EM-7803-AK  Rev.4  P. 7 / 8

MODBUS FUNCTION CODES & SUPPORTED CODES

 

Data and Control Functions

CODE

NAME

01

Read Coil Status

Digital output from the slave (read/write) 

02

Read Input Status

Status of digital inputs to the slave (read only) 

03

Read Holding Registers

General purpose register within the slave (read/write) 

04

Read Input Registers

Collected data from the field by the slave (read only) 

05

Force Single Coil

Digital output from the slave (read/write) 

06

Preset Single Register

General purpose register within the slave (read/write) 

08

Diagnostics

11

Fetch Comm. Event Counter

Fetch a status word and an event counter

12

Fetch Comm. Event Log

A status word, an event counter, a message count and a field of event bytes

15

Force Multiple Coils

Digital output from the slave (read/write) 

16

Preset Multiple Registers

General purpose register within the slave (read/write) 

17

Report Slave ID

Slave type/ ‘RUN’ status

 

Exception Codes

CODE

NAME

01

Illegal Function

Function code is not allowable for the slave

02

Illegal Data Address

Address is not available within the slave

03

Illegal Data Value

Data is not valid for the function

 

Diagnostic Subfunctions

CODE

NAME

00

Return Query Data

Loop back test

MODBUS I/O ASSIGNMENT

ADDRESS

DATA TYPE

DATA

Coil (0X)

1 – 16

Digital Output (discrete output of the basic module)

17 – 32

Digital Output (discrete output of the extension module)

Inputs (1X)

1 – 16

Digital Input (discrete input of the basic module)

17 – 32

Digital Input (discrete input of the extension module)

33 – 48

Reserved (unused)

49 – 64

Module Status

65 – 80

Reserved (unused)

Input Registers (3X)

1 – 4

I

Analog Input

5 – 16

----

Reserved (unused)

17 – 24

F

Analog Input

25 – 48

----

Reserved (unused)

Holding Registers (4X)

1 – 2

I

Analog Output

3 – 16

----

Reserved (unused)

17 – 20

F

Analog Output

21 – 48

----

Reserved (unused)

I: Integer, -1500 – +11500 (-15 – +115%)
F: Floating
Note: DO NOT access addresses other than mentioned above. Such access may cause problems such as inadequate operation.

Содержание R7M-DAC16C

Страница 1: ...TIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10 approx 40mA GENERAL PRECAUTIONS Before you remove the unit or...

Страница 2: ...s place digit of the address 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 Node Address Setting x1 Factory setting 00 Node Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch Factory...

Страница 3: ...13 X5 Input 5 5 X6 Input 6 14 X7 Input 7 6 Y0 Output 0 15 Y1 Output 1 7 Y2 Output 2 16 Y3 Output 3 8 Y4 Output 4 17 Y5 Output 5 9 Y6 Output 6 18 Y7 Output 7 TERMINATING RESISTOR To use the terminating...

Страница 4: ...5 20 3 12 5 5 22 DIN RAIL 35 mm wide 54 2 13 17 66 50 1 97 18 5 73 115 4 53 7 M3 SCREW TERMINALS for Modbus POWER 18 M3 SCREW TERMINALS for I O 6 24 6 24 CONNECTION DIAGRAM Note In order to improve E...

Страница 5: ...OFF ON ON Y0 MOMENTARY OUTPUT MODE Y0 and Y1 Y2 and Y3 Y4 and Y5 Y6 and Y7 are respectively combined to realize momentary switching with one shot output Bit 0 2 4 6 are used to control each set of out...

Страница 6: ...4 Unused 15 Unused Momentary Output Mode BIT OUTPUT DATA STATE 0 Y0 1 One shot output Y1 0 One shot output 1 Unused 2 Y2 1 One shot output Y3 0 One shot output 3 Unused 4 Y4 1 One shot output Y5 0 One...

Страница 7: ...ultiple Registers General purpose register within the slave read write 17 Report Slave ID Slave type RUN status Exception Codes CODE NAME 01 Illegal Function Function code is not allowable for the sla...

Страница 8: ...Rev 4 P 8 8 WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable w...

Отзывы: