Use (e.g.) a shield cover 
when noise leaks through 
the opening.

To external apparatus

Keep the opening

for cabling as small as

possible.

Install an electromagnetically
shielded gasket when 
noise leaks through 
the opening.

Shielding is strengthened 
by using an electro-
magnetically shielded 
control panel.

By connecting the
internal panel plate 
and the panel cover with 
an earth strap, grounding 
may be strengthened and
EMC may be improved.

Ground the control panel 

at low impedance using 

 (e.g.) braided wires.

Keep the opening for 

ventilation as small as

posible.

Attach an electro-
magnetically shielded
filter when noise leaks 
through the opening.

Install the R7C Series inside

a control panel.

Attachment part of earth

clamp should be fixed with 

screw in conduction with the

internal panel plate.

• Points of cautions applicable when installing the R7C Series

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7C-EC16B/UL

Страница 1: ...ed by a Class 2 power sup ply CONFORMITY WITH EU DIRECTIVES The equipment must be mounted inside the instrument panel of a metal enclosure The actual installation environments such as panel con figurations connected devices connected wires may af fect the protection level of this unit when it is integrated in a panel system The user may have to review the CE requirements in regard to the whole sys...

Страница 2: ...2 12 Y3 Output 3 4 Y4 Output 4 13 Y5 Output 5 5 Y6 Output 6 14 Y7 Output 7 6 Y8 Output 8 15 Y9 Output 9 7 YA Output 10 16 YB Output 11 8 YC Output 12 17 YD Output 13 9 YE Output 14 18 YF Output 15 CONNECTING THE EXTENSION MODULE 1 Remove the extension connector cover located at the side of the basic module 2 Connect the extension module 3 Mount the combined module on a DIN rail TERMINAL CONNECTION...

Страница 3: ...V 24V 18 YF WIRING INSTRUCTIONS SCREW TERMINAL Torque 0 5 N m SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size Spade tongue type is also applicable Applicable wire size 0 25 to 1 65 mm2 AWG 22 to 16 Recommended manufacturer Japan Solderless Terminal MFG Co Ltd Nichifu Co Ltd 6 24 max 3 3 13 max mm inch 056 222 38 18 mailbox sentronic com www sentronic com SE...

Страница 4: ...h a thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module to the internal panel plate of the control panel Note If electromagnetic radiation disturbance increases by grounding the FG terminal remove the grounding When painting the internal plate of the co...

Страница 5: ...and the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as posible Attach an electro magnetically shielded filter when noise leaks through the opening Install the R7C Series inside a control panel Attachment part of earth clamp should be fixed with screw...

Страница 6: ...utions are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the signal cables susceptible to the noise Ferrite core can be attached close to the cable outlet of the control panel or close to the I O terminal or connector whichever is more effective Also the i...

Страница 7: ...atus Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To connect with apparatuses outside the control panel via CC Link ground the cable shield using an earth clamp Keep the wires away from each other at both ends of the filter 056 222 38 18 mailbox sentronic...

Отзывы: