EXTERNAL VIEWS

8

67

3

4

5

2 1 0 F

E

D C

B

A

9

• Front View (cover opened)

• Side View

5

6

7

8

1

2

3

4

1

SW3

SW2

SW1

2345678

OFF

ON

0

16

SW3

SW2

SW1

Module Address

Setting

Operating Mode

Setting

Status LED

Power LED

 

INDICATOR LED

ID

COLOR

FUNCTION

Power

OFF

Power supply is off

Green ON

Power supply is on.

Status

OFF

Standing by (at the startup) 
or communication error

Green ON

Normal communication

Green blink

Configuration mode

Red ON

DIP switch error

Red blink
2 sec. interval

Parameter error

Red blink
0.5 sec. interval

Burnout

 

MODULE ADDRESS

Module address is selectable between 0 and 31.  Choose 0 or 
16 with SW1 for offsetting the address selected with SW2 (0 
to F, hexadecimal).
The module’s slot position on the base and the module ad-
dress are not necessarily correlated.

ADDRESS

SW1

SW2

ADDRESS

SW1

SW2

0

0

0

16

16

0

1

0

1

17

16

1

2

0

2

18

16

2

3

0

3

19

16

3

4

0

4

20

16

4

5

0

5

21

16

5

6

0

6

22

16

6

7

0

7

23

16

7

8

0

8

24

16

8

9

0

9

25

16

9

10

0

A

26

16

A

11

0

B

27

16

B

12

0

C

28

16

C

13

0

D

29

16

D

14

0

E

30

16

E

15

0

F

31

16

F

 

OPERATING MODE

(*) Factory setting

• Thermocouple Type

T/C

INPUT 1

INPUT 2

SW3

SW3

1

2

3

4

5

6

K (CA) (*)
E (CRC)

J (IC)

T (CC)

B (RH)

R

S

C (WRe 5-26)

Use PC Configurator Software (model: R6CON) to set N, U, 
L, P (Platinel II) and PR thermocouples.

 = ON, Blank = OFF

• Burnout

BURNOUT

SW3-7

Upscale (*)
Downscale

 = ON, Blank = OFF

• Configuration Mode

CONFIGURATION MODE

SW3-8

DIP SW (*)
PC

 = ON, Blank = OFF