background image

R7C-DS4N

EM-7801-BA  P. 8 / 10

Use (e.g.) a shield cover 
when noise leaks through 
the opening.

To external apparatus

Keep the opening

for cabling as small as

possible.

Install an electromagnetically
shielded gasket when 
noise leaks through 
the opening.

Shielding is strengthened 
by using an electro-
magnetically shielded 
control panel.

By connecting the
internal panel plate 
and the panel cover with 
an earth strap, grounding 
may be strengthened and
EMC may be improved.

Ground the control panel 

at low impedance using 

 (e.g.) braided wires.

Keep the opening for 

ventilation as small as

posible.

Attach an electro-
magnetically shielded
filter when noise leaks 
through the opening.

Install the R7C Series inside

a control panel.

Attachment part of earth

clamp should be fixed with 

screw in conduction with the

internal panel plate.

• Points of cautions applicable when installing the R7C Series

056 222 38 18

[email protected]

www.sentronic.com

SENTRONIC

AG

Содержание R7C-DS4N

Страница 1: ...ith its maximum surge voltage 40V or less between lines Rec ommended M System model MDP D24 POWER INPUT RATING OPERATIONAL RANGE Locate the power input rating marked on the product and confirm its ope...

Страница 2: ...ng 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE Factory setting Extension SW1 1 1 2 SW1 1 SW1 2 EXTENSION OFF OFF No extension ON OFF Discrete input 8 or 16 points OFF ON Discret...

Страница 3: ...ce Missing parts of the data sent from the master ON OFF OFF OFF OFF Unable to receive data due to wire breakdown ON OFF ON OFF ON OFF Faulty Baud Rate and or Station Address setting OFF OFF OFF OFF O...

Страница 4: ...SCREW TERMINALS for INPUT 6 24 6 24 CONNECTION DIAGRAM 2 11 3 4 13 5 6 15 7 8 17 9 L0 I0 COM INPUT 0 L1 I1 COM INPUT 1 L2 I2 COM INPUT 2 L3 I3 COM INPUT 3 1 10 SNSR EXC SNSR EXC 4 1 5 2 3 6 7 EXC SUPP...

Страница 5: ...N Analog input 0 Analog input 1 Analog input 2 Analog input 3 RWrn 0 1 2 3 Unused Unused Unused Unused RWwn 0 1 2 3 Interval timed Response X Refresh Data Y RX n 0 F to RX n 0 0 Reserved Status RX n 0...

Страница 6: ...nput 1 ADC error Input 2 ADC error Input 3 ADC error Unused Input range error 15 115 0 Normal 1 Error ADC error no response from ADC 0 Normal 1 Error STATUS Analog input module without extension modul...

Страница 7: ...thick cable to maintain low imped ance at high frequency Use shielded cables for the signals taken out of the control panel Choose a thick and short cable to ground the FG terminal of the R7C module t...

Страница 8: ...the panel cover with an earth strap grounding may be strengthened and EMC may be improved Ground the control panel at low impedance using e g braided wires Keep the opening for ventilation as small as...

Страница 9: ...ns are illustrated in the next page Keep cables as short as possible It prevents noise emissions from the cables and noise overlapping to the cables Attach a ferrite core to reduce noise impact to the...

Страница 10: ...s Keep the cable as short as possible To external apparatus Shielded Cable Earth Clamp Remove a part of the shielded cable cover and ground it to the internal panel plate using an earth clamp To conne...

Отзывы: