background image

R7F4HEIP-DC16B

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-8005-C  P. 2 / 7

COMPONENT IDENTIFICATION

IP Address Setting Rotary SW

RJ-45 Modular Jack

Status Indicator LED

PC Configurator Jack

Discrete Output Status Indicator LED

Sensor Exc. / Output Connectors

Power Supply Connector

 

STATUS INDICATOR LED

ID

STATUS

COLOR FUNCTION

PWR ON

Green

The internal power is supplied 
normally.

MS

ON

Green

Operating in a normal condition

Blinking Red

Duplicated IP address,
Internal data error

NS

ON

Green

Link on-line and connections in 
the established state

Blinking

Link on-line but no connections 
in the established state

ON

Red

Duplicated IP address

Blinking

Communication timeout

LNK1 ON

Green

LNK1 is established

LNK2 ON

Green

LNK2 is established

 

DISCRETE OUTPUT STATUS INDICATOR LED

LED green indicators shows the signal status.
  ON  : LED ON
  OFF : LED OFF

 

IP ADDRESS

Set the host address (2-digit hexadecimal number) in the 
IP address using rotary switches SA1 and SA2 for the first 
digit and the second digit, respectively.
When using the host address in the IP address set on the 
PC configurator software (model: R7CFG), set the switches 
to ‘00H’.
When the network address, Subnet Mask, and Default 
Gateway need to be changed, do so on R7CFG.
(Setting range: 00H – FFH)
(Factory setting: 00H)

IP Address   Host Address MSD (×1)

IP Address   Host Address LSD (×10)

012

34

56

789

AB

C

DE

012

34

56

789

AB

C

DE

 

POWER SUPPLY TERMINAL ASSIGNMENT

1 2 3 4 5

1. FE
2. NC
3. NC
4. +24V  
5. 0V

Functional Earth


Power Input (24V DC)

Power Input (0V)

Applicable connector: TFMC1,5 / 5–STF–3,5(Phoenix Contact)
                                    (included in the package)
Applicable wire size: 0.2 − 1.5 mm

2

; stripped length 10 mm

Recommended solderless terminal
• AI0,25-10YE 0.25 mm

2

 (Phoenix Contact)

• AI0,34-10TQ 0.34 mm

2

 (Phoenix Contact)

• AI0,5-10WH 0.5 mm

2

 (Phoenix Contact)

• AI0,75-10GY 0.75 mm

2

 (Phoenix Contact)

• A1-10 1.0 mm

2

 (Phoenix Contact)

• A1,5-10 1.5 mm

2

 (Phoenix Contact)

Содержание R7F4HEIP-DC16B

Страница 1: ...easures to ensure the CE conform ity POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 24V DC rating 24V 10...

Страница 2: ...ows the signal status ON LED ON OFF LED OFF IP ADDRESS Set the host address 2 digit hexadecimal number in the IP address using rotary switches SA1 and SA2 for the first digit and the second digit resp...

Страница 3: ...49 50 51 52 PIN No ID FUNCTION PIN No ID FUNCTION 1 24V1 24V DC 27 24V2 24V DC 2 Y0 Output 0 28 Y8 Output 8 3 24V1 24V DC 29 24V2 24V DC 4 GND1 0V 30 GND2 0V 5 Y2 Output 2 31 Y10 Output 10 6 24V1 24V...

Страница 4: ...ve the upper hook of the unit from the DIN rail 1 2 3 SURFACE MOUNTING 1 Insert the two DIN rail mounter sliders until it clicks once as shown below 1 1 2 Mount the unit with M4 screws referring to th...

Страница 5: ...43 DIN rail 35mm wide 2 4 3 dia 4 deep CONNECTION DIAGRAM Note In order to improve EMC performance bond the FE terminal to ground Caution FE terminal is NOT a protective conductor terminal 1 The netwo...

Страница 6: ...nfigured with the PC configurator software model R7CFG Refer to the users manual of the software for detailed operations CHANNEL BATCH SETTING PARAMETER SETTING RANGE DEFAULT SETTING Output Hold Clear...

Страница 7: ...F4HEIP CONNECTION Enter ping command on the Windows MS DOS as follows C WINDOWS ping Enter IP address in decimal ping with 32 bytes of data Reply from bytes 32 time 10ms TTL 64 Reply from bytes 32 tim...

Отзывы: