

+

Input (+)

2

NC

No connection

3

NC

No connection

4

Input (–)

 

MODULE ADDRESS: SW1, 2

The left switch determines the tenth place digit, while the 
right one does the ones place digit of the module address.
Address is selected between 0 to 30.
(Factory setting: 0)

Module Address Setting (x10) 

Module Address Setting (x1) 

5

4

3

2

1

0

9

8

7

6

5

4

3

2

1

0

9

8

7

6

 

OPERATING MODE

(*) Factory setting

• Input Range: SW4-1, 4-2

Same setting for all channels.  Use PC Configurator to set 
independent ranges per channel.

INPUT RANGE

SW4-1

SW4-2

0 − 20mA DC

OFF

OFF

4 − 20mA DC (*)

ON

OFF

• Configuration Mode: SW4-8

CONFIGURATION MODE

SW4-8

DIP switch setting (*)

OFF

PC Configurator and communication

ON

Note: Be sure to set unused SW4-3 through 4-7 to OFF.

 

TERMINATOR DIP SW: SW3

TERMINATOR SW

SW3

Without (*)

OFF

With

ON

Отзывы: