R7G4HH-A-YVF4
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7777-F Rev.2 P. 8 / 9
COMMUNICATION CABLE CONNECTIONS
Master Module
RXD+
RXD−
TXD+
TXD−
SLD
Slave Module
RXD+
RXD−
TXD+
TXD−
SLD
Slave Module
Terminating
Resistor
Terminating
Resistor
Terminating
Resistor
TXD+
TXD−
RXD+
RXD−
SHIELD
Master Module
TR+
TR−
SLD
Slave Module
TR+
TR−
SLD
Slave Module
Note: Be sure to turn ON the switch of the terminating resistor located at both ends of the modules.
TR+
TR−
SHIELD
•
Full-duplex communication
•
Half-duplex communication
■
MASTER CONNECTION
Terminating
Resistor
MOUNTING REQUIREMENTS
unit: mm (inch)
140 (5.51)
2−M4
WIRING INSTRUCTIONS
■
TORQUE
Wiring screw for separable terminal: 0.5 N∙m
Fixing screw for separable terminal: 0.5 N∙m
■
SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm
2
(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG. Co., Ltd, Nichifu Co., Ltd
6 (.24) max
3.3 (.13) max
mm (inch)
■
HOW TO UNMOUNT THE SEPARABLE TERMINAL
The separable terminal of the unit is 2 piece constructions.
It is possible to remove the terminal by loosening two screws
of terminal alternately.